background image

Page 15 

Example −− Suction Line Pipe Sizing

Given:

 71/2 ton condensing unit with evaporator lower

than condenser. Application includes 82 linear feet of pip
ing and 4 ells. There is a 20foot vertical lift and 62 feet of
horizontal run. Refer to figure 15.

Find:

 Select tube size from figure 14.

Solution:

 Select a 11/8 inch O.D. line with 6 psig per 100

feet pressure drop and 2900 fpm velocity. Now, calculate
pressure drop due to the friction to determine if this is a
good selection.

Figure 15

Indoor Coil

Example  Indoor Coil Below Condenser

Suction Line

Suction Riser

Oil Trap

20 FT.

2 FT.

60 FT.

From table 3, four ells

 

at 1.8 equivalent feet each equals

7.2 equivalent feet. When added to the 82 feet of pipe, the
total equivalent feet becomes 89.2 feet (round up to 90
feet).

Multiply 6/100 by 90 equivalent feet to calculate total friction
loss of 5.4 psig.

Use figure 14 to calculate the pressure drop in 25 feet of 11/8
inch line. Multiply 6/100 by 25 feet to calculate friction loss of
1.5 psig. This loss has already been included in the capacity,
so it should be subtracted from the total.

The Btuh capacity lost in the total equivalent length" of the
refrigerant line (using figures 12 and 14) equals 1% X (5.4 −
1.5) X 90,000 = 3510.

Btuh lost = 0.01 x (3.9) x 90,000 = 3510

The capacity loss for the line selected is approximately
3.9%.

The preceding calculation shows that this is a workable
system, but the line will lose capacity and efficiency.

Alternative Sizing: 

Using the same (71/2 ton) example,

this time select 13/8 inch O.D. line. A 13/8 inch O.D. line
with 2 psig per 100 feet pressure drop has 1760 fpm veloc
ity. Now calculate the pressure drop due to friction loss to
determine if this is a better selection.

From figure 3, four ells at 2.4 equivalent feet each equals
9.6 equivalent feet. When added to the 82 feet of pipe, the
total equivalent feet becomes 91.6 feet (round up to 92
feet).

Multiply 2/100 by 92 equivalent feet to calculate total fric
tion loss of 1.8 psig.

Use figure 14 to calculate the pressure drop in 25 feet of 13/8
inch line. Multiply 2/100 by 25 feet to calculate friction loss of
0.5 psig. This loss has already been included in the capacity,
so it should be subtracted from the total.

The Btuh capacity lost in the total equivalent length" of the
refrigerant line (using figures 12 and 14) equals 1% X (1.8 −
0.5) X 90,000 = 1170.

Btuh lost = 0.01 x (1.3) x 90,000 = 1170

The capacity loss for the line selected is approximately
1.3%.

The conditions in this example will allow either 11/8 inch or
13/8 inch suction line to be used, since capacity loss is
minimized and velocity is sufficient to return oil to the com
pressor.

Double Suction Risers

If the condensing unit is equipped to run with a capacity re
duction of less than 50 percent, suction lines can generally
be sized in accordance with the previous sections. If the
suction velocity is high enough to entrain oil when the unit is
operating at reduced capacity, double suction risers are
generally unnecessary.
However, suction−type hot gas bypass kits reduce the
unit’s capacity and suction line refrigerant velocity, and
therefore, double suction risers are required in these
cases.

In general, double suction risers are necessary any time the
minimum load on the compressor does not create sufficient
velocity in vertical suction risers to return oil to the compres
sor. Double suction risers are also generally required any
time the pressure drop or velocity in a single suction riser is
excessive.

Figure 16 shows a simplified example of a double suction
riser installation. A trap is installed between the two risers
as shown. During partial load operation when gas velocity
is not sufficient to return oil through both risers, the trap
gradually fills with oil until the second riser is sealed off.
When this happens, the vapor travels up the first riser only.

With only the first riser being used, there is enough velocity
to carry the oil. This trap must be close coupled to limit the
oil holding capacity to a minimum. Otherwise, the trap
could accumulate enough oil on a partial load to seriously
lower the compressor crankcase oil level.

Summary of Contents for HS29-072

Page 1: ...ting 7 Electrical 7 Plumbing 10 Service Valves 17 Leak Testing 18 Evacuation Dehydration 18 Start Up 19 Charging 20 System Operation 21 Maintenance 21 Start Up Performance Check List 22 Shipping Packi...

Page 2: ...et Air Inlet Air AA BB CC DD Center Of Gravity EE FF AA BB CC DD Center Of Gravity EE FF Compressor A 3 1 4 83 34 864 B Control Box Access Side View Lifting Holes For Rigging Forklift Slots Both Sides...

Page 3: ...l Outdoor Fans And Guards 2 Control Box Lifting Holes For Rigging Forklift SlotS Both Sides Discharge Air Inlet Air Electrical Inlets Either Side Liquid Line Either Side 1 7 16 37 6 5 8 168 4 3 8 111...

Page 4: ...lve low pressure switch S87 low ambient switch S11 fan guard compressor B1 liquid line service valve HS29 120 Unit Parts Arrangement Figure 2 condenser fan motor B4 B5 control box low ambient switch S...

Page 5: ...C1 minimum run timer DL33 outdoor fan relay K10 latching relay K167 ground lug HS29 120 Control Box Arrangement Figure 4 contactor K1 low ambient thermostat S41 capacitor C1 C2 latching relay K167 ou...

Page 6: ...ve grade to allow water to drain adequately Locate the top of the slab so that run off water from higher ground will not collect around the unit Roof Mounting Install the unit at a minimum of 4 inches...

Page 7: ...y and maximum overcurrent protection size WARNING Unit must be grounded in accordance with national and local codes Electric Shock Hazard Can cause injury or death Line Voltage Knockouts are provided...

Page 8: ...Page 8 Typical Unit Wiring Diagram HS29 072 090 Figure 8...

Page 9: ...Page 9 Typical Unit Wiring Diagram HS29 120 Figure 9...

Page 10: ...elihood of slugging is greatly increased if the lines are over 50 feet 15 m An incremental increase in liquid line size results in a 40 to 50 percent increase in liquid refriger ant to fill the line T...

Page 11: ...2 1 5 1 0 9 8 7 6 5 4 3 2 HCFC 22 Liquid Line Pressure Drop lbs 100 Feet NOTE Shaded area represents unacceptable velocity range Figure 10 12 5 40 30 20 15 40 30 20 15 EXAMPLE 10 TON UNIT 5 8 IN O D...

Page 12: ...e drop due to friction and the pressure drop due to vertical lift then add the two Pressure drop due to friction Pressure drop due to vertical lift Pressure drop in the liquid line You must consider t...

Page 13: ...00 fpm velocity for oil entrainment In order to ensure oil entrainment suction risers require a mini mum velocity of 1200 fpm 1500 fpm is preferred re gardless of the length of the riser Figure 14 ill...

Page 14: ...0 9 8 7 6 5 4 3 2 1 5 1 0 9 8 7 6 5 4 3 2 HCFC 22 Suction Line Pressure Drop lbs 100 Feet NOTE Shaded area denotes unacceptable velocity range Figure 14 40 30 20 15 40 30 20 15 EXAMPLE 10 TON UNIT 1 3...

Page 15: ...ss of 1 8 psig Use figure 14 to calculate the pressure drop in 25 feet of 1 3 8 inch line Multiply 2 100 by 25 feet to calculate friction loss of 0 5 psig This loss has already been included in the ca...

Page 16: ...ells Find Select tube sizes for horizontal runs and risers fig ure 14 Determine if double suction risers are necessary Size the double suction riser for proper system perfor mance Solution Size each s...

Page 17: ...psig The total pressure drop for the riser is equal to the average of the pressure drop in both risers 1 4 B riser drop 1 26 A riser drop 2 66 2 66 2 1 33 average pressure drop through A and B risers...

Page 18: ...Schrader valve core is present in this valve A cap is also provided to seal off the service port The valve is not re buildable so it must always be replaced if failure has oc curred Opening the Suctio...

Page 19: ...the manifold gauge set to the service valve ports as follows D low pressure gauge to suction line service valve D high pressure gauge to liquid line service valve 3 Purge the system of dry air helium...

Page 20: ...isted on the unit nameplate If it is not do not start the equipment until you have consulted the power company and the volt age condition has been corrected 5 To start the unit set the thermostat for...

Page 21: ...1 105_F 40_C 298 71 308 82 314 77 290 73 115_F 46_C 333 72 342 83 352 79 328 74 HS29 072 tested with CB30U 65 Pressure shown is with typical 5 ton indoor coil match up HS29 072 and HS29 090 tested wit...

Page 22: ...time control This control prevents the compressor from short cycling and ensures that the oil returns to the compressor properly When a cooling cycle begins the run time control keeps the compressor o...

Page 23: ...al ____________ Start Up Performance Check List HS29 072 090 120 Job Name Job Location Installer Unit Model No Nameplate Voltage Minimum Circuit Ampacity Maximum Overcurrent Protection Size Refrigeran...

Reviews: