background image

Page 17 

Size large riser
(Riser carrying largest part of load)

The larger line carries 6.5 tons capacity at full load. Select
from figure 14 a 11/8 inch O.D. line (smallest line with ac
ceptable velocity). When operating at 6.5 tons capacity,
this line will operate at 2500 fpm and will produce 4.5 psig
drop per 100 feet.

Putting the Segments Together

Next, you must determine if the line sizes you selected will
result in satisfactory pressure drop between the condens
ing unit and the evaporator

.

Start by finding the total equivalent feet of the large (B) ris
er. See figure 18. Fifteen feet of pipe, plus two tees (branch
side of tee at 4.5 equivalent feet each), plus four ells (1.8
equivalent feet each) = 31.2 equivalent feet length:

15 + 9 (two 4.5 foot tees) + 7.2 (four 1.8 foot ells ) = 31.2

Now, find the total equivalent feet of the small (A) riser. See
figure 18. Fifteen feet of pipe, plus one ell (1.5 equivalent
feet), plus one tee (branch side of tee at 3.5 equivalent
feet), plus one tee (line side of tee at 1.0 equivalent feet) =
21.0 equivalent feet length:

15 + 1.5 + 3.5 + 1.0 = 21.0

Use the total equivalent length of each riser to compute the
pressure drop of each riser. For the large (B) riser, 11/8
inch O.D. suction line with 6.5 tons capacity has 4.5 psig
drop per 100 feet. Multiply (4.5/100) by 31.2 equivalent feet
to calculate the total friction loss of 1.4 psig.

(4.5 

 100) X 31.2 = 1.4

For the small (A) riser, a 7/8 inch O.D. suction line with 3.5
tons capacity has 6 psig drop per 100 feet. Multiply (6/100)
by 21 equivalent feet to calculate the total friction loss of
1.26 psig:

(6 

 100) X 21 = 1.26 psig.

The total pressure drop for the riser is equal to the average
of the pressure drop in both risers:

1.4 (B riser drop) + 1.26 (A riser drop) = 2.66

2.66 

 2 = 1.33

(average pressure drop through A
and B risers)

Find the pressure drop for the horizontal run of pipe. A
13/8 inch pipe at 10 tons capacity and has 3.3 psig drop
per 100 feet. Multiply 3.3/100 by 61 equivalent feet to cal
culate the total friction loss of 2.01 psig:

3.3 

 100 X 61 = 2.01

Add the pressure drop through the risers to the pressure
drop through the horizontal run to find the total pressure
drop for the system:

2.01 psig (horiz. run) + 1.33 psig (avg. riser) = 3.34

Use figure 14 to calculate the pressure drop in 25 feet of
13/8 inch line. Multiply 3.3/100 by 25 feet to calculate the
friction loss of 0.825 psig.

3.3 

 100 X 25 = 0.825

The Btuh capacity lost in the total equivalent length"
of the refrigerant line (using figures 12 and 14) = 1% x
(3.34 − 0.825) x 120,000:

Btuh lost = 0.01 x (2.515) x 120,000 = 3018

Capacity loss for the line selected is approximately 2.5 per
cent.

Service Valves

The liquid line and suction line service valves and gauge
ports are accessible inside the unit. These gauge ports are
used for leak testing, evacuating, charging, and checking
the charge. Condensing unit, lines, and evaporator need to
be evacuated.

Liquid Line Service Valve

HS29−072/090/120 units use the liquid line service valve
shown in figure 19. A Schrader valve core is factory
installed. A service port cap is supplied to protect the
Schrader valve from contamination and serve as the pri
mary leak seal.

Accessing the Schrader Valve:

 1 − Remove service port cap with an adjustable wrench.

 2 − Connect gauge to the service port.

 3 − When testing is complete, replace service port cap.

Tighten finger tight, then tighten an additional 1/6 turn.

Summary of Contents for HS29-072

Page 1: ...ting 7 Electrical 7 Plumbing 10 Service Valves 17 Leak Testing 18 Evacuation Dehydration 18 Start Up 19 Charging 20 System Operation 21 Maintenance 21 Start Up Performance Check List 22 Shipping Packi...

Page 2: ...et Air Inlet Air AA BB CC DD Center Of Gravity EE FF AA BB CC DD Center Of Gravity EE FF Compressor A 3 1 4 83 34 864 B Control Box Access Side View Lifting Holes For Rigging Forklift Slots Both Sides...

Page 3: ...l Outdoor Fans And Guards 2 Control Box Lifting Holes For Rigging Forklift SlotS Both Sides Discharge Air Inlet Air Electrical Inlets Either Side Liquid Line Either Side 1 7 16 37 6 5 8 168 4 3 8 111...

Page 4: ...lve low pressure switch S87 low ambient switch S11 fan guard compressor B1 liquid line service valve HS29 120 Unit Parts Arrangement Figure 2 condenser fan motor B4 B5 control box low ambient switch S...

Page 5: ...C1 minimum run timer DL33 outdoor fan relay K10 latching relay K167 ground lug HS29 120 Control Box Arrangement Figure 4 contactor K1 low ambient thermostat S41 capacitor C1 C2 latching relay K167 ou...

Page 6: ...ve grade to allow water to drain adequately Locate the top of the slab so that run off water from higher ground will not collect around the unit Roof Mounting Install the unit at a minimum of 4 inches...

Page 7: ...y and maximum overcurrent protection size WARNING Unit must be grounded in accordance with national and local codes Electric Shock Hazard Can cause injury or death Line Voltage Knockouts are provided...

Page 8: ...Page 8 Typical Unit Wiring Diagram HS29 072 090 Figure 8...

Page 9: ...Page 9 Typical Unit Wiring Diagram HS29 120 Figure 9...

Page 10: ...elihood of slugging is greatly increased if the lines are over 50 feet 15 m An incremental increase in liquid line size results in a 40 to 50 percent increase in liquid refriger ant to fill the line T...

Page 11: ...2 1 5 1 0 9 8 7 6 5 4 3 2 HCFC 22 Liquid Line Pressure Drop lbs 100 Feet NOTE Shaded area represents unacceptable velocity range Figure 10 12 5 40 30 20 15 40 30 20 15 EXAMPLE 10 TON UNIT 5 8 IN O D...

Page 12: ...e drop due to friction and the pressure drop due to vertical lift then add the two Pressure drop due to friction Pressure drop due to vertical lift Pressure drop in the liquid line You must consider t...

Page 13: ...00 fpm velocity for oil entrainment In order to ensure oil entrainment suction risers require a mini mum velocity of 1200 fpm 1500 fpm is preferred re gardless of the length of the riser Figure 14 ill...

Page 14: ...0 9 8 7 6 5 4 3 2 1 5 1 0 9 8 7 6 5 4 3 2 HCFC 22 Suction Line Pressure Drop lbs 100 Feet NOTE Shaded area denotes unacceptable velocity range Figure 14 40 30 20 15 40 30 20 15 EXAMPLE 10 TON UNIT 1 3...

Page 15: ...ss of 1 8 psig Use figure 14 to calculate the pressure drop in 25 feet of 1 3 8 inch line Multiply 2 100 by 25 feet to calculate friction loss of 0 5 psig This loss has already been included in the ca...

Page 16: ...ells Find Select tube sizes for horizontal runs and risers fig ure 14 Determine if double suction risers are necessary Size the double suction riser for proper system perfor mance Solution Size each s...

Page 17: ...psig The total pressure drop for the riser is equal to the average of the pressure drop in both risers 1 4 B riser drop 1 26 A riser drop 2 66 2 66 2 1 33 average pressure drop through A and B risers...

Page 18: ...Schrader valve core is present in this valve A cap is also provided to seal off the service port The valve is not re buildable so it must always be replaced if failure has oc curred Opening the Suctio...

Page 19: ...the manifold gauge set to the service valve ports as follows D low pressure gauge to suction line service valve D high pressure gauge to liquid line service valve 3 Purge the system of dry air helium...

Page 20: ...isted on the unit nameplate If it is not do not start the equipment until you have consulted the power company and the volt age condition has been corrected 5 To start the unit set the thermostat for...

Page 21: ...1 105_F 40_C 298 71 308 82 314 77 290 73 115_F 46_C 333 72 342 83 352 79 328 74 HS29 072 tested with CB30U 65 Pressure shown is with typical 5 ton indoor coil match up HS29 072 and HS29 090 tested wit...

Page 22: ...time control This control prevents the compressor from short cycling and ensures that the oil returns to the compressor properly When a cooling cycle begins the run time control keeps the compressor o...

Page 23: ...al ____________ Start Up Performance Check List HS29 072 090 120 Job Name Job Location Installer Unit Model No Nameplate Voltage Minimum Circuit Ampacity Maximum Overcurrent Protection Size Refrigeran...

Reviews: