background image

Page 19 

 2 − Open the high pressure side of the manifold to allow

the HCFC22 into the line set and indoor unit. Weigh in
a trace amount of HCFC22.

 [A trace amount is a maxi

mum of 2 ounces (57 g) refrigerant or 3 pounds (31
kPa) pressure]. 

Close the valve on the HCFC22 cylin

der and the valve on the high pressure side of the man
ifold gauge set. Disconnect HCFC22 cylinder.

 3 − Connect  a  cylinder  of  nitrogen  (that  has  a  pressure

regulating valve) to the center port of the manifold
gauge set.

 4 − Connect the high pressure hose of the manifold gauge

set to the service port of the suction valve.

NOTE − Normally the high pressure hose is connected
to the liquid line port. However, connecting it to the suc
tion port more effectively protects the manifold gauge
set from high pressure damage.

 5 − Adjust the nitrogen pressure to 150 psig (1034 kPa).

Open the valve on the high side of the manifold gauge
set which will pressurize the line set and indoor unit.

 6 − After a few minutes, open a refrigerant port to ensure

that the amount of refrigerant you added is large
enough to be detected. (Amounts of refrigerant will
vary with line lengths.) Check all joints for leaks. Purge
the nitrogen and HCFC22 mixture. Correct any leaks
and recheck.

Evacuation & Dehydration

IMPORTANT

Units are shipped with a holding charge of dry air
and helium which must be removed before the unit
is evacuated and charged with refrigerant.

Evacuating the system of noncondensables is critical for
the unit to operate properly. Noncondensables are gases
that will not condense under temperatures and pressures
which are present while an air conditioning system is oper
ating. Noncondensables and water vapor combine with re
frigerant to produce substances that corrode copper piping
and compressor parts.

  1 −Remove the suction valve actuation/stem cap. Turn

the stem unit it is fully open. To open the liquid valve,
remove cap and turn the valve stem until it is fully open.

  2 −Connect the manifold gauge set to the service valve

ports as follows:
 

low pressure gauge to 

suction 

line service valve

 

high pressure gauge to 

liquid 

line service valve

  3 −Purge the system of dry air, helium, or nitrogen.

IMPORTANT

Never use compliant scroll compressors (as with
any refrigerant compressor) to evacuate a refrigera
tion or air conditioning system!

NOTE − Use a temperature vacuum gauge, mercury
vacuum, or thermocouple gauge. The usual Bourdon
tube gauges are inaccurate in the vacuum range.

  4 −Connect the vacuum pump (with vacuum gauge) to the

center port of the manifold gauge set.

  5 −Open both manifold valves and start the vacuum pump.

  6 −Evacuate the line set, outdoor unit, and the indoor unit

to an absolute pressure of 23 mm (23,000 microns) of
mercury or approximately 1 inch of mercury. During the
early stages of evacuation, close the manifold gauge
valve at least once to determine if there is a rapid rise in
absolute pressure. A rapid rise in pressure indicates a
relatively large leak. If this occurs, repeat the leak test.

NOTE − The term 

absolute pressure

 means the total

actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pres
sure in a vacuum is equal to atmospheric pressure mi
nus vacuum pressure.

  7 −When the absolute pressure reaches 23 mm (23,000

microns) of mercury, do the following:
 

D

close the manifold gauge valves

 

D

turn off the vacuum pump

 

D

disconnect the manifold gauge center port hose 
from the vacuum pump

Attach the manifold center port hose to a nitrogen cyl
inder with the pressure regulator set to 150 psig (1034
kPa) and purge the hose. Open the manifold gauge
valves to break the vacuum in the line set and indoor
unit. Close the manifold gauge valves.

CAUTION

Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use compres
sors to evacuate a system.
Extremely low vacuums can cause internal arcing
and compressor failure.
Damage caused by deep vacuum operation will void
warranty.

  8 −Shut off the nitrogen cylinder and remove the manifold

gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and the indoor unit.

Summary of Contents for HS29-072

Page 1: ...ting 7 Electrical 7 Plumbing 10 Service Valves 17 Leak Testing 18 Evacuation Dehydration 18 Start Up 19 Charging 20 System Operation 21 Maintenance 21 Start Up Performance Check List 22 Shipping Packi...

Page 2: ...et Air Inlet Air AA BB CC DD Center Of Gravity EE FF AA BB CC DD Center Of Gravity EE FF Compressor A 3 1 4 83 34 864 B Control Box Access Side View Lifting Holes For Rigging Forklift Slots Both Sides...

Page 3: ...l Outdoor Fans And Guards 2 Control Box Lifting Holes For Rigging Forklift SlotS Both Sides Discharge Air Inlet Air Electrical Inlets Either Side Liquid Line Either Side 1 7 16 37 6 5 8 168 4 3 8 111...

Page 4: ...lve low pressure switch S87 low ambient switch S11 fan guard compressor B1 liquid line service valve HS29 120 Unit Parts Arrangement Figure 2 condenser fan motor B4 B5 control box low ambient switch S...

Page 5: ...C1 minimum run timer DL33 outdoor fan relay K10 latching relay K167 ground lug HS29 120 Control Box Arrangement Figure 4 contactor K1 low ambient thermostat S41 capacitor C1 C2 latching relay K167 ou...

Page 6: ...ve grade to allow water to drain adequately Locate the top of the slab so that run off water from higher ground will not collect around the unit Roof Mounting Install the unit at a minimum of 4 inches...

Page 7: ...y and maximum overcurrent protection size WARNING Unit must be grounded in accordance with national and local codes Electric Shock Hazard Can cause injury or death Line Voltage Knockouts are provided...

Page 8: ...Page 8 Typical Unit Wiring Diagram HS29 072 090 Figure 8...

Page 9: ...Page 9 Typical Unit Wiring Diagram HS29 120 Figure 9...

Page 10: ...elihood of slugging is greatly increased if the lines are over 50 feet 15 m An incremental increase in liquid line size results in a 40 to 50 percent increase in liquid refriger ant to fill the line T...

Page 11: ...2 1 5 1 0 9 8 7 6 5 4 3 2 HCFC 22 Liquid Line Pressure Drop lbs 100 Feet NOTE Shaded area represents unacceptable velocity range Figure 10 12 5 40 30 20 15 40 30 20 15 EXAMPLE 10 TON UNIT 5 8 IN O D...

Page 12: ...e drop due to friction and the pressure drop due to vertical lift then add the two Pressure drop due to friction Pressure drop due to vertical lift Pressure drop in the liquid line You must consider t...

Page 13: ...00 fpm velocity for oil entrainment In order to ensure oil entrainment suction risers require a mini mum velocity of 1200 fpm 1500 fpm is preferred re gardless of the length of the riser Figure 14 ill...

Page 14: ...0 9 8 7 6 5 4 3 2 1 5 1 0 9 8 7 6 5 4 3 2 HCFC 22 Suction Line Pressure Drop lbs 100 Feet NOTE Shaded area denotes unacceptable velocity range Figure 14 40 30 20 15 40 30 20 15 EXAMPLE 10 TON UNIT 1 3...

Page 15: ...ss of 1 8 psig Use figure 14 to calculate the pressure drop in 25 feet of 1 3 8 inch line Multiply 2 100 by 25 feet to calculate friction loss of 0 5 psig This loss has already been included in the ca...

Page 16: ...ells Find Select tube sizes for horizontal runs and risers fig ure 14 Determine if double suction risers are necessary Size the double suction riser for proper system perfor mance Solution Size each s...

Page 17: ...psig The total pressure drop for the riser is equal to the average of the pressure drop in both risers 1 4 B riser drop 1 26 A riser drop 2 66 2 66 2 1 33 average pressure drop through A and B risers...

Page 18: ...Schrader valve core is present in this valve A cap is also provided to seal off the service port The valve is not re buildable so it must always be replaced if failure has oc curred Opening the Suctio...

Page 19: ...the manifold gauge set to the service valve ports as follows D low pressure gauge to suction line service valve D high pressure gauge to liquid line service valve 3 Purge the system of dry air helium...

Page 20: ...isted on the unit nameplate If it is not do not start the equipment until you have consulted the power company and the volt age condition has been corrected 5 To start the unit set the thermostat for...

Page 21: ...1 105_F 40_C 298 71 308 82 314 77 290 73 115_F 46_C 333 72 342 83 352 79 328 74 HS29 072 tested with CB30U 65 Pressure shown is with typical 5 ton indoor coil match up HS29 072 and HS29 090 tested wit...

Page 22: ...time control This control prevents the compressor from short cycling and ensures that the oil returns to the compressor properly When a cooling cycle begins the run time control keeps the compressor o...

Page 23: ...al ____________ Start Up Performance Check List HS29 072 090 120 Job Name Job Location Installer Unit Model No Nameplate Voltage Minimum Circuit Ampacity Maximum Overcurrent Protection Size Refrigeran...

Reviews: