Table 1. Alert Codes and Troubleshooting
Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in
the Installer alert button. Minor and Moderate alerts are found only in the Installer alert
button.
Alert
Code
Steps to clear
Alert Text
Priority
117
Minor
(Furnace) The reporting unit has poor earth
grounding.
Provide proper grounding for the unit. Check for proper earth ground to the system. The
alarm/code will clear 30 seconds after it is corrected.
120
Moderate
(Thermostat / Furnace / Air Handler / Out
door Unit / Equipment Interface Module)
There is a delay in the
(Thermostat, furnace,
airhandler or outdoor unit)
responding to the
system.
Typically, this alarm/code does not cause any issues and will clear on its own. The alarm/
code is usually caused by a delay in the outdoor unit responding to the thermostat. Check
all wiring connections. Cleared after unresponsive device responds to any inquiry.
124
Critical
(Thermostat / Furnace / Air Handler / Out
door Unit / Equipment Interface Module /
Damper Control Module)) The thermostat
has lost communication with the
(furnace,
airhandler or outdoor unit)
for more than 3
minutes.
Equipment lost communication with the thermostat. Check the wiring connections, ohm
wires and cycle power. The alarm stops all associated HVAC operations and waits for a
heartbeat message from the unit that's not communicating. The alarm/fault clears after
communication is reestablished.
125
Critical
(Thermostat / Furnace / Outdoor Unit /
Damper Control Module) There is a hard
ware problem on either the
(Thermostat, fur
nace control board, airhandler control board
or outdoor unit control board).
There is a control hardware problem. Replace the control if the problem prevents opera
tion and is persistent. The alarm/fault is cleared 300 seconds after the fault recovers.
126
Critical
(Furnace / Outdoor Unit) There is an internal
communication problem with the
(furnace
control board, airhandler control board or
outdoor unit control board).
There is an internal hardware problem on the control. Typically the control will reset itself.
Replace the control if the problem prevents operation and is persistent. The alarm/fault is
cleared 300 seconds after the fault recovers.
130
Moderate
(Air Handler / Equipment Interface Module)
An airhandler configuration jumper is miss
ing.
Configuration jumper(s) missing on control (applicable in noncommunicating applications
only). Replace the jumper or put wire between terminals on control. Cleared after jumper is
connected.
131
Critical
(Thermostat / Furnace / Air Handler / Out
door Unit / Equipment Interface Module /
Damper Control Module)) The
(Thermostat,
furnace, airhandler or outdoor unit)
control
parameters are corrupted.
Reconfigure the system. Replace the control if heating or cooling is not available.
132
Critical
(Air Handler / Damper Control Module) The
device's control software is corrupted.
Recycle power. If failure reoccurs, replace the control. System reset is required to recov
er.