iComfort
Wi‐Fi
®
7-Day Programmable Communicating Thermostat
37
Wiring Diagrams
iComfort Communicating System Wiring
iComfort by Lennox
FURNACE (IFC) OR AIR HANDLER (AHC)
iComfort
Wi‐Fi
®
THERMOSTAT
iComfort by Lennox
OUTDOOR AIR CON
DITIONING OR HEAT
PUMP UNIT
OPTIONAL OUT
DOOR AIR SENSOR
(SEE OAS NOTE)
OPTIONAL DIS
CHARGE AIR
SENSOR (SEE
DAS NOTE)
iComfort
Wi‐Fi
®
Thermostat
iComfort by Lennox
Indoor Furnace or Air Handler
iComfort by Lennox
Outdoor Condensing Unit or Heat Pump
DAS NOTE
- The discharge air sensor is
intended to be mounted downstream of the
furnace heat exchanger and air conditioning
coil. It must be placed in free airflow, where
other accessories (such as humidifiers, UV
lights, etc.) will not interfere with its accur
acy. Wiring distance between the IFC or
AHC and the discharge air sensor should
not exceed 10ft when wired with 18-gauge
thermostat wire.
OAS NOTE
- Wiring distance between the
IFC or AHC and the outdoor temperature
sensor should not exceed 200ft when wired
with 18-gauge thermostat wire.
Maximum total length of all connections on
the RSBus is limited to 1500ft.
Wire gauge of RSBus wire is 18.
RSBus
RSBus