DAS NOTE
: The discharge air sensor is intended to be mounted
downstream of the heat exchanger and air conditioning coil. It must be
placed in free airflow, where other accessories (such as humidifiers, UV
lights, etc.) will not interfere with its accuracy. Wiring distance between the
IFC or AHC and the discharge air sensor should not exceed 10 feet when
wired with 18-gauge thermostat wire.
OAS NOTE:
The outdoor temperature sensor wiring distance between the
IFC or AHC should not exceed 200 feet when wired with 18-gauge
thermostat wire.
RSBUS NOTE
Maximum total length of all connections on the RSBus is
limited to 1500 ft. (450 m). Max. length between components is 300 ft. (90
m).