20
R s+ s- c
+ - A B
FRONT SIDE VIEW
+ M −
M-BUS ON
iCON Building
Controller
+ M −
Shields
Purple Jacket
Do not connect shield
wire to Central Hub
+ M −
+ M −
Shields
Shields
(Do not connect)
Each device on the M-Bus must have a unique M-Bus address
starting with one and sequential amoung the other devices.
M-BUS ON
iCON Building
Controller
M-BUS ON
iCON Building
Controller
M-BUS ON
iCON Building
Controller
SIDE SIDE VIEW
NOTE
:
iCON can support up to four iCON Building Controllers
-
G +
IMPORTANT
:
Do not attach shield wire to the Central Hub. This Central Hub is typically
mounted on drywall or other non-conductive surfaces and is not well grounded. Generally,
iCON Building Controllers will have the better grounds and are preferred. Attach shield to
ground on only one iCON Building Controller.
M-BUS Terminal
Figure 7. iCON Central Hub to iCON Building Controller (M-Bus)