Table 3. Alarm Faults
Alarm
Mgr
Alarm
ID
Category
Alert
Level
(Severe,
Low,
Info)
Local
Display:
Alert Title
Local Display: Alert
Detailed Description
M3-Specific
Description
IMC Error Description
IMC Action
100
Configuration
Low
Air Vol Control
Setup Error
VAV, CAV, w/bypass damper, or
exhaust fan configuration error.
Check for proper installation of
GP board and settings.
Air Vol Control
Setup Error
VAV, CAV, w/bypass damper, or exhaust
fan configuration error. Cases that can
cause this alarm:
• GP1 (A133 w/ DIP set to VAV)
present but no ECTO 0.01, 0.23, or
8.16 option selected.
• ECTO 0.01, 0.23, or 8.16 option is
selected, but no GP1 present (A133
w/DIP set to VAV).
• ECTO 8.16 option 1-23 is selected
but no A56 board present.
• ECTO 0.23 set to option 1-15 and
ECTO 8.16 is set to option 8-15.
• ECTO 5.01 set to option 5-7 and
ECTO 8.16 is set to option 8-15.
• ECTO 5.01 set to option 5-7, but
no GP1 present (A133 w/DIP set to
VAV).
ECTO 5.01 set to option 5-7, but no
EM1 (A56) present.
• ECTO 7.25 option 12-15 selected,
but no GP1 present (A133 w/DIP set
to VAV).
Affected features do not
operate.
101
Configuration
Low
MGV Control
Setup Error
MGV configuration error. Check
for proper installation of GP
board and settings.
MGV Control Setup
Error
MGV configuration error. Cases that can
cause this alarm:
• ECTO 3.13 option 1-6 or ECTO
3.21 option 1-15 selected, but no
GP1 (A133) (W/DIP set to MGV) is
present.
• GP1 (A133) (W/DIP set to MGV) is
present, but no ECTO 3.13 option
1-6 nor ECTO 3.21 option 1-15 has
been selected.
• ECTO 7.25 option 8-11 selected, but
no GP1 (A133) (W/DIP set to MGV)
is present.
Affected features (e.g. modulating
heat) do not operate.