Page - Application Guide INNOV@-0907
interconnectivity systems
Description
•
Master / slave function :
The "Master" unit.s temperature and humidity probes must be
located in an "intermediate" position inside the controlled envi-
ronment. The "Master" unit drives the logic which is adopted by
all connected units. This is important to avoid situations in which
units in dehumidification and units in humidification contra-work
at the same time in the same environment.
The "Master" unitmodifies the working logic in case that the
measured temperature or humidity are exceeding the setpoint
-even by just a few decimal points. In case of a black-out or of
a disconnection of the "Master" unit from the pLAN network, the
connected units will start to function independently based just
on the their own probes.
• Stand-by&rotation activated by timing, time band or automa-
tically on event.
• Stand-by & rotation of 1 to N units [N is the number of installed
units].
Unit 1
Unit 8
sTAND-BY
UNIT
Unit 2
Unit 3
With local display
Advanced Control pCO - Local Area Network
Remote Display
UNIT
4
5
6
7
sTAND-BY
UNIT
Summary of Contents for INNOVA DHADC Series
Page 1: ...Providing indoor climate comfort INNOV Application guide INNOV AGU 0907 E ...
Page 2: ......
Page 55: ......