background image

Page 3

L3711C 7-DAY PROGRAMMABLE THERMOSTAT

HEAT − Using the Heat Mode

Enabling and Disabling Heat Mode

The thermostat must be in the heat mode to control the
heating equipment. Press the HEAT button to enable or
disable heat mode. If the thermostat is in cool or off mode,
pressing the HEAT button enables the heat mode (indi-
cated by HEAT in the lower right corner − see figure 4).

Heat

Prog

Fan

Settings

Cool

Day/Time

Hold

Enter

(DOOR
OPEN)

Auto

Copy

(Outside)

66

5:30

70

82

Figure 4. Turn Heat ON/OFF

If the thermostat is in heat mode, heat mode is disabled
when the HEAT button is pressed. This is indicated by OFF
near the right side of the display as shown in figure 5.

75

ROOM

°

75

HEAT SETPOINT

°

OFF

Figure 5. Heat/Cool Mode Disabled

Heating Demand

Set the thermostat to heat mode to control the heating
equipment. Then, if the room temperature is lower than the
temperature setpoint, as shown in figure 6, the thermostat
detects a heating demand and will activate the heating
equipment to satisfy the demand.

72

ROOM

°

75

HEAT SETPOINT

°

HEAT

Figure 6. Heating Demand

Heating operation is indicated by a flame icon in the lower
right corner. When the actual temperature rises above the
temperature setpoint, the flame icon will disappear. This
indicates that the heating demand has been satisfied and
that the heating equipment has been turned off.

NOTE − Heating equipment is activated for at least 3 min-
utes if no buttons are pressed during the demand interval.

COOL − Using the Cool Mode

Enabling and Disabling Cool Mode

Use the COOL button to enable or disable cool mode as
desired. If the thermostat is in heat or off mode, cool mode
is enabled when the COOL button is pressed. This is indi-
cated by COOL on the right side of the display (see figure
7).

Heat

Prog

Fan

Settings

Cool

Day/Time

Hold

Enter

(DOOR
OPEN)

Auto

Copy

(Outside)

66

i0:30

75

70

Figure 7. Turn Cool ON/OFF

If the thermostat is in cool mode, pressing the COOL but-
ton  disables cool mode (indicated by OFF, similar to figure
5).

Cooling Demand

Set the thermostat to cool mode to control the cooling
equipment. Then, if the room temperature is higher than
the temperature setpoint, as shown in figure 7, the thermo-
stat detects a cooling demand and will activate the cooling
equipment to satisfy the demand.

Cooling operation is indicated by flashing snowflake"
icons in the display. When the actual temperature drops
below the temperature setpoint, the snowflake icons will
disappear. This indicates that the cooling demand has
been satisfied and that the cooling equipment has been
turned off.

NOTE − If no buttons are pressed during a demand for
cooling, the equipment must operate for at least 4 minutes.
After a demand has been satisfied, cooling equipment op-
eration is locked out for 5 minutes. If another cooling de-
mand occurs during this 5−minute interval, COOL" and the
snowflakes will flash; however, the cooling equipment will
not operate until the 5−minute delay has elapsed.

NOTE − The cooling setpoint cannot be lower than the
heating setpoint. Also, the difference between the cooling
and heating setpoint must be at least 4 degrees.

AUTO − Using the Autochangeover Mode

When in either heat mode or cool mode, autochangeover
can be enabled or disabled by pressing the AUTO button. If
enabled, AUTO appears at the lower right corner of the dis-
play. The thermostat will then automatically change over
from heating to cooling and vice versa, to keep the room
temperature in between the heating and cooling setpoints.
Autochangeover can be used in either of the thermostat
hold modes, or when the thermostat program is running.
These modes are described later.

Summary of Contents for L3711C

Page 1: ...tochangeover Mode 3 HOLD Temperature Hold Mode 4 PROG Thermostat Programming 4 COPY Copy a Program 5 FAN Controlling Fan Operation 5 Displaying Outside Temperature 5 SETTINGS Filter Maintenance Reminder 5 Service Indicator 6 Thermostat RESET 6 Removing Installing Thermostat 6 Default Thermostat Settings 6 Thermostat Output Table 7 Technical Specifications 7 General These instructions are intended ...

Page 2: ...er input Start making changes within 15 seconds or the HOME screen will re turn Heat Prog Fan Settings Cool Day Time Hold Enter DOOR OPEN Auto Copy Outside Figure 3 Thermostat Buttons When an Arrow HOLD HEAT or COOL button is pressed SETPOINT and the temperature setting appears for 15 seconds If desired start making changes within 15 sec onds or the HOME screen will return The backlight will turn ...

Page 3: ...he right side of the display see figure 7 Heat Prog Fan Settings Cool Day Time Hold Enter DOOR OPEN Auto Copy Outside 66 i0 30 75 70 Figure 7 Turn Cool ON OFF If the thermostat is in cool mode pressing the COOL but ton disables cool mode indicated by OFF similar to figure 5 Cooling Demand Set the thermostat to cool mode to control the cooling equipment Then if the room temperature is higher than t...

Page 4: ...HOLD flashes see figure 9 This overrides the program for 2 hours from the last button press then returns to the program While in Temporary Hold press HOLD once to switch to Permanent Hold HOLD displays solid PROG not dis played press HOLD again to return to the program PROG displays HOLD not displayed Heat Prog Fan Settings Cool Day Time Hold Enter DOOR OPEN Auto Copy Outside 68 i0 30 72 70 Figure...

Page 5: ...ling the Fan Operation Use the FAN button to select either continuous fan mode or auto fan mode To change from continuous to auto fan mode or vice ver sa press the FAN button Note whether a fan icon in the FAN box is present indicating that the fan is running or not fan not running If continuous fan mode is enabled ON displayed in FAN box see figure 12 the fan will run continuously regard less of ...

Page 6: ...om a qualified service technician Thermostat RESET Under some abnormal conditions it may be necessary to reset the thermostat to its default condition Such a RE SET would delete all programming and settings and there fore should only be used on rare occasions when the the thermostat fails to function as designed and or as pro grammed Such an instance can occur as a result of a pow er surge or simi...

Page 7: ...shown in Celsius position 1 2 3 4 5 6 7 PLUG IN Use Care To Avoid Bending Prongs Figure 17 Changing Fahrenheit Celsius Setting Indoor Temperature Measurement Range Measurement Scale Fahrenheit Measurement Range 35 F to 99 F Measurement Resolution 0 5 F Measurement Accuracy 1 F Field Offset via DIP switches to 3 F Sampling Method temperature measurements sampled every 15 seconds Displayed temperatu...

Page 8: ...ce Reminder Settings of Off 6 or 12 months of chronological time are available When programmed time has elapsed a MAIN TENANCE indicator is displayed Service Reminder The SERVICE indicator is displayed only under the follow ing conditions S if the thermostat Y1 terminal has been activated with 24VAC for at least 5 minutes AND the L terminal is shorted to the R terminal OR S if the thermostat Y1 te...

Reviews: