Page 37
TABLE 24
MINIMUM AND MAXIMUM CFM
BELT DRIVE STD. & HIGH EFFICIENCY UNITS
Gas Heat Minimum CFM
Unit
Gas Heat
Size
Airflow
CFM
LGH092-120, 150
Std.,
Med.
2225
LGH092-120, 150
High
2550
Electric Heat Minimum CFM
Unit
Heat Size
(kW)
Airflow
CFM
LCH092-102
0
2800
LCH092-150
15,
22.5,
30, 45
2800
LCH120-150
0, 60
4000
Cooling Low Minimum CFM - 220 CFM/ton
Unit
Blower
Speed
Airflow
CFM
LGH/LCH092
Low
1650
LGH/LCH102
Low
1870
LGH/LCH120
Low
2200
LGH/LCH150
Low
2750
Cooling High Minimum CFM - 280 CFM/ton
Unit
Blower
Speed
Airflow
CFM
LGH/LCH092
High
2100
LGH/LCH102
High
2380
LGH/LCH120
High
2800
LGH/LCH150
High
3500
Smoke and Ventilation Minimum CFM - 150 CFM/ton
Unit
Not Ap
plicable
Airflow
CFM
LGH/LCH092
NA
1125
LGH/LCH102
NA
1275
LGH/LCH120
NA
1500
LGH/LCH150
NA
1875
Heating and Cooling Maximum CFM - 480 CFM/ton
Unit
Blower
Speed
Airflow
CFM
LGH/LCH092
High
3600
LGH/LCH102
High
4080
LGH/LCH120
High
4800
LGH/LCH150
High
6000
TABLE 25
MINIMUM AND MAXIMUM CFM
BELT DRIVE ULTRA HIGH EFFICIENCY BLOWERS
094U4M, 122U4M, 152U4M
Gas Heat Minimum CFM
Unit
Gas Heat Size
Airflow CFM*
LGH094-152
Std. , Med.
2225
LGH094-152
High
2550
Electric Heat Minimum CFM
Unit
Heat Size (kW)
Airflow CFM
LCH094
7.5, 15, 22.5, 30, 45
2800
LCH122, 152
15, 22.5, 30, 45
2800
LCH122, 152
0, 60
4000
Cooling Low Minimum CFM - 160 CFM/ton
Unit
Blower Speed
Airflow CFM
LGH/LCH094
Low
1200
LGH/LCH122
Low
1600
LGH/LCH152
Low
2000
Cooling High Minimum CFM - 280 CFM/ton
Unit
Blower Speed
Airflow CFM
LGH/LCH094
High
2100
LGH/LCH122
High
2800
LGH/LCH152
High
2500
Smoke and Ventilation Minimum CFM - 150 CFM/ton
Unit
Not Applicable
Airflow CFM
LGH/LCH094
NA
1125
LGH/LCH122
NA
1500
LGH/LCH152
NA
1875
Heating and Cooling Maximum CFM - 480 CFM/ton
Unit
Blower Speed
Airflow CFM
LGH/LCH094
High
3600
LGH/LCH122
High
4800
LGH/LCH152
High
6000
*Rounded to nearest 25 CFM.