background image

Page 26 

Defrost Control Timing Pins

Each timing pin selection provides a different accumulated 

compressor run time period during one thermostat run 

cycle. This time period must occur before a defrost cycle 

is initiated. The defrost interval can be adjusted to 30 

(T1), 60 (T2), or 90 (T3) minutes. 

It is intended that this 

product should be set at the 60-minute time interval at 

initial installation

. If the timing selector jumper is not in 

place, the control defaults to a 90-minute defrost interval. 

The maximum defrost period is 14 minutes and cannot be 

adjusted. 

For geographic areas that experience low temperature 

and high humidity conditions (below 35°F and above 

80%  RH),  the  defrost  timer  pin  must  be  field  set  at 

installation to a 60 or 30 minute defrost interval to 

ensure reliable system operation while in heating mode.

NOTE:

A test option is provided for troubleshooting. The test mode 

may be started any time the unit is in the heating mode and 

the defrost thermostat is closed or jumpered. If the jumper 

is in the TEST position at power up, the control will ignore 

the test pins. When the jumper is placed across the TEST 

pins for 2 seconds, the control will enter the defrost mode. 

If the jumper is removed before an additional 5-second 

period has elapsed (7 seconds total), the unit will remain 

in defrost mode until the defrost thermostat opens or 14 

minutes have passed. If the jumper is not removed until 

after the additional 5-second period has elapsed, the 

defrost will terminate and the test option will not function 

again until the jumper is removed and reapplied.

Second-Stage Lock-In

If first-stage output is active in heating mode and the outdoor 

ambient temperature is below the lock-in temperature 

(approximately 40°F), the second-stage output will be 

energized even without a Y2 room thermostat input.

Compressor Delay (Quiet-Shift)

The defrost board has a field-selectable function to reduce 

occasional sounds that may occur while the unit is cycling 

in and out of the defrost mode. The compressor will be 

cycled off for 30 seconds going in and out of the defrost 

mode when the compressor delay jumper is removed.

NOTE: 

The  30-second  “off”  cycle  is  not  functional  when 

jumpering the TEST pins.

Time Delay

The defrost control includes a compressor timer, which 

ensures the compressor is off for a minimum amount of 

time between operating cycles.

The  timed-off  delay  is  5  minutes  long.  The  delay  helps 

to protect the compressor from short cycling in case the 

power to the unit is interrupted or a pressure switch opens. 

The delay is bypassed by placing the timer select jumper 

across the TEST pins for 0.5 seconds.

Pressure Switch Circuit

High and low pressure switches are connected to the 

defrost control board on heat pump models. Air conditioning 

models have a high pressure switch installed in line with 

the compressor contactor coil (see Figure 13).

During a single demand cycle, the defrost control will 

lock out the unit after the fifth time that the circuit is 

interrupted by any pressure switch wired to the control 

board. In addition, the diagnostic LEDs will indicate a 

locked-out pressure switch after the fifth occurrence 

of an open pressure switch (see Table 5). 

The unit will remain locked out until power to the board 

is interrupted, then re-established, or until the jumper 

is applied to the TEST pins for 0.5 seconds.

NOTE: 

The defrost control board ignores input from the 

low pressure switch terminals as follows:

•  During the TEST mode
•  During the defrost cycle
•  During the 90-second start-up period
• 

For the first 90 seconds each time the reversing valve 

switches heat/cool modes

If the TEST pins are jumpered and the 5-minute delay 

is being bypassed, the LO PS terminal signal is not 

ignored during the 90-second start-up period.

Diagnostic LEDs

The defrost board uses two LEDs for diagnostics. The 

LEDs flash a specific sequence according to the condition 

as shown in Table 5.

Defrost Board Diagnostic LEDs

Green LED 

(DS2)

Red LED 

(DS1)

Condition

OFF

OFF

No Power to Control

Simultaneous slow FLASH

Normal Operation /  

Power to Control

Alternating Slow FLASH

5-min Anti-Short-Cycle Delay

ON

Slow FLASH

Low Pressure Switch Ignored 

(Low Ambient)

Fault & Lockout Codes

OFF

Slow FLASH

Low Pressure Switch Fault

OFF

ON

Low Pressure Switch Lockout

Slow FLASH

OFF

High Pressure Switch Fault

ON

OFF

High Pressure Switch Lockout

Table 5. Defrost Control (CMC1) Diagnostic LEDs

Summary of Contents for LRP16GE Series

Page 1: ...stries Inc Dallas Texas USA THIS MANUAL MUST BE LEFT FOR FUTURE REFERENCE WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss o...

Page 2: ...17 07 13 44 13 44 14 32 16 06 6 20 40 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS 11 49 2 33 47 66 1 98 16 77 2 48 14 02 47 66 POWER ENT...

Page 3: ...AGE ENTRY 7 8 DIA KNOCKOUT GAS SUPPLY 44 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS TOP VIEW POWER ENTRY GAS ENTRY RETURN AIR 2 11 19 49...

Page 4: ...44 3 8 1127 44 3 8 1127 16 7 8 429 13 7 8 352 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 4 19 1 25 5 1 2 140 5 3 4 146 11 1 2 287 17 1 4 438 1 3 8 35 3 3 4 95 13 3...

Page 5: ...13 in 76 x 330 mm 52 7 8 1343 44 3 8 1127 19 1 2 380 11 1 2 287 19 1 2 380 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 3 4 95 22 7 8 581 7 178 3 4 19 1 25 NOTE If bo...

Page 6: ...8 203 SIDES AND BACK FLANGE 6 152 UNIT BASE RAIL CLIPS 4 NOTE Minimum Height 4 102 UNIT BASE RAIL CLIPS 4 Usage A B C in mm in mm in mm 24 36 42 7 8 1089 13 7 8 352 16 7 8 429 48 60 51 3 8 1305 19 1 2...

Page 7: ...nits are not suitable for use with conventional venting systems Inspection As soon as the unit is received it should be inspected for possible damage during transit If damage is evident the extent of...

Page 8: ...s may be installed on combustible floors Units must be installed outdoors Clearance to combustibles below the unit flue is 10 inches since the flue points down Do not permit overhanging structures or...

Page 9: ...truction bag see Figure 2 Vent Hood Attach with Screws Figure 2 Installing the Vent Cover Rigging Unit Exercise care when moving the unit Do not remove any packaging until the unit is near the place o...

Page 10: ...ilter rack kit If an existing gas furnace is being removed from a common venting system when this packaged unit is installed then read and follow the instructions in the Removal of Unit from Common Ve...

Page 11: ...rating plate Gas Piping Recommendations A drip leg and a ground joint union must be installed in the gas piping A ground joint union is recommended by the manifold valve When required by local codes a...

Page 12: ...he National Electrical Code ANSI NFPA No 70 latest edition Canadian Electrical Code Part 1 CSA C22 1 latest edition or local codes where they prevail Use wiring with a temperature limitation of 75 C m...

Page 13: ...d insulated wires 18 AWG should be used to connect the thermostat to the unit Compressor Units are shipped with compressor mountings factory adjusted and ready for operation Do not loosen compressor m...

Page 14: ...as valve and connecting a water manometer or gauge Under no circumstances should the final manifold pressure vary more than 0 3 w c from the above specified pressures To adjust the regulator turn the...

Page 15: ...roughout the external static range A particular CFM can be obtained by positioning jumpers COOL HEAT and ADJUST on the blower control The HEAT and COOL jumpers are labeled A B C and D Each of the numb...

Page 16: ...duce the selected air flow rate by 25 percent when humidity levels are high An LED D1 lights when the blower is operating in the dehumidification mode Cooling System The cooling system is a factory ch...

Page 17: ...nds of the ignition trial If the flame is established within 10 seconds the control de energizes the spark If flame is not established within 10 seconds the gas valve and spark are de energized and th...

Page 18: ...need cleaning Sooting of a gas appliance is highly irregular and once cleaned the cause of the sooting must be determined If the heat exchanger should become sooted it can be cleaned as follows 1 Remo...

Page 19: ...eration Call for heat 2 Flash Two flashes in second with 1 second pause System lockout Failed to detect or sustain flame 3 Flash Three flashes in 1 5 seconds with 1 second pause Pressure switch senses...

Page 20: ...00 400 1260 1080 900 720 1400 1200 1100 975 630 540 450 360 048 Blower Performance 0 through 0 80 in w g External Static Pressure Range 1980 1760 1540 1320 1350 1200 1100 1000 990 880 770 660 NORM 180...

Page 21: ...Page 21 Figure 9 Wiring Diagram Single Phase Wiring Diagram LRP16GE...

Page 22: ...being pulled through the condensate line will prevent positive drainage without a proper trap The condensate drain line must be properly trapped routed to a suitable drain and primed prior to unit com...

Page 23: ...JUST jumper is labeled Test and Norm The and pin settings are used to add or subtract a percentage of the CFM selected The Test jumper is used to operate the motor in the test mode Figure 12 shows the...

Page 24: ...e is no demand for heating or cooling the blower control will provide 50 percent of the COOL CFM selected DEHUMIDIFICATION The blower control includes an HUM terminal which provides for connection of...

Page 25: ...l Board 24V TERMINAL STRIP CONNECTIONS DIAGNOSTIC LEDS HIGH PRESSURE SWITCH TEST PINS DEFROST TIMING PINS P1 REVERSING VALVE DEFROST THERMOSTAT S6 LOW PRESSURE SWITCH COMPRESSOR DELAY PINS S4 S87 SERV...

Page 26: ...he compressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The defrost control includes a compressor timer which ensures the compresso...

Page 27: ...ance normally consists of changing or cleaning the filters and cleaning the evaporator coil On occasion other components may also require cleaning Filters Filters are not supplied with the unit Inspec...

Page 28: ...49 150 36 132 134 136 137 138 139 140 142 144 145 147 148 48 136 138 140 142 143 144 145 147 148 149 150 151 60 134 135 137 138 139 140 141 142 144 145 147 148 24 Liquid 237 257 278 298 306 320 343 36...

Page 29: ...36 26 33 40 50 54 61 68 75 83 95 103 117 131 48 28 36 43 53 57 65 72 79 89 102 107 116 125 60 31 39 46 56 60 68 75 82 89 99 106 117 128 24 Liquid 264 271 279 289 294 301 309 316 324 335 340 348 357 36...

Page 30: ...Page 30 Wiring Diagram LRP16HP Figure 14 HP Wiring Diagram...

Reviews: