background image

Page 11

DEMAND

CAI

GAS VALVE

15

ON
OFF

38

IGNITOR

34

1

Pre -Purge

Ignitor Warm-up

Trial for

Ignition

Post

 Purge

5 SEC

80

*Blower on time will be 30 seconds after flame is sensed. Blower off time will depend on “OFF TIME” Setting.

INDOOR BLOWER

Blower “On”*

Delay

ELECTRONIC IGNITION

FIGURE 4 

Fan Time Control

Ignition Control 103217-03 
Heating Fan On Time

The fan on time of 30 seconds is not adjustable.

Heating Fan Off Time

Fan off time (time that the blower operates after the heat 

demand has been satisfied) can be adjusted by moving 

the jumper to a different setting. The unit is shipped with 

a  factory  fan  off  setting  of  90  seconds.  For  customized 

comfort, monitor the supply air temperature once the heat 

demand  is  satisfied.  Note  the  supply  air  temperature  at 

the instant the blower is de-energized.
Adjust the fan-off delay to achieve a supply air tempera

-

ture between 90° - 110° at the instant the blower is de-en

-

ergized. (Longer delay times allow for lower air tempera

-

ture, shorter delay times allow for higher air temperature). 

See figure 5.

Cooling Fan On Time

The fan on time is 2 seconds and is not adjustable.

Cooling Fan Off Time

The control has a 45 second fan off delay after cooling 

demand has been met. This delay is factory set and not 

adjustable.

HEAT FAN

OFF TIME IN SECONDS

To adjust fan-off timing, reposition jumper across pins to

achieve desired setting.

NO JUMPER

60 90

12

0

180

60 90

12

0

180

60 90

12

0

180

60 90

120 18

0

60 Second 

off Time

90 Second 

off Time

120 Second 

off Time

180 Second 

off Time

FIGURE 5 

Ignition Control 107163-01

The heat fan-on time of 30 seconds is not adjustable The 

heat fan-off delay (amount of time that the blower oper

-

ates after the heat demand has been satisfied) may be 

adjusted by changing the two position dip switch on the 

integerated control, to one of four slections. Blower off de

-

lay is factory set at 90 seconds. For other blower off delay 

settings, please refer to the following chart:

Blower Delay Select

SW2-1

SW2-2

60

OFF

ON

90

OFF

OFF

120

ON

OFF

180

ON

ON

Factory Setting is 90

Summary of Contents for ML180DF045E36A

Page 1: ...LP Propane operation ML180DFE model units are equipped with a hot surface ignition system and a constant torque ECM motor The motor is programmed to provide constant torque at each of the five select...

Page 2: ...Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations Isolated combustion system rating for non weatherized furnaces SPECIFICATIONS Gas Heating Performance Mode...

Page 3: ...s cfm Watts cfm Watts 0 00 1430 285 1215 180 1035 120 995 110 930 100 0 10 1400 285 1175 185 995 130 885 100 850 90 0 20 1375 300 1145 200 950 140 840 110 725 85 0 30 1335 315 1120 210 915 145 790 115...

Page 4: ...1195 130 0 10 1725 390 1495 270 1390 220 1320 195 1145 140 0 20 1695 405 1470 285 1340 235 1280 210 1105 145 0 30 1660 415 1425 300 1290 240 1225 215 1040 160 0 40 1615 430 1395 310 1250 255 1185 230...

Page 5: ...Box includes integrated control interlock switch and transformer Gas Valve Burner Box includes sensor ignitor and rollout switches Combustion Air Inducer Blower Access Panel Heating Compartment Acces...

Page 6: ...t if repair is attempted The hot surface ignition control system consisting of an integrated control figure 3 with control terminal designa tions in tables 1 2 and 3 sensor and ignitor figure 6 The in...

Page 7: ...lve Out TABLE 3 1 4 Quick Connect Terminals 120HUM Humidifier 120VAC LINE 120VAC XFMR Transformer 120VAC CIRC Indoor blower 120VAC EAC Indoor air quality accessory 120VAC NEUTRALS Common 120VAC HUM24...

Page 8: ...Switch Open 9 Pressure Switch failed to close or opened during heat demand 10 Watchguard Pressure Switch opened 5 times during one heat demand 11 Pressure Switch stuck closed prior to activation of c...

Page 9: ...llout Switch Open 9 Pressure Switch failed to close or opened during heat demand 10 Watchguard Pressure Switch opened 5 times during one heat demand 11 Pressure Switch stuck closed prior to activation...

Page 10: ...s2 Pressure Switch failed to close or opened during heat demand inducer on 10 Flashes2 Watchguard Pressure switch opened 5 times during a single heating demand 11 Flashes2 Pressure switch stuck closed...

Page 11: ...zed Longer delay times allow for lower air tempera ture shorter delay times allow for higher air temperature See figure 5 Cooling Fan On Time The fan on time is 2 seconds and is not adjustable Cooling...

Page 12: ...thin three minutes or SureLight control will go into Watchguard for one hour The switch is factory set and cannot be adjusted The switch may have a different setpoint for each unit model number If lim...

Page 13: ...ire from Integrated Control and Connect Alligator Clip to Flame Sensor Lead Flame Sensor Terminal Remove Sensor Wire from Integrated Control and Connect Alligator Clip to Terminal on Control DIGITAL M...

Page 14: ...needed If the reading on the meter is not correct 0 or infinity then a second test is needed Test 2 Check ignitor for correct resistance Seperate the 2 pin jack plug near the manifold and check resist...

Page 15: ...ducer Pressure Switch S18 Units are equipped with a combustion air pressure switch located on the combustion air inducer orifice bracket The switch is connected to the combustion air inducer housing b...

Page 16: ...resent in tests 1 and 2 and motor is not operating properly replace motor The motor is not field repairable If replacing the indoor blower motor or blower wheel is necessary placement is critical The...

Page 17: ...peed tap used for continuous fan 1 2 3 4 or 5 on input plug P49 If 24 volts is not present problem may be up stream of plug P49 Proceed to test 4 Multi Meter set to VAC 12 0 12 0 24 Multi Meter set to...

Page 18: ...ximately the same resistance within an ohm 3 Check to see if the blower wheel spins freely Motor Test FIGURE 16 TABLE 9 Scale Measurement range in words ohms 2 M two megohm two million ohms 0 2 000 00...

Page 19: ...to be performed 3 Remove the upper access panel 4 Move gas valve switch to OFF position Do not force See figure 18 5 Replace the upper access panel B Safety or Emergency Shutdown Disconnect main powe...

Page 20: ...itting Connect to a test gauge to measure supply pressure 2 Start unit and allow 5 minutes for unit to reach steady state 3 After allowing unit to stabilize for 5 minutes record supply pressure and co...

Page 21: ...opane 10 0 10 0 10 0 11 0 13 0 TABLE 13 Pressure Switch and Gas Conversion Kits at all Altitudes Model Input Size High Altitude Pressure Switch Kit High Altitude Natuarl Gas Orifice Kit LP Propane Ori...

Page 22: ...132 Vac NOTE Figures 21 and 22 are typical ignition control illustrations CHECK VOLTAGE BETWEEN LINE NEUTRAL AND LOW VOLTAGE C TERMINAL FIGURE 20 TABLE 14 Furnace Status Measurement VAC Expected Maxi...

Page 23: ...5 W C For cooling speed external static pressure drop must not be more than 0 8 W C 4 Seal the hole when the check is complete EXTERNAL STATIC PRESSURE Supply Duct Static Return Duct Static Total Duct...

Page 24: ...rovide combustion air 10 Inspect the furnace venting system to make sure it is in place structurally sound and without holes corrosion or blockage Vent system must be free and clear of obstructions an...

Page 25: ...manifold assembly to the vestibule panel and remove the assembly from the unit 7 Remove screws from both sides top and bottom of vestibule panel 8 Remove heat exchanger It may be necessary to spread c...

Page 26: ...burner box cover 15 Reconnect all wires 16 Reconnect top cap and vent pipe to combustion air inducer outlet 17 Reconnect gas supply piping 18 Turn on power and gas supply to unit 19 Set thermostat and...

Page 27: ...e found to be closed Call for heat can continue 5 A92 integrated control energizes B6 combustion air inducer S18 combustion air pressure switch closes Once S18 closes a 15 second pre purge follows 6 A...

Page 28: ...OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED FLASHES CODE 11 PRESSURE SWITCH CLOSED GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY Sequence holds until press...

Page 29: ...NCE FOUR TIMES FLAME SIGNAL 1 5 MICROAMPS OR GREATER YES YES YES ROLLOUT SWITCH CLOSED LED FLASHES CODE 8 ROLLOT SWITCH OPEN GAS VALVE POWER OFF COMBUSTION AIR INDUCER POWER ON INDOOR BLOWER ON SEQUEN...

Page 30: ...SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED EAC TERM ENERGIZED COMPRESSOR O...

Page 31: ...D EAC TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G ENERGIZES SYSTEM FAN AT FAN SPEED EAC TERM ENERGIZED NO YES YES NO SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30 S...

Reviews: