FIGURE 22

Common Venting Using Metal-Lined Masonry Chimney

4 in. (102 mm)

minimum

MIN. LENGTH -- AS

SHORT AS PRACTICAL

MAX. LENGTH
-- SEE NOTE 1

BELOW.

SEALED

PERMANENTLY

SEALED FIREPLACE

OPENING

EXTERIOR

CHIMNEY WITH

METAL

LINER

VENT CONNECTOR

NOTE 1 - Refer to the provided venting tables for installations.  Refer
to the capacity requirements shown in the provided venting tables.

OTHER

APPLIANCE

FURNACE

5 ft. (1.5 m)

minimum

DO NOT insulate the space between the liner and the
chimney wall with puffed mica or any other loose gran­
ular insulating material.

IMPORTANT

SINGLE appliance venting of a fan‐assisted furnace
into a tile‐lined masonry chimney (interior or outside
wall) is PROHIBITED. The chimney must first be lined
with either type B1 vent or an insulated single wall
flexible vent lining system which has been sized ac­
cording to the provided venting tables and the vent
pipe manufacturer's instructions.

A fan-assisted furnace may be commonly vented into an
existing lined masonry chimney if the following conditions
are met:

  The chimney is currently serving at least one drafthood-

equipped appliance;

  The vent connectors and chimney are sized according

to the provided venting tables.

If type B1 double‐wall vent is used inside a chimney, no oth­
er appliance can be vented into the chimney. The outer wall
of type B1 vent pipe must not be exposed to flue products.
A type B1 vent or masonry chimney liner shall terminate
above the roof surface with a listed cap or a listed roof as­
sembly according to the terms of their respective listings
and the vent manufacturer's instructions.

When inspection reveals that an existing chimney is not
safe for the intended purpose, it shall be rebuilt to conform
to nationally recognized standards, lined or relined with
suitable materials, or replaced with a gas vent or chimney
suitable for venting ML180UHT series units. The chimney
passageway must be checked periodically to ensure that it
is clear and free of obstructions.

Do not install a manual damper, barometric draft regulator,
or flue restrictor between the furnace and the chimney.
Never connect a Category I appliance to a chimney that is
servicing a solid-fuel appliance. If a fireplace chimney flue
is used to vent this appliance, the fireplace opening must
be permanently sealed.
A type B or listed chimney lining system that passes
through an unused masonry chimney flue is not considered
to be exposed to the outdoors.

General Venting Requirements

Vent all ML180UHT furnaces according to these instruc­
tions:

 1 - Vent diameter recommendations and maximum allow­

able piping runs are found in the provided venting
tables.

 2 - In no case should the vent or vent connector diameter

be less than the diameter specified in the provided
venting tables.

 3 - The minimum vent capacity determined by the sizing

tables must be less than the low fire input rating and the
maximum vent capacity must be greater than the high
fire input rating.

 4 -

Single appliance vents -

 If the vertical vent or tile‐lined

chimney has a larger diameter or flow area than the
vent connector, use the 

vertical vent diameter

 to de­

termine the 

minimum vent capacity

 and the 

vent

connector diameter

 to determine the 

maximum vent

capacity

. The flow area of the vertical vent, however,

shall not exceed 7 times the flow area of the listed ap­
pliance categorized vent area, drafthood outlet area or
flue collar area unless designed according to approved
engineering methods.

 5 -

Multiple appliance vents -

 The flow area of the largest

section of vertical vent or chimney shall not exceed 7
times the smallest listed appliance categorized vent
area, drafthood outlet area or flue collar area unless
designed according to approved engineering meth­
ods.

Summary of Contents for ML180UHT

Page 1: ...r death WARNING Improper installation adjustment alteration service or maintenance can cause property damage person al injury or loss of life Installation and service must be performed by a licensed p...

Page 2: ...ne side return air See Blower Performance Tables for additional informa tion 1 Bottom Return Air Opening GAS PIPING INLET Either Side Side Return Air Opening Either Side 1Bottom Return Air Opening FLU...

Page 3: ...LP Propane is a regulated manufactured gas a Wobbe number is not required to determine acceptability For propane installations the acceptable heating value range is 93 2 mj m3 2500 btu ft3 5 NOTE Lenn...

Page 4: ...system as possible The furnace should also be located close to the chimney or vent termination point Do not install the furnace where drafts might blow direct ly into it This could cause improper com...

Page 5: ...t be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration If the furnace is located in a building of tight construction with weather stripping...

Page 6: ...ngular air ducts shall be no less than 75 mm 3 inches In calculating free area the blocking effect of louvers grilles or screens must be considered If the design and free area of protective cov ering...

Page 7: ...ss may be placed under each corner of the furnace as ap propriate to the application The ML180UHT gas furnace can be installed as shipped in either the upflow position or the horizontal position Selec...

Page 8: ...ght in through the bottom or either side of the furnace installed in an upflow application If the furnace is installed on a platform with bottom return make an airtight seal between the bottom of the...

Page 9: ...ust not extend beyond the markings on the furnace cabinet 2 To minimize pressure drop the largest opening height possible up to 356 mm 14 in is preferred FURNACE FRONT AIR FLOW 1 Unit side return air...

Page 10: ...ove installations are shown in figure 10 This furnace may be installed in either an attic or a crawl space Either suspend the furnace from roof rafters or floor joists as shown in figure 11 or install...

Page 11: ...33 21 405 X 635 X 25 1 16 X 25 X 1 508 X 635 X 25 1 20 X 25 X 1 D 622 24 1 2 405 X 635 X 25 2 16 X 25 X 1 610 X 635 X 25 1 24 X 25 X 1 Duct System Use industry approved standards to size and install t...

Page 12: ...nd or make up box as needed per the follow ing steps See figures 14 through 20 1 Remove the four mounting screws figure 13 which secure the combustion air inducer pressure switch assembly to the orifi...

Page 13: ...excess wire and secure to the gas manifold Pressure Switch Vent Pipe Flue Transition Cover Plate Collector Box FLOW AIR HORIZONTAL RIGHT POSITION Side Vent Discharge FIGURE 18 FLOW AIR Pressure Switc...

Page 14: ...ee be used Drive one self drilling screw through the front and one through each side of the vent pipe and collar See figure 21 Install the first vent connector elbow at a minimum of six inches 152 mm...

Page 15: ...relined with suitable materials or replaced with a gas vent or chimney suitable for venting ML180UHT series units The chimney passageway must be checked periodically to ensure that it is clear and fre...

Page 16: ...ity listed in the common venting tables should be reduced by 20 the equivalent of two 90 elbows 0 80 x maximum common vent capacity The horizontal length of the offset shall not exceed 1 1 2 feet 46 m...

Page 17: ...ance Height H feet Lateral L feet Vent and Connector Diameter D inches 3 Inch 4 Inch 5 Inch 6 Inch Appliance Input Rating in Thousands of Btu Per Hour MIN MAX MIN MAX MIN MAX MIN MAX 6 0 0 78 0 152 0...

Page 18: ...1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 22 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 30 1 20 62 31 113 45 181...

Page 19: ...em is venting properly step 3 return all doors widows exhaust fans fireplace damp ers and any other gas burning appliances to their pre vious mode of operation 7 If a venting problem is found during a...

Page 20: ...OFF VALVE With 1 8 in NPT Plugged Tap Shown NOTE BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET FIGURE 24 GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE GROUND JOINT UNION DRIP LEG MANUAL...

Page 21: ...rating for thermostat connections 5 Electrically ground the unit according to local codes NOTE The ML180UHT furnace contains electronic components that are polarity sensitive Make sure that the furna...

Page 22: ...tion System TERMINAL DESIGNATIONS HUM Humidifier 240VAC LINE Input 240VAC XFMR Transformer 240VAC EAC Electronic Air Cleaner 240VAC COOL Cool Speed 240VAC PARK1 PARK2 Dead terminals for alternate spee...

Page 23: ...Page 23 FIGURE 28 ML180UHT Schematic Wiring Diagram...

Page 24: ...does not get hot when there is no call for heat on units with an automatic ignition system WARNING If you do not follow these instructions exactly a fire or explosion may result causing property dama...

Page 25: ...tment Gas Flow To check for proper flow to combustion chamber deter mine Btu input from appliance rating plate Divide this input rating by the Btu per cubic foot of available gas Result is the require...