SPECIFICATIONS
Gas
Heating
Performance
Model No.
ML195UH
090XP48C
ML195UH
110XP48C
ML195UH
110XP60C
ML195UH
135XP60D
1
AFUE
95%
95%
95%
95%
Input - Btuh
88,000
110,000
110,000
132,000
Output - Btuh
85,000
105,000
106,000
126,000
Temperature rise range - °F
40 - 70
50 - 80
40 - 70
45 - 75
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10.0
3.5 / 10.0
3.5 / 10.0
3.5 / 10.0
High static - in. w.g.
0.5
0.5
0.5
0.5
Connections
in.
Intake / Exhaust Pipe (PVC)
2 / 2
2 / 2
2 / 2
2 / 2
Gas pipe size IPS
1/2
1/2
1/2
1/2
Condensate Drain Trap (PVC pipe) - i.d.
1/2
1/2
1/2
1/2
with furnished 90° street elbow 1/2 slip x 1/2 Mipt
1/2 slip x 1/2 Mipt
1/2 slip x 1/2 Mipt
1/2 slip x 1/2 Mipt
with field supplied (PVC coupling) - o.d.
3/4
3/4
1
1
Indoor
Blower
Wheel nom. dia. x width - in.
10 x 10
10 x 10
11-1/2 x 10
11-1/2 x 10
Motor output - hp
1/2
1/2
1
1
Tons of add-on cooling
3 - 4
3 - 4
4 - 5
4 - 5
Air Volume Range - cfm
900 - 2140
715 - 2000
1250 - 2485
1145 - 2595
Electrical
Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
8.2
8.2
11.5
11.5
Maximum overcurrent protection
12
12
15
15
Shipping Data
lbs. - 1 package
149
159
164
177
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
SPECIFICATIONS
Gas
Heating
Performance
Model No.
ML195UH
045XP24B
ML195UH
045XP36B
ML195UH
070XP36B
ML195UH
090XP36C
1
AFUE
95%
95%
95%
95%
Input - Btuh
44,000
44,000
66,000
88,000
Output - Btuh
41,000
42,000
64,000
85,000
Temperature rise range - °F
40 - 70
25 - 55
40 - 70
50 - 80
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10.0
3.5 / 10.0
3.5 / 10.0
3.5 / 10.0
High static - in. w.g.
0.5
0.5
0.5
0.5
Connections
in.
Intake / Exhaust Pipe (PVC)
2 / 2
2 / 2
2 / 2
2 / 2
Gas pipe size IPS
1/2
1/2
1/2
1/2
Condensate Drain Trap (PVC pipe) - i.d.
1/2
1/2
1/2
1/2
with furnished 90° street elbow 1/2 slip x 1/2 Mipt
1/2 slip x 1/2 Mipt
1/2 slip x 1/2 Mipt
1/2 slip x 1/2 Mipt
with field supplied (PVC coupling) - o.d.
3/4
3/4
3/4
3/4
Indoor
Blower
Wheel nom. dia. x width - in.
10 x 8
10 x 8
10 x 8
10 x 8
Motor output - hp
1/3
1/3
1/3
1/3
Tons of add-on cooling
2.5 - 3
2 - 3
2.5 - 3
2 - 3
Air Volume Range - cfm
390 - 1140
700 - 1605
650 - 1585
655 - 1630
Electrical
Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
3.1
6.1
6.1
6.1
Maximum overcurrent protection
12
12
12
12
Shipping Data
lbs. - 1 package
119
121
129
144
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.