Page 41
FIGURE 52
ML195UH With Evaporator
Coil Using A Separate Drain
Condensate
Drain Connection
Field Provided Vent
(1” min. 2” max. above
condensate connec
tion)
Evaporator drain
line required
FIGURE 53
Horizontal Furnace 4” Min. to 5” Max.above
condensate drain connection)
FurnaceCondensate
Drain Connection
From Evaporator Coil
Optional
Condensate Trap With Optional Overflow Switch
FIGURE 54
ML195UH with Evaporatoir Coil Using a Separate Drain
(Unit shown in horizontal left-hand discharge position)
.
5’ max.
PVC Pipe Only
4”min
5”max
Evaporator
Coil
Drain Pan
Condensate
Drain Connection
Field Provided Vent
(4” min. to 5” max. above
condensate connection)
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap