Sequence of Operation Flow Chart - Integrated Control 103085
HEATING SEQUENCE OF OPERATION
NORMAL HEATING MODE
ABNORMAL HEATING MODE
CONTROL SELF-CHECK OKAY?
NORMAL OPERATION:
LED: STEADY ON
NO
YES
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER DELAY OFF.
LED: OFF
POLARITY REVERSED.
LED: 9 FLASHES
POWER ON
IS POLARITY CORRECT?
ROLLOUT SWITCH CLOSED?
THERMOSTAT CALLS FOR
HEAT:
LED: STEADY ON
IS COMBUSTION AIR
PRESSURE SWITCH OPEN?
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
LED: 5 FLASHES
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES
AND POWER IS RESET OR T'STAT IS INTERRUPTED
FOR MINIMUM OF 1 SECOND.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON HEATING SPEED.
LED: 1 FLASH
GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH
DELAY.
LED: 2 FLASHES
(Sequence holds until pressure switch
opens or thermostat resets control.)
NO
NO
YES
YES
IS VOLTAGE
ABOVE 90 VOLTS?
LED: ON STEADY
IGNITOR WILL GLOW DIMLY BUT WILL NOT LIGHT
NO
NO
NO
IS COMBUSTION AIR INDUCER
ENERGIZED?
HAS COMBUSTION AIR PRESSURE
SWITCH CLOSED IN 2.5 MINUTES?
YES
YES
PRESSURE SWITCH IS IN WATCHGUARD MODE.
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY.
LED: 3 FLASHES
IS 5‐MINUTE RESET PERIOD COMPLETE?
NO
PRIMARY AND SECONDARY LIMIT SWITCH.
CLOSED?
YES
YES
CONTINUED NEXT
PAGE
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER ON
LED: 4 FLASHES
NO
YES
NO
YES
IS THERE A PROPER GROUND?
YES
NO
IMPROPER GROUND.
LED: OFF
CONTROL WILL NOT RESPOND TO CALL FOR HEAT
UNTIL PROPER GROUND.
YES
YES
BURNER OFF?
(Contiuous Flame Check)