Page 60
COOLING SEQUENCE OF OPERATION
NORMAL COOLING MODE
ABNORMAL COOLING MODE
IGNITION CONTROL MAIN POWER ON. LED: ON STEADY
CONTROL SELF DIAGNOSTIC CHECK.
IS CONTROL OPERATING NORMALLY?
YES
LED: 9 FLASHES
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
POWER ON
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
LED: OFF
INTERRUPT MAIN POWER TO RESET CONTROL.
YES
IS POLARITY CORRECT?
LED: ON STEADY.
REMAINS UNCHANGED THROUGHOUT COOLING CYCLE.
THERMOSTAT CALLS FOR COOLING.
COMPRESSOR CONTACTOR AND SYSTEM FAN
ENERGIZED WITH 1‐SECOND DELAY
(COOLING SPEED). EAC TERM. ENERGIZED.
COMPRESSOR OFF.
THERMOSTAT OPENS.
SYSTEM FAN AND EAC TERM. OFF
WITH 60‐SECOND DELAY.
NO
NO
IS VOLTAGE
ABOVE 90 VOLTS?
LED: ON STEADY.
CONTROL WILL CONTINUE TO CALL FOR
COOLING IN THIS CONDITION.
YES
NO
IS THERE A PROPER GROUND?
YES
NO
LED: ON STEADY
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
CONTINUOUS FAN SEQUENCE OF OPERATION
LED: ON STEADY
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN ON CONTINUOUS
BLOWER SPEED. EAC TERMINAL IS ENERGIZED.
THERMOSTAT CALLS FOR HEAT (W).
THERMOSTAT CALLS FOR COOLING.
THERMOSTAT OPENS.
SYSTEM FAN SWITCHED TO COOL SPEED.
EAC TERM. REMAINS ON.
THERMOSTAT OPENS.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN ON
CONTINUOUS BLOWER SPEED.
NO
YES
YES
NO
HUM TERM. ENERGIZES
WITH COMB. AIR INDUCER.
SYSTEM FAN SWITCHES TO
HEATING SPEED.
SYSTEM FAN SWITCHES TO
CONTINUOUS BLOWER SPEED
.
HUM TERM. DE-ENERGIZES
WITH COMB. AIR INDUCER