Page 40
CAUTION
Do not use copper tubing or existing copper
condensate lines for drain line
.
6 -
If unit will be started immediately upon completion
of installation, prime trap per procedure outlined in
Unit Start-Up section.
Condensate line must slope downward away from the
trap to drain. If drain level is above condensate trap,
condensate pump must be used. Condensate drain
line should be routed within the conditioned space to
avoid freezing of condensate and blockage of drain
line. If this is not possible, a heat cable kit may be used
on the condensate trap and line. Heating cable kit is
available from Lennox in various lengths; 6 ft. (1.8m) -
kit no. 26K68 and 24 ft. (7.3m) - kit no. 26K69.
HorizontalFurnace4” Min. to 5” Max.above
condensatedrain connection)
FurnaceCondensate
DrainConnection
From Evaporator Coil
Optional
Condensate Trap With Optional Overflow Switch
FIGURE 49
Furnace With Evaporator
Coil Using A Separate Drain
Condensate
DrainConnection
Field Provided Vent
(1” min. 2” max. above
condensate connection)
Evaporator drain
line required
(Trap at coil is optional)
FIGURE 50
Furnace with Evaporator
Coil Using a Common Drain
(1” min. to 2” Max.above
condensatedrain connection)
Condensate
DrainConnection
Evaporator drain
line required
(Trap at coil is optional)
FIGURE 51