background image

Page 44

IV-HEATING SYSTEM SERVICE CHECKS

A-C.S.A. Certification

All units are C.S.A. design certified without modifications. 

Refer  to  the  ML196UHE  Operation  and  Installation  In

-

struction Manual Information.

B-Gas Piping

 IMPORTANT

If a flexible gas connector is required or allowed by 

the authority that has jurisdiction, black iron pipe 

shall be installed at the gas valve and extend outside 

the furnace cabinet. The flexible connector can then 

be added between the black iron pipe and the gas 

supply line.

 WARNING

Do not over torque (800 in-lbs) or under torque (350 

in-lbs) when attaching the gas piping to the gas 

valve.

Gas supply piping should not allow more than 0.5”W.C. 

drop in pressure between gas meter and unit. Supply gas 

pipe must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be 

resistant to action of liquefied petroleum gases.

C-Testing Gas Piping

 IMPORTANT

In case emergency shutdown is required, turn off the 

main shut-off valve and disconnect the main power 

to unit. These controls should be properly labeled 

by the installer.

When pressure testing gas lines, the gas valve must be 

disconnected and isolated. Gas valves can be damaged if 

subjected to more than 0.5 psig (14” W.C.). See FIGURE 

56.

MANUAL MAIN SHUT-OFF

VALVE WILL NOT HOLD

NORMAL TEST PRESSURE

CAP

FURNACE

ISOLATE

GAS VALVE

1/8” N.P.T. PLUGGED TAP

FIGURE 56 

When  checking  piping  connections  for  gas  leaks,  use 

preferred means. Kitchen detergents can cause harmful 

corrosion corrosion on various metals used in gas piping. 

Use of a specialty Gas Leak Detector is strongly recom

-

mended. It is available through Lennox under part number 

31B2001. See Corp. 8411-L10, for further details.

 WARNING

Do  not  use  matches,  candles,  flame  or  any  other 

source of ignition to check for gas leaks.

D-Testing Gas Supply Pressure
Gas Flow (Approximate)

TABLE 17 

GAS METER CLOCKING CHART

ML196 

Unit

Seconds for One Revolution

Natural

LP/Propane

1 cu ft Dial 2 cu ft Dial 1 cu ft Dial 2 cu ft Dial

-030

120

240

300

600

-045

80

160

200

400

-070

55

110

136

272

-090

41

82

102

204

-110

33

66

82

164

-135

27

54

68

136

Natural-1000 btu/cu ft           LP-2500 btu/cu ft

Furnace should operate at least 5 minutes before check

-

ing gas flow. Determine time in seconds for two revolu

-

tions of gas through the meter. (Two revolutions assures 

a more accurate time.) Divide by two and compare to time 

in TABLE 17. If manifold pressure matches TABLE 19 and 

rate  is  incorrect,  check  gas  orifices  for  proper  size  and 

restriction. Remove temporary gas meter if installed.

NOTE - 

To obtain accurate reading, shut off all other gas 

appliances connected to meter.

Supply Pressure Measurement

When  testing  supply  gas  pressure,  use  the  1/8”  N.P.T. 

plugged  tap  located  on  the  gas  valve  to  facilitate  test 

gauge connection. See FIGURE 55. Check gas line pres

-

sure with unit firing at maximum rate. Low pressure may 

result in erratic operation or underfire. High pressure can 

result in permanent damage to gas valve or overfire.
On multiple unit installations, each unit should be checked 

separately, with and without other units operating. Supply 

pressure must fall within range listed in TABLE 19.

Manifold Pressure Measurement

Follow the steps below and use FIGURE 57 as a refer

-

ence. Gas manifold Kit 10L34 provides additional compo

-

nents if needed.

1 - 

 Connect the test gauge positive side “+“ to manifold 

pressure tap on gas valve.

2 -   Tee  into  the  gas  valve  regulator  vent  hose  and 

connect to test gauge negative “-”.

3 -   Start unit and let run for 5 minutes to allow for steady 

state conditions.

4 -   After allowing unit to stabilize for 5 minutes, record 

manifold  pressure  and  compare  to  value  given  in 

TABLE 19.

5 -   Shut  unit  off  and  remove  manometer  as  soon  as 

an accurate reading has been obtained. Take care 

to remove barbed fitting and replace threaded plug.

6 - 

 Start  unit  and  perform  leak  check.  Seal  leaks  if 

found.

Summary of Contents for ML196UH030XE36B

Page 1: ...ory equipped for use with natural gas A kit is available for conversion to LP Propane operation All ML196UHE units are equipped with a hot surface ignition system The gas valve is redundant to assure...

Page 2: ...Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations Isolated combustion system rating for non weatherized furnaces SPECIFICATIONS Gas Heating Performance Mod...

Page 3: ...98 Size of filter in 18 x 25 x 1 20 x 25 x 1 25 x 25 x 1 Side Return Single 44J22 44J22 44J22 Ten Pack 66K63 66K63 66K63 Size of filter in 16 x 25 x 1 16 x 25 x 1 16 x 25 x 1 NIGHT SERVICE KIT Night S...

Page 4: ...137 625 125 0 70 1210 395 1075 300 950 240 640 146 565 130 0 80 N A N A 1030 305 915 250 595 148 535 135 ML196UH030XE36B PERFORMANCE Less Filter External Static Pressure in w g Air Volume Watts at Va...

Page 5: ...cfm Watts 0 00 1470 313 1355 233 1195 171 975 92 895 50 0 10 1445 325 1330 249 1170 184 940 101 855 63 0 20 1430 335 1300 270 1150 196 885 109 735 75 0 30 1385 350 1265 275 1110 206 870 122 680 82 0...

Page 6: ...5 385 1165 290 0 80 1950 795 1670 580 1485 460 1360 390 1140 293 1895 790 1650 590 1465 470 1335 395 1120 295 ML196UH135XE60D PERFORMANCE Less Filter External Static Pressure in w g Air Volume Watts a...

Page 7: ...EMBLY CONTROL BOX former circuit breaker and interlock switch COMBUSTION AIR INDUCER BURNER ACCESS PANEL COMBUSTION AIR PRESSURE SWITCH PRIMARY LIMIT GAS VALVE BLOWER ASSEMBLY FLEXIBLE NO HUB EXHAUST...

Page 8: ...r T1 The breaker is rated at 3A at 32V If the current exceeds this limit the breaker will trip and all unit opera tion will shutdown The breaker can be manually reset by pressing the button on the fac...

Page 9: ...sor 5 Watchguard burner failed to light exceeded maximum number of retries or recycles 6 Not Used 7 Primary or Secondary Limit Open or Watchguard Mode Limit Switch Open longer than 3 minutes 8 Rollout...

Page 10: ...es into Watchguard Flame Failure mode After a 60 minute reset period the integrat ed control will begin the ignition sequence again Fan Time Control Ignition Control 103217 03 Heating Fan On Time The...

Page 11: ...rtbeat is indicated by 1s on 1s off It is used for idle continuous fan and cool modes Note 2 Error codes are indicated by a rapid flash the LED flashes X times at second on second off remains off for...

Page 12: ...6UHE units use an aluminized steel primary and stainless steel secondary heat exchanger assembly Heat is transferred to the air stream from all surfaces of the heat exchanger The shape of the heat exc...

Page 13: ...hrough the flame and sensing electrode The ig nition control allows the gas valve to remain open as long as flame signal is sensed NOTE The ML196UHE is polarity sensitive Make sure that the furnace is...

Page 14: ...icroAmps Multi Meter To Control Sensor Terminal To Flame Terminal Flame Sensor Terminal Flame Sensor Wire Intergrated Control Remove sensor from integrated control and connect alligator clip to flame...

Page 15: ...resistance of ignitor at the plug Reading should be between 39 and 70 ohms If the reading is correct then the problem is with the wiring between the jack plug and the control If reading is not correct...

Page 16: ...ducer orifice to insure proper flow through the heat exchanger The switch is a SPST N O pressure switch electrically connected to the integrated control The purpose of the switch is to prevent burner...

Page 17: ...d end header box are negative How sure than the port 4 Operate unit and observe manometer reading Readings will change as heat exchanger warms a Take one reading immediately after start up b Take a se...

Page 18: ...tial pressure across the pressure switch Check for restricted inlet vent Remove all block age Check for proper vent sizing and run length See table 13 Wrong pressure switch installed in the unit or pr...

Page 19: ...ltage is present in tests 1 and 2 and motor is not operating properly replace motor The motor is not field repairable If replacing the indoor blower motor or blower wheel is necessary placement is cri...

Page 20: ...peed tap used for continuous fan 1 2 3 4 or 5 on input plug P49 If 24 volts is not present problem may be up stream of plug P49 Proceed to test 4 Multi Meter set to VAC 12 0 12 0 24 Multi Meter set to...

Page 21: ...ximately the same resistance within an ohm 3 Check to see if the blower wheel spins freely Motor Test FIGURE 19 TABLE 9 Scale Measurement range in words ohms 2 M two megohm two million ohms 0 2 000 00...

Page 22: ...PolyPro by Duravent InnoFlue by Centrotherm UL 1738 CERTIFIED GAS VENTING SYSTEM IPEX System1738 Schedule 40 PVC Pipes and Fittings UL1738 IPEX System1738 PVC FGV Cement Primer Not approved as of 12...

Page 23: ...ermination kits 30G28 44W92 4493 and 81J20 are certified to ULC S636 for use in Canada only 5 See table 8 for vent accelerator requirements 6 Requires field provided 2 to 1 1 2 reducer Joint Cementing...

Page 24: ...vacation home make provisions for draining condensate collection trap and lines If replacing a furnace which was commonly vented with another gas appliance the size of the existing vent pipe for that...

Page 25: ...combination vent pipe may be used Contact Lennox Application Department for assis tance in sizing vent pipe in these applications NOTE The exhaust collar on all models is sized to ac commodate 2 Sched...

Page 26: ...43 123 122 103 103 65 5 n a 61 46 24 95 95 73 38 118 117 98 98 60 6 56 41 19 90 90 68 33 113 112 93 93 55 7 51 36 14 85 85 63 28 108 107 88 88 50 8 46 31 n a 80 80 58 23 103 102 83 83 45 9 41 26 75 7...

Page 27: ...100 84 49 116 116 109 109 65 3 10 n a 63 48 32 12 95 95 79 44 111 111 104 104 60 4 n a 58 43 27 n a 90 90 74 39 106 106 99 99 55 5 53 38 22 85 85 69 34 101 101 94 94 50 6 48 33 17 80 80 64 29 96 96 89...

Page 28: ...10 n a 61 46 24 n a 90 90 68 33 108 107 88 88 50 4 n a 56 41 19 85 85 63 28 103 102 83 83 45 5 51 36 14 80 80 58 23 98 97 78 78 40 6 46 31 9 75 75 53 18 93 92 73 73 35 7 41 26 n a 70 70 48 13 88 87 6...

Page 29: ...r pipe in horizontal runs of exhaust pipe Exhaust 6 Min FIGURE 25 SIDE VIEW 2 2 2 or TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT OR NON DIRECT VENT APPLICATIONS RIGHT HAND DISCHAR...

Page 30: ...e screen to route the intake piping as shown in FIGURE 27 or FIGURE 28 Maintain a minimum clearance of 3 76mm around the air intake opening The air intake opening with the protective screen should alw...

Page 31: ...and the flue gases are discharged to the out doors The ML196UHE is then classified as a direct vent Category IV gas furnace In both Non Direct Vent and Direct Vent applications the vent termination i...

Page 32: ...15 N A 22 N A 3 in N A N A 2 2 10 10 16 16 13 13 1Refer to 99 Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook 2 Poly Propylene vent pipe PP by Dur...

Page 33: ...al to or greater than soffit depth 3 feet 9m 12 3 feet 9m within a height 15 feet 4 5m above the meter regulator assembly 3 feet 9m 6 inches 152mm for appliances 10 000 Btuh 3kw 12 inches 305mm for ap...

Page 34: ...feet 4 5m above the meter regulator assembly 3 feet 9m 6 inches 152mm for appliances 10 000 pliances 10 000 Btuh 3kw and 50 000 pliances 50 000 Btuh 15kw 6 inches 152mm for appliances 10 000 Btuh 3kw...

Page 35: ...ssure zones the maximum separation requirement of intake and exhaust pipe DOES NOT apply 3 On roof terminations the intake piping should terminate straight down using two 90 elbows See FIGURE 34 4 Exh...

Page 36: ...ROVIDED REDUCER MAY BE REQUIRED TO ADAPT DIFFERENT VENT PIPE SIZE TO TERMINATION INTAKE Accelerator not required for 3 concentric 12 305mm FIGURE 38 12 305mm Min above grade or average snow ac cumulat...

Page 37: ...ective shield is recommended The shield should be constructed using wood sheet metal or other suitable material All seams joints cracks etc in affected area should be sealed using an appropriate seala...

Page 38: ...OVIDE SUPPORT FOR EXHAUST LINES 12 305mm ABOVE AVE SNOW ACCUMULATION FIGURE 43 Crawl Space and Extended Horizontal Venting Lennox provides kit 51W18 USA kit 15Z70 Canada to install 2 or 3 PVC exhaust...

Page 39: ...drain Condensate line must maintain a 1 4 downward slope from the furnace to the drain Unit shown in upflow position with remote trap 5 max T o Drain PV CPipeOnly FieldProvidedVent Min 1 AboveCondens...

Page 40: ...sed on the condensate trap and line Heating cable kit is available from Lennox in various lengths 6 ft 1 8m kit no 26K68 and 24 ft 7 3m kit no 26K69 HorizontalFurnace4 Min to 5 Max above condensatedra...

Page 41: ...FIGURE 52 Furnace with Evaporator Coil Using a Common Drain Unit shown in horizontal left hand discharge position Condensat e Drain Connection 4 min to 5 Max above condensatedrain connection 5 max PV...

Page 42: ...ction In Unit Condensate Drain Connection In Unit Vent To Drain Condensate Drain Connection In Unit Optional Condensate Drain Connection OptionalDrainPipingFromTrap DrainTrapAssembly Furnished DrainTr...

Page 43: ...he trap should be primed with sufficien water to ensure proper condensate drain operation WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage...

Page 44: ...Gas Flow Approximate TABLE 17 GAS METER CLOCKING CHART ML196 Unit Seconds for One Revolution Natural LP Propane 1 cu ft Dial 2 cu ft Dial 1 cu ft Dial 2 cu ft Dial 030 120 240 300 600 045 80 160 200...

Page 45: ...e maximum carbon monoxide reading should not exceed 100 ppm TABLE 18 ML196UHE Unit CO2 Nat CO2 LP 030 7 5 8 5 8 2 9 5 045 070 090 110 135 H High Altitude NOTE In Canada certification for installations...

Page 46: ...he conversion procedure TABLE 20 Conversion Kit and Pressure Switch Requirements at Varying Altitudes ML196 Model Natural to LP Propane High Altitude Natural Burner Orifice Kit High Altitude LP Propan...

Page 47: ...s a function of load indicates a poor or partial ground Compare the readings to the table below If the readings exceed the maximum shown in TABLE 21 make repairs before operating the furnace 2 In addi...

Page 48: ...urn air plenums Insert manometer hose flush with inside edge of hole or insulation Seal around the hose with permagum Connect the zero end of the manometer to the discharge supply side of the system O...

Page 49: ...winter and the indoor coil to freeze in the summer resulting in an increase in the number of service calls Before using any filter with this system check the specifications provided by the filter man...

Page 50: ...essure switch assembly Remove the assembly Keep tubing attached to pressure switches 14 Disconnect the plug from the combustion air inducer Remove two screws which secure combustion air inducer to col...

Page 51: ...ssembly if needed 1 Turn off electrical and gas power supplies to furnace Remove upper and lower furnace access panels 2 Disconnect the wires from the gas valve 3 Remove the burner box cover if equipp...

Page 52: ...or heat can continue 5 A92 integrated control energizes B6 combustion air inducer S18 combustion air pressure switch closes Once S18 closes a 15 second pre purge follows 6 A92 integrated control energ...

Page 53: ...ALVE ENERGIZED GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED FLASHES CODE 11 PRESSURE SWITCH CLOSED GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY S...

Page 54: ...RESET IGNITION SEQUENCE FOUR TIMES FLAME SIGNAL 1 5 MICROAMPS OR GREATER YES YES YES ROLLOUT SWITCH CLOSED LED FLASHES CODE 8 ROLLOT SWITCH OPEN GAS VALVE POWER OFF COMBUSTION AIR INDUCER POWER ON IND...

Page 55: ...ITCH CLOSED LED SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED EAC TERM ENERGIZ...

Page 56: ...AN SWITCHED TO COOL SPEED EAC TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G ENERGIZES SYSTEM FAN AT FAN SPEED EAC TERM ENERGIZED NO YES YES NO SYSTEM FAN SWITCHES...

Page 57: ...Page 57...

Reviews: