TABLE 19
Manifold and Supply Line Pressure 0-10,000ft.
ML196
Unit
Gas
Manifold Pressure in. wg.
Supply Line Pressure
in. w.g.
0 - 10000 ft.
0 - 4500 ft 4501 - 5500 ft 5501 - 6500 ft 6501 - 7500 ft 7501 - 10,000 ft
All
Models
Natural
3.5
3.3
3.2
3.1
3.5
4.5
13.0
L.P. Propane
10.0
9.4
9.1
8.9
10.0
11.0
13.0
NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the
conversion procedure.
TABLE 20
Conversion Kit and Pressure Switch Requirements at Varying Altitudes
ML196 Model
Natural to LP/
Propane
High Altitude
Natural Burner
Orifice Kit
High Altitude
LP/Propane Burner
Orifice Kit
High Altitude Pressure Switch
0 - 7500 ft
(0 - 2286m)
7501 - 10,000 f t
(2286 - 3038m)
7501 - 10,000 ft
(2286 - 3038m)
4501 - 7500 ft
(1373 - 2286m)
7501 -10,000 ft
(2286 - 3048m)
-030
17H63
14C90
17H66
11U66
11U69
-045
*11K49
73W37
*11K44
11U66
11U69
-070
11U70
11U68
-090
11U70
11U64
-110
11U70
11U64
-135
11U70
11U68
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-