Page 2
SPECIFICATIONS
Gas
Heating
Performance
Model No.
ML296UH045XV36B
ML296UH070XV36B
AHRI Reference No.
N/A
N/A
1
AFUE
96%
96%
High
Fire
Input - Btuh
44,000
66,000
Output - Btuh
42,000
62,000
Temperature rise range - °F
35 - 65
50 - 80
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10.0
3.5 / 10.0
Low
Fire
Input - Btuh
29,000
43,000
Output - Btuh
28,000
41,000
Temperature rise range - °F
20 - 50
25 - 55
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
1.7 / 4.9
1.7 / 4.9
High static - in. w.g.
Heating
0.8
0.8
Cooling
1.0
1.0
Connections
in.
Intake / Exhaust Pipe (PVC)
2 / 2
2 / 2
Gas pipe size IPS
1/2
1/2
Condensate Drain Trap (PVC pipe) - i.d.
3/4
3/4
with furnished 90° street elbow
3/4 slip x 3/4 Mipt
3/4 slip x 3/4 Mipt
with field supplied (PVC coupling) - o.d.
3/4 slip x 3/4 MPT
3/4 slip x 3/4 MPT
Indoor
Blower
Wheel nominal diameter x width - in.
10 x 9
10 x 9
Motor output - hp
1/2
1/2
Tons of add-on cooling
2 - 3
2 - 3
Air Volume Range - cfm
485 - 1370
500 - 1365
Electrical Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
7.7
7.7
Maximum overcurrent protection
15
15
Shipping Data
lbs. - 1 package
130
138
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.
Gas
Heating
Performance
Model No.
ML296UH090XV48C
ML296UH110XV60C
AHRI Reference No.
N/A
N/A
1
AFUE
96%
96%
High
Fire
Input - Btuh
88,000
110,000
Output - Btuh
84,000
106,000
Temperature rise range - °F
45 - 75
45 - 75
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10.0
3.5 / 10.0
Low
Fire
Input - Btuh
57,000
72,000
Output - Btuh
55,000
70,000
Temperature rise range - °F
30 - 60
35 - 65
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
1.7 / 4.9
1.7 / 4.9
High static - in. w.g.
Heating
0.8
0.8
Cooling
1.0
1.0
Connections
in.
Intake / Exhaust Pipe (PVC)
2 / 2
2 / 2
Gas pipe size IPS
1/2
1/2
Condensate Drain Trap (PVC pipe) - i.d.
3/4
3/4
with furnished 90° street elbow
3/4 slip x 3/4 Mipt
3/4 slip x 3/4 Mipt
with field supplied (PVC coupling) - o.d.
3/4 slip x 3/4 MPT
3/4 slip x 3/4 MPT
Indoor
Blower
Wheel nominal diameter x width - in.
11 x 11
11 x 11
Motor output - hp
3/4
1
Tons of add-on cooling
2.5 - 4
3 - 5
Air Volume Range - cfm
680 - 1770
790 - 1955
Electrical Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
10.1
12.8
Maximum overcurrent protection
15
20
Shipping Data
lbs. - 1 package
163
174
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.