background image

4

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

LENNOX HEARTH PRODUCTS  •  MERIT PLUS

®

 B-VENT GAS FIREPLACES (MPB33/35/40/45)  •  INSTALLATION INSTRUCTIONS

Test gauge connections are provided on the 

front of the millivolt and electronic gas control 

valve (identified IN for the inlet and OUT for the 

manifold side). The control valves have a 3/8" 

(10 mm) NPT thread inlet and outlet side of the 

valve (refer to 

Figures 1 and 2

).

Propane tanks are at pressures that will cause 

damage to valve components. Verify that the 

tanks have step down regulators to reduce the 

pressure to safe levels.

ORIFICE SIzES - SEA LEVEL TO HIGH 

ALTITUDE (ALL MODELS)

These appliances are tested and approved for 

installation at elevations of 0 - 4500 ft (0 - 1372 

m) above sea level using the standard burner 

orifice sizes (marked with an "*" in 

Table 4

)

For elevations above 4500 ft, contact your gas 

supplier or qualified service technician. 

Deration

 - At higher elevations, the amount 

of BTU fuel value delivered must be reduced 

by either:

•  Using gas that has been derated by the gas 

company.

• Changing the burner orifice to a smaller size 

as regulated by the local authorities having 

jurisdiction and by the (USA) National Fuel 

Gas Code NFPA 54/ANSI Z223.1 - latest 

edition or, in Canada, the CAN/CGA-B149.1 

codes - latest edition.

Fuel #

Low

High

Natural Gas

2.2" WC

(0.55 kPa)

3.5" WC

(0.87 kPa)

Propane

6.3" WC

(1.57 kPa)

10.0" WC

(2.49 kPa)

Table 3 - Manifold Gas Supply Pressure

The appliance and its appliance main gas 

valve must be disconnected from the gas 

supply piping system during any pressure 

testing of that system at test pressures 

in 

excess of

 1/2 psi (3.5 kPa).

The appliance must be isolated from the gas 

supply piping system by closing its equipment 

shutoff valve during any pressure testing of 

the gas supply piping system at test pres-

sures equal to or 

less than

 1/2 psi (3.5 kPa).

Fuel #

Minimum

Maximum

Natural Gas

4.5" WC

(1.12 kPa)

10.5" WC

(2.62 kPa)

Propane

11.0" WC

(2.74 kPa)

13.0" WC

(3.24 kPa)

Table 2 - Inlet Gas Supply Pressure 

GAS PRESSURE - ALL MODELS

Tables 2 and 3

 

show the appliances' inlet and 

manifold gas pressure requirements:

REqUIREMENTS FOR THE COMMON-

WEALTH OF MASSACHUSETTS

These fireplaces are approved for installation in 

the US state of Massachusetts if the following 

additional requirements are met:

•  Install  this  appliance  in  accordance  with 

Massachusetts Rules and Regulations 248 

C.M.R. 

•  Installation and repair must be done by a 

plumber or gas fitter licensed in the Com-

monwealth of Massachusetts.

•  The flexible gas line connector used shall 

not exceed 36 inches (92 centimeters) in 

length.

•  The individual manual shut-off must be a 

T-handle type valve.

Cold Climate Insulation

For cold climate installations, seal all cracks 

around your appliance with noncombustible 

material and wherever cold air could enter 

the room. It is especially important to insulate 

outside chase cavity between studs and under 

floor on which appliance rests, if floor is above 

ground level. Gas line holes and other openings 

should be caulked or stuffed with unfaced 

fiberglass insulation. 

Install the appliance according to the regulations 

of the local authorities having jurisdiction and, 

in the USA, the National Fuel Gas Code NFPA 

54 - latest edition / ANSI Z223.1 or, in Canada, 

the CAN/CGA-B149.1 - latest edition. 
Flame breadth, height and width will diminish 

4% for every 1,000 feet of altitude. 

Gas Valve 

Diagrams

See 

Figure 1

 for millivolt models 

and 

Figure 2 

for electronic models.

In Canada - CAN/CGA-2.17-M91 (R2009) 

(high altitude): THE CONVERSION SHALL 

BE CARRIED OUT BY A MANUFACTUR-

ER’S AUTHORIzED REPRESENTATIVE, 

IN ACCORDANCE WITH THE REqUIRE-

MENTS OF THE MANUFACTURER, PRO-

VINCIAL OR TERRITORIAL AUTHORITIES 

HAVING JURISDICTION AND IN ACCOR-

DANCE WITH THE REqUIREMENTS OF 

THE CAN/CGA-B149.1 OR CAN/CGA-

B149.2 INSTALLATION CODES.

H I

LO

W

HT

PT

HT

PT

PILO

T

PI

LO

T

ON

it

OFF

IN

OUT

HI/LO Variable

Flame Height

Adjustment

Figure 1 - SIT Millivolt Gas Valve

Manifold Pressure Tap

Inlet Pressure Tap

Pilot Adjustment

Screw

Main Gas Control Knob

OFF/PILOT/ON

Orange Wire

(from DFC Wire 

Harness)

Main Gas Inlet

3/8" NPT

Green Wire

(from DFC Wire Harness)

Inlet (IN) Test Port

Manifold (OUT) Test Port

Figure 2 - SIT Electronic Gas Valve

Hi/Lo Flame 

Control Knob

Yellow Ground Wire

(from DFC Wire Harness)

Burner Orifice Sizes 

Elevation 0-4500 feet ( 0-1372 meters)

Model

Nat.Gas

drill size (inches)

Propane

drill size (inches)

MPB33

#47 (0.0785")*

99K74 •

(0.048")*

99K78 •

MPB35

#44 (0.086")*

60J80 •

#55 (0.052")*

19L52 •

MPB40

#38 (0.102")*

99K76 •

(0.062")*

21L01 •

MPB45

#37 (0.104")*

24M10 •

#52 (0.0635")*

37G00 •

Table 4 

* Standard size installed at factory

•  Part /Cat. Number

Summary of Contents for MPB33CNE

Page 1: ... SURFACE VITRÉE CHAUDE PEUT CAUSER DES BRÛLURES LAISSER REFROIDIR LA SURFACE VITRÉE AVANT D Y TOUCHER NE PERMETTEZ JAMAIS À UN ENFANT DE TOUCHER LA SURFACE VITRÉE EL VIDRIO CALIENTE CAUSARÁ QUEMADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NIÑOS DEBEN NUNCA TOCAR EL VIDRIO Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT ...

Page 2: ...on 5 Vent Termination Clearances 5 Appliance and Vent Clearances 6 Pre Installation Steps 7 Typical Installation Sequence 7 Detailed Installation Steps 7 Step 1 Framing 7 Framing Specifications 8 Fireplace Specifications 9 Step 2 Routing Gas Line 9 Step 3 Installing Vent System 10 Step 4 Field Wiring 11 Step 5 Wiring Optional Forced Air Blower Kit 12 Step 6 Connecting Gas Line 12 Step 7 Installing...

Page 3: ...nal Safety Standards and are tested and listed by OMNI Test Laboratories Inc Report No 116 F 36d 5 toANSIZ21 50b 2009 inCanada CSA 2 22b 2009 and CAN CGA 2 17 M91 R2009 in both USA and Canada as vented gas fireplaces Bothmillivoltandelectronicversionsofthese appliances may be used in bedrooms only when the room is an unconfined space as defined by the National Fuel Gas Code Use in bedrooms may not...

Page 4: ...onin the US state of Massachusetts if the following additional requirements are met Install this appliance in accordance with Massachusetts Rules and Regulations 248 C M R Installation and repair must be done by a plumber or gas fitter licensed in the Com monwealth of Massachusetts The flexible gas line connector used shall not exceed 36 inches 92 centimeters in length The individual manual shut o...

Page 5: ...d out of traffic and away from furniture and draperies Figure 3 En raison des températures élevées l appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures Figure 3 The location should also be free of electrical plumbing or other heating air conditioning ducting Be aware that this is a heat producing ap pliance Objects placed above the unit ...

Page 6: ... side of the fireplace may abutt a perpendicular wall For this type of installation the other side of the fireplace must be a flat wall to allow for proper air flow and burner operation Combustiblematerialsmayprojectbeyondone or both sides of the fireplace opening when these materials are kept within the Safe Zone illustrated in Figure 6 3 1 2 in 89mm Top View of Fireplace Combustiblematerials may...

Page 7: ...abs one on each side located at the base of the fireplace and secure to the floor by nailing with 8d nails or equivalent see Figure 10 Anchor Tab Step 10 REMOVING AND Installing THE Glass Door Page 19 Step 11 Burner Adjustments Page 19 Adjust burner primary air shutter to achieve proper flame appearance Step 12 TESTING VENT OPERATION Page 21 Vent operation test and safety limit switch operation St...

Page 8: ... Enclosure Including Finishing Materials if any Rough Framing Face Unfinished Shown o N l e d o M A t i n U e z i S A g n i m a r F e z i S B C D E F G H J K n i 5 3 8 1 5 3 4 1 5 3 4 1 9 1 8 5 9 1 7 5 2 1 4 3 8 2 6 1 4 6 1 9 6 8 5 0 4 m m 2 9 8 5 9 8 5 9 8 3 8 4 8 9 4 0 6 4 1 0 3 7 6 0 4 2 0 1 7 6 1 2 3 0 1 n i 8 1 0 4 4 1 0 4 4 1 0 4 4 2 8 5 4 2 6 1 3 1 1 6 6 1 1 0 3 6 1 4 6 1 9 6 2 3 1 1 3 4 m ...

Page 9: ...lynoone unfamiliarandunqualifiedshouldattemptsizing or installing gas piping NOTES All appliances are factory equipped with a flexible gas line connector and 1 2 shutoff valve see Figure 21 on Page 13 Step 2 ROUTING Gas Line Routea1 2 13mm gaslineasshowninFigure 13 Gas lines must be routed constructed and made of materials that are in strict accordance withlocalcodesandregulations Theappliance as ...

Page 10: ...rtical is used or 15 4 6 m when an offset is greater than 45 degrees and up to 60 degrees see Figure 17 The offset may start at the fireplace flue collar The maximum overall height of the vent system and appliance should not exceed 40 feet Install the B vent system in accordance with the vent manufacturer s instructions Required Pipe Diameter MPB33 series Requires 4 102 mm MPB35 series Requires 5 ...

Page 11: ...TIONAL GROUND BATTERY HOLDER DFC WIRE HARNESS SPARK WIRE CABLE PILOT GROUND WIRE PILOT SENSOR CABLE HOOD IGNITER ROD FLAME SENSOR PILOT TUBE CPI SWITCH OFF O INTERMITTENT PILOT MODE ON STANDING PILOT MODE PROFLAME DFC BOARD PROFLAME VALVE ELECTRONIC PILOT ASSEMBLY B BLACK BR BROWN GY GRAY PU PURPLE R RED BL BLUE G GREEN O ORANGE W WHITE Y YELLOW WIRING COLOR CODE B B B R R W W B B B B BL BL G G O ...

Page 12: ... the grounding prong from the plug Step 6 Connecting Gas Line Make gas line connections All codes require a shut off valve mounted in the supply line The orientation of the shut off valve should face the front see Figure 22 Figure 21 illustrates two methodsforconnectingthegassupply Theflex line method is acceptable in the U S however Canadian requirements vary depending on locality Installation mu...

Page 13: ... DONOTterminatetheductcloserthan3 below the chimney top Outside supplemental combustion air ducting may be run upwards or vertically through framing and ceiling joists with the hood installed through an outside wall and 3 1 m belowthetermination Ductingmayalsoberun downward through floor joists and under the hometoaventilatedcrawlspacenotconsidered part of the living area of the home Outside Air C...

Page 14: ... for MPB35 Series appliances and Figure 30 for MPB40 and MPB45 Series appliances NOTE Turn off all electricity to the appliance before you install volcanic stone embers and logs The flame should project 1 25 mm beyond the hood at all three ports see Figure 24 Replace logs if removed for pilot inspection To light the burner turn ON the remote wall switch and rotate the gas valve control knob counte...

Page 15: ...nt door see Removing the Glass Enclosure Panel on Page 19 Step 2 Install decorative volcanic stone Sprinkle the decorative volcanic stone in a pleasing pattern The volcanic stone should be placed directly on top of the firebox bottom along the front and to the back at the right and left sides of the burner Position any optional ceramic fiber liners before placing the stone Logs should be positione...

Page 16: ...upper end Place the left log and then the smaller left and right top logs All logs that have notches to fit over the grate tines should be positioned with these notches directly against the grate All top logs that rest on lower logs do so over flattened mounting faces in the bottom logs Properlogandtwigplacementiscriticaltoencourageoutstanding flame appearance and prevent sooting 3 2 4 5 6 1 2 3 4...

Page 17: ... placed in the order shown Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the hole on its upper end Place the left log and then the smaller left and right top logs All logs that have notches to fit over the grate tines should be positioned with these notch...

Page 18: ...ion the individual logs as shown below Logs should be placed in the order shown Position the center log on the burner first then place the glowing embers as shown in Figure 27 Place the rear log both the right and left and then the smaller left and right top logs All logs that have notches to fit over the grate tines should be positioned with these notches directly against the grate All top logs t...

Page 19: ...t appear sooty NOTE Thefollowingchartisprovidedtoaidyou in achieving the correct air shutter adjustment for your installation Removing the Glass Enclosure Panel see Figure 31 Removethetoplouverassembly Openthelower control compartment door see Figure 22 on Page 13 by pressing in simultaneously at the left and right top corners of the door the door is hinged at the bottom Remove the bottom compartm...

Page 20: ...position 1 Refer to Figures 32 33 and 34 for proper flame appearance To adjust the flame refer to Figure 35 and move the rod up and down the adjustment rod is located in the lower control area Position the air shutter to the factory setting as shown in Table 8 2 Light appliance follow lighting procedure on lighting label in control compartment or in the Care and Operation Instructions 3 Allow the ...

Page 21: ...ure 37 for its location If during appliance operation the flame goes out independently of the burner on off wall switch it may be due to a blocked vent If this condition occurs the safety limit switch will activate causing the fireplace burner to shut off To reset the safety limit switch perform the following steps NOTE Allow the appliance to cool completely 7 Remove the top louver panel 8 Reset t...

Page 22: ...de est utilisée pour contrôler le foyer nettoyez la soigneusement pour éliminer la poussière et les traces de graisse ou d huile Collez l étiquette sur le boîtier de la télécommande Figure B Choisissez la langue qui est principale ment parlée dans la résidence du propriétaire En cas de doute collez l étiquette en anglais 3 Si vous ne trouvez pas les étiquettes veuillez appeler Lennox Hearth Produc...

Page 23: ...sembly C Remove the burner assembly with attached venturi tube Millivolt and Electronic Ignition System Appliances Step 1 SIT Systems Refer to Figure 38 and the instructions provided with the SIT Regu lator Conversion Kit Using a Torx T20 driver to remove and discard the pressure regulator mounting screws two screws for electronic models three screws for millivolt models pressure regulator tower t...

Page 24: ...y proper burner ignition and operation See Burner Adjustments and Burner Flame Appearance on Pages 19 and 20 Step 12 Inspect the pilot system for proper flame The pilot flame should engulf the flame sensor as shown in Figures 24 and 25 on Page 14 Step 13 Using a manometer test the inlet and manifold gas pressures see Tables 2 and 3 on Page 4 ALWAYS TEST PRESSURES WITH THE VALVE REGULATOR CONTROL A...

Reviews: