Adjust the blower speed so that the temperature rise
is within the rise specified on the rating plate. Consult the
wiring diagram for speed changes on the direct drive
motor.
Limit Control Checkout:
After the furnace has been in operation for at least 15
minutes, restrict the return air supply by blocking the
filters or closing the return registers and allow the furnace
to shut down on high limit. The main burners will shut
OFF and the main blower and combustion blower should
continue to run. Remove the restriction and the burners
should come back on in a few minutes.
Flame Rollout Switch:
This unit is equipped with two (2) manual reset flame-
rollout switches that protects against improper venting of
the flue gases from the heat exchanger due to blockage
causing heat (or flames) to "rollout" into the burner box
from the heat exchangers, either safety device will
activate and shut off power to the automatic gas valve
before there is damage to the furnace. The loss of power
to the gas valve will shut off the gas burners. Should this
occur, it will be necessary to determine the cause of the
rollout, correct the condition that caused it, and reset the
flame-rollout switch.
The furnace should be allowed to cool-off before
attempting to reset the switch. Failure to follow
these instructions could result in injury due to burns!
The switch located behind the burner access panel is
accessed by removing the burner access panel from the
furnace, and is reset by pushing in the button in the
middle of the switch (between the two wire connections -
See Figure 16). Very little force is required to push the
reset button, and a "click" should be heard when the
switch resets.
Figure 16
FLAME ROLLOUT SWITCH
Pressure Switch Check:
To check the operation of the pressure switch vent
safety control, remove the vent adaptor from the
combustion blower. Place the furnace into operation.
Gradually cover up the blower outlet; the main burners
should shut OFF. Remove the restriction and the unit
should relight. Replace the vent adaptor and reseal the
opened joints as required.
The operational checkout is now complete. Be sure
to adjust the thermostat to the desired setting and inform
the homeowner how to operate the furnace system before
leaving the job site.
If the pressure switch activates to shut the furnace
down, the vent system must be checked and
cleared. Failure to do so may result in serious
bodily harm or nuisance furnace shutdown and/or
a hazardous condition that may lead to property
damage, personal injury or death.
20541501
Issue 0240
Page 21 of 26
Summary of Contents for MPGA 050 B3
Page 1: ...APPLICATION GUIDE GAS FURNACE Fit s All 80 English 02 2004...
Page 2: ......
Page 5: ......
Page 7: ...FURNACE WIRING SPECIFICATIONS 20541501 Issue 0240 Page 5 of 26...
Page 19: ...20541501 Issue 0240 Page 17 of 26 THEORY OF OPERATION...
Page 24: ...SEQUENCE OF OPERATION Direct ignition system control 20541501 Issue 0240 Page 22 of 26...
Page 27: ...TROUBLE SHOOTING With LED Indicator Assistance 20541501 Issue 0240 Page 25 of 26...
Page 28: ...WIRING DIAGRAM 20541501 Issue 0240 Page 26 of 26...
Page 36: ......