Application Guide
•
MWC-0410-E
• 3 •
FEATURES AND BENEFITS
ELECTRICAL BOX
The MWC is designed for 400V/3/50Hz supply.
- Unit electrical cabinet, components and wiring in compliance
with EN 60204-1 electrical directive.
- 400V/3/50Hz power supply (without neutral) with a single
point of power connection.
- IP24 protection class.
- Recognized brand electrical components for ease of main-
tenance.
- Main on/off switch mounted on the front panel.
- DC50 user interface mounted on the front panel.
- 400/24 V transformer to supply the control circuit.
- Labelled electrical wires to facilitate maintenance and dia-
gnostic.
- Optional power and control circuit for the pumps.
CONTROL
CLIMATIC™ microprocessor based control is providing the
following functions:
- 4 scheduling time zones per day over 7 days to allow energy
consumption management according to the building use and
environmental constraints.
- PI control of the water temperature with operating time
equalisation of the compressors.
- Intelligent advanced control algorithm to protect the compres-
sors against excessive short-cycling and to allow operation
of the unit without buffer tank in most comfort air conditioning
applications (e.g. unit with fan-coils). Refer to minimum ins-
tallation water loop volume recommendations.
- Water pump control with operating time equalization and
automatic change-over in case of a pump fault (Twin pump
only).
- Master/slave or cascade control of two chillers operating
in parallel with operating time equalization and automatic
change-over in case of a unit fault.
CLIMATIC™ is pre-factory con
fi
gured with default settings
allowing a fast commissioning on site. The DC50™ user interface
with graphical display is easy to use, intuitive. Main customer
parameters can be read or modi
fi
ed without main power shut-off
(Entering/leaving water temperatures, alarms, water set-points,
high and low pressure readings).
The DS50™ service display (optional) is a .plug and play"
controller that allows service people to read and modify all
unit parameters (Unit settings, operating time and number of
compressor starts, low and high pressure reading, read the
history of last 32 faults...).
COMMUNICATION
The control board is equipped with a RS485 serial communication
port to allow remote management through communication
bus.
According to the wished communication protocol, our control
board can be
fi
tted with ModBUS®, LonWorks® or BacNET®
communication interface (options).
The main control board has free dry contacts that allow remote
control of the unit by wired cable:
- Remote on/off of the unit.
- Remote alarm reset to re-start the unit.
- Alarm or alert indications.
- Free customer contact.
With the optional extension board BE50, it is possible to get
additional customized digital or analog inputs/outputs for remote
control of the unit:
- Fault pumps (dry contact).
- Operation indication at 100% on circuit 1 or 2 (dry
contact).
- Dual water set-point management (dry contact).
- Force heating or cooling mode (24V AC input).
- Power limitation by disabling circuit 1 or 2 (24V AC input).
- Force unoccupied mode (24V AC input).
- Water set-point offset based on a 4-20mA signal.
DIRECTIVES
The unit is built to meet European norms and standards &
Eurovent certiFIcation performance standards.
. DI 97/23/CE Pressure Equipment Directive.
. DI 98/37/CE Machinery Directive.
. DI 73/23/CE Low Voltage Directive.
. DI 89/336/CE Electro Magnetic Compatibility Directive
. EN 378-2 Safety and Environmental Directive.
. The European Restriction of the Use of Certain Hazardous-
Substances (RoHS).