MWC™
180
230
280
330
380
kW
186,1
232,8
280,7
333,6
380,4
kW
39,3
49,9
59,7
70,9
81,0
A
70,6
86,6
101,1
118,1
133,2
EER
4,74
4,66
4,70
4,70
4,70
ESEER
(2)
6,74
6,31
6,38
6,25
6,03
m
3
/h
32,0
40,1
48,3
57,4
65,4
kPa
34,9
28,9
40,7
31,5
40,2
m
3
/h
37,2
46,7
56,2
66,8
76,2
kPa
46,2
38,3
30,3
41,8
40,5
kW
196,5
246,4
296,9
351,9
401,7
kW
48,5
61,5
73,1
86,9
99,1
A
86,6
110,0
130,7
155,3
177,1
4,05
4,00
4,06
4,05
4,05
m
3
/h
33,8
42,4
51,1
60,5
69,1
kPa
38,6
32,1
25,4
34,8
33,7
m
3
/h
32,0
40,1
48,3
57,4
65,4
kPa
34,9
28,9
40,7
31,5
40,2
4
4
4
4
4
%
20-50-75-
100%
21-43-62-83-
100%
21-36-53-71-
85-100%
15-46-61-87-
100%
25-50-75-
100%
l
(2 x 3,2)
+ (2 x 3,2)
(3,2+6,3)
+ (2 x 3,2)
(3,2+6,3)
+ (3,2+6,3)
(2 x 6,3)
+ (3,2+6,3)
(2 x 6,3)
+ (2 x 6,3)
R410A
2
2
2
2
2
kg
8
12
14
14
22
l
13
24
35
35
43
kPa
600
600
600
600
600
4"
4"
4"
4"
4"
l
13
24
24
35
35
kPa
600
600
600
600
600
4"
4"
4"
4"
4"
dB(A)
81
87
89
90
92
400V / III / 50 Hz
A
266,9
402,9
431,7
460,1
488,3
A
123,8
152,2
181,0
209,4
237,6
mm
2150
2150
2150
2150
2150
mm
820
820
820
820
820
mm
1645
1870
1870
1870
1870
m²
1,8
1,8
1,8
1,8
1,8
kg
756
974
1158
1328
1534
kg
736
914
1088
1248
1444
MWC
• 6 •
Application Guide
•
MWC-0410-E
Cooling mode
Cooling capacity
(1)
Power input
(1)
Full load amps
(1)
Evaporator water
fl
ow
(1)
Evaporator pressure drop
(1)
Condenser water
fl
ow
(1)
Condenser pressure drop
(1)
Heating mode
Heating capacity
(3)
Power input
(3)
Full load amps
(3)
COP
Condenser water
fl
ow
(3)
Condenser pressure drop
(3)
Evaporator water
fl
ow
(3)
Evaporator pressure drop
(3)
Compressor
Scroll - Hermetic
Number of compressor
nr
Capacity steps
Oil charge per compressor
Oil type
type
MOBIL EAL Arctic 22CC or ICI EMKARATE RL32CF
Refrigerant
Expansion
type
Thermostatic expansion valve
Number of circuit
nr
Charge per circuit
Condenser (Heating mode)
AISI 316 stainless steel plate brazed with copper heat exchanger
Water volume
Water operating pressure
Hydraulic connections
Victaulic
Water inlet/outlet
Inches
Evaporator (Cooling mode)
AISI 316 stainless steel plate brazed with copper heat exchanger
Water volume
Water operating pressure
Hydraulic connections
Victaulic
Water inlet/outlet
Inches
Acoustic
Global sound power level
(1)
Electrical data
Start-up intensity
Maximum current
Dimensions
Length
Width
Height
Footprint
Operating weight
Shipping weight
GENERAL DATA
All data are at Eurovent conditions :
(1)
Gross cooling capacity with 12/7°C evaporator water temperature and
30/35°C condenser water temperature.
(*) Except for MWC 720 :13/7°C evaporator water temperature.
(2)
ESEER according to EN14511 Eurovent calculation method.
(3)
Gross heating capacity with 40/45°C condenser water temperature and 10°C
evaporator water inlet, with the same evaporator water
fl
ow as in cooling
mode.
OPERATING LIMITS
on page 13
COOLING ONLY
Summary of Contents for MRC 180