background image

Page 12

Manual bleeding of the fuel pump is required on initial start
up. Failure to bleed air from the oil pump could result in an
air lock/oil starvation condition.

NOTE − As an extra precaution, cycle heating on and off ten
times after bleeding air from the oil pump. This will elimi-
nate air in the gun assembly.

Figure 14

Oil Piping

ÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎ

air vent

fill

pipe

Oil

Tank

fuel

pump

Aux

Filter

Shut−off

Valve

8 ft (2.4 m) 

Maximum

One Pipe Lift

One-Pipe System

To determine the  correct tubing size for piping, refer to table 3 .

Table 3

One−Pipe Oil Sizing

Line Length

Pipe Diameter (OD Tubing)

0−50’ (15 m)

3/8" (10 mm)

51−100’ (15 m)

1/2" (12 mm)

Two−Pipe System

When using a two−pipe system with the oil tank below the
level of the burner, use a single−stage fuel pump in lift con-
ditions of up to 10 feet (3 m) and/or a vacuum of 10" (254
mm) Hg or less. See figure 15. Use a two−stage fuel pump
when lift exceeds 10 feet (3 m) and/or a vacuum of 10" (254
mm) Hg to 15" (381 mm) Hg. Both conditions require that
you use of a two−pipe system, which consists of a return
line that purges the fuel pump of air by returning it to the
tank. To determine the run and lift for piping, refer to table 4 .

Use continuous lengths of heavy wall copper tubing or
steel pipe for oil supply pipe. Install oil supply pipe under
floor or near walls to protect it from damage. Avoid running
pipes along joists or reverberating surfaces. Always use
flare fittings. All fittings must be accessible. Do not use
compression fittings.

IMPORTANT

Both oil supply and return pipes must be submerged
in oil in the supply tank.

Figure 15

Oil Piping

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

fuel

pump

Aux

Filter

Return

pipe

Fill

Pipe

Air Vent

Oil

Tank

Inlet

Return

pipe

H

3"−4"

(76 mm −102 mm)

R

outside tank fuel pump above bottom of tank.

Two-Pipe System

Table 4

Two−Pipe Maximum Pipe Length (H + R)

3450 RPM − 3 GPH (11.4 LPH)

Lift H"

3/8" (10 mm) OD

Tubing

1/2" (12 mm) OD

Tubing

Single

Stage

Two

Stage

Single

Stage

Two

Stage

0’

(0.0 m)

84’

(25.6 m)

93’

(28.3 m)

100’

(30.5 m)

100’

(30.5 m)

2’

(0.6 m)

73’

(22.3 m)

85’

(25.9 m)

100’

(30.5 m)

100’

(30.5 m)

4’

(1.2 m)

63’

(19.2 m)

77’

(23.5 m)

100’

(30.5 m)

100’

(30.5 m)

6 ’

(1.8m)

52’

(15.8 m)

69’

(21.0 m)

100’

(30.5 m)

100’

(30.5 m)

8’

(2.4 m)

42’

(12.8 m)

60’

(18.3 m)

100’

(30.5 m)

100’

(30.5 m)

10’

(3.0 m)

31’

(9.4 m)

52’

(15.9 m)

100’

(30.5 m)

100’

(30.5 m)

12’

(3.7 m)

21’

(6.4 m)

44’

(13.4 m)

83’

(25.3 m)

100’

(30.5 m)

14’

(4.3 m)

−−−

36’

(11.0 m)

41’

(12.5 m)

100’

(30.5 m)

16’

(4.9 m)

−−−

27’

(8.2 m)

−−−

100’

(30.5 m)

18’

(5.5 m)

−−−

−−−

−−−

76’

(23.2 m)

Oil Supply Line & Filter Connections

One−Pipe Systems

CAUTION

Do not install the bypass plug into the pump on one−
pipe systems.

The burner is shipped with fuel pump set for one−pipe op-
eration. For one−pipe systems, the oil supply pipe is con-
nected to the inlet tap on the pump. A one−pipe system
should only be used where there is gravity oil flow to the
pump and the pipe is not run at any point above the oil level
in the tank.

Summary of Contents for O23

Page 1: ...the Unit 5 Unit Adjustments 5 Venting 6 Flue Connections 10 Supply Return Air Plenums 11 Oil Supply Line Filter Connections 12 Leak Check 13 Electrical Wiring 13 Unit Start Up Adjustments 15 Service 1...

Page 2: ...120 mm 495 778 457 498 406 O23Q5 140 154 in 22 1 2 33 1 8 21 22 1 8 18 O23Q5 140 154 mm 572 841 533 562 457 O23 Start Up Performance Check List Filter Clean Secure Supply Voltage Electrical Connectio...

Page 3: ...igure 2 FB HEAD HEAD INSULATOR CLIP RETAINING 1 4 HEX HEAD SCREW FB HEADS ASSY FOR AIR TUBE ASSY ELECTRODE HEAD NOZZLE LINE PEDESTAL ADAPTER NOZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET MOTOR 4X4...

Page 4: ...nings are required Dimensions of combustion air openings are shown in table 1 One opening shall be below burner level and the other opening shall be no more than 6 152 mm from the room s ceiling IMPOR...

Page 5: ...llowing D Draft gauge D CO2 or O2 analyzer D Smoke tester D Pressure gauge D High temperature thermometer D Beckett T 500 gauge D Oil vacuum gauge D Knowledge of proper test equipment operation CAUTIO...

Page 6: ...ss steel rather than aluminum Prior to installation of unit make a thorough inspection of the chimney to determine whether repairs are necessary Make sure the chimney is properly constructed and sized...

Page 7: ...needs to exit from side of cabinet use the pilot hole located on either side of the unit to cut a 6 152 mm round hole Attach finishing plate provided with four sheet metal screws to cover rough edges...

Page 8: ...alled so that supply ducts carry air circulated by the furnace to areas outside the space con taining the furnace the return air must be handled by ducts which are sealed to the furnace casing and whi...

Page 9: ...square inch 6 4 square centimeters per 4 000 Btu 1172 W per hour of the total input rating of all other equip ment in the enclosure OIL FURNACE When ducts are used they shall be of the same cross sec...

Page 10: ...operation Adjust ther mostat so appliance will operate continuously 5 Test for spillage using a draft gauge 6 After it has been determined that each appliance re maining connected to the common ventin...

Page 11: ...raft control at least 12 inches beyond the furnace If there is no space to install the draft control in the flue pipe it may be installed in the vent above the flue pipe Follow the instructions packed...

Page 12: ...ar walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings All fittings must be accessible Do not use compression fittings IMPORTANT Both o...

Page 13: ...mm Oil Filters Cat Number 10 micron filter no mounting bracket 81P89 10 micron filter mounting bracket 53P92 10 micron replacement cartridge for filter 45 gph 53P93 Filter restriction indicator gauge...

Page 14: ...Page 14 Figure 16 Fan Control Board thermostat terminal strip fan off delay switches Figure 17 Typical O23 Wiring Diagram...

Page 15: ...Page 15 Figure 18 Typical O23 Wiring Diagram...

Page 16: ...o its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the readings The difference in tempera tures in the supply and return air plenu...

Page 17: ...rol 7 Stack Temperature Take a stack temperature reading in the vent pipe Subtract the room air temperature from the stack temperature This will give you the net stack temperature Use the efficiency c...

Page 18: ...ergized Circulating fan is energized at the cool speed Cooling compressor turns on immediately Thermostat ends call for cool G and Y terminals are de energized Circulating fan and cooling compressor t...

Page 19: ...ry control If the burner starts fault is in the Flame detector exposed to light Seal off false source of light the burner starts fault is in the detector circuit short circuit in the flame detec tor R...

Page 20: ...ugged Nozzle strainer plugged Replace nozzle with the same size spray angle and spray type Inspect the nozzle for plugged orifice or carbon build up around orifice Poor or off center spray type Fouled...

Page 21: ...lace nozzle Too much air lean short fire Reduce combustion air check combustion Too little air long dirty fire Increase combustion air check combustion Poor Fire If burner con tinues to run does not l...

Page 22: ...operly rotating wheel Restrictions in return or supply air system Correct cause of restriction Adjustable limit control set too low Reset limit to maximum stop setting Power If voltage fluctuates faul...

Page 23: ...ack tem reading more than a trace Incorrect burner head adjust ment Correct burner setting CO2 stack tem perature and smoke Too little combustion air Increase combustion air smoke Too little blower ai...

Reviews: