background image

Page 13

 1 − Connect the inlet pipe to the pump inlet. Start the burner.

 2 − Arrange the primary burner control for continuous op-

eration during purging. See figure 14.

 3 − Turn the bleed valve one turn counterclockwise to

open.

 4 − Bleed the unit until all air bubbles disappear.

NOTE − Hurried bleeding will prevent the unit from op-
erating properly.

 5 − Tighten the bleed valve securely.

Two−Pipe Systems

If the installation requires a two−pipe operation, install the
bypass plug included in the bag which is attached to the
pump. To convert the pump, install the bypass plug accord-
ing to the provided pump instructions. Notice in the two-
pipe system the return pipe must terminate in the tank 3"
(76 mm) to 4" (102 mm) above the supply inlet. Ensure the
return pipe terminates at the correct measurement or air
may escape into the system. This could result in loss of
prime.

NOTE− If using an outside tank in cold climates a number
one fuel or an oil treatment is strongly recommended.

 1 − Remove 1/4" plug from return port.

 2 − Insert bypass plug and tighten it. See figure NO TAG.

 3 − Attach the return and inlet pipes. Start the burner. Air

bleeding is automatic.

NOTE − If a faster bleed is necessary, open the bleed
valve.

 4 − The return pipe must terminate 3" to 4" above the sup-

ply pipe inlet. See figure NO TAG.

NOTE − If the return pipe does not terminate where it
should, air may enter the system, and prime may be
lost.

An oil filter is required for all models.

 Install filter inside

the building between the tank shut-off valve and the burner.
Locate filter close to burner for easy maintenance. Table 5
lists the filters for the O23 furnace.

Table 5

Installation Clearances inches (mm)

Oil Filters

Cat. 

Number

10 micron filter (no mounting bracket)

81P89

10 micron filter (mounting bracket)

53P92

10 micron replacement cartridge for filter, 45 gph

53P93

Filter restriction indicator gauge

53P90

Consult burner manufacturer’s instructions packaged with
unit for further details concerning oil supply pipe connec-
tions.

Leak Check

After oil piping is completed, carefully check all piping con-
nections (factory and field) for oil leaks.

Oil Pipe Heater (Optional)

A heater for the oil pipe is available for applications that are
located in cold climates. The heater warms the oil pipe to
assist the initial start−up.

Electrical Wiring

All wiring must conform to the National Electric Code
(NEC), or Canadian Electric Code (CEC) and any local
codes. Refer to figure 16 for the terminal designations on
the fan control board.

 1− Refer to the appliance rating plate for proper fuse size.

 2− Install the room thermostat and make wire connections

to the fan control board. Avoid installing thermostat on
an outside wall or where it can be affected by radiant
heat. Set the adjustable heat anticipator on thermostat
according to the wiring diagram sticker provided on
unit.

 3− Install a separate fused disconnect switch near unit so

power can be shut off for servicing.

 4− Complete line voltage wiring from disconnect switch

near unit to make-up box.

NOTE − An equipment ground screw is provided. Refer
to unit wiring diagram and figure 16 for O23 series
units. Ground unit using a suitable ground wire.

 5− Any accessory rated up to 1 amp can be connected to

the accessory terminal. The accessory terminal is en-
ergized when the blower is operating.

IMPORTANT

When an accessory is being used in a continuous fan
application which does not include the S68 ON/OFF
switch, the accessory must be wired between L1 and
N on the fan control board to ensure proper voltage.

Summary of Contents for O23

Page 1: ...the Unit 5 Unit Adjustments 5 Venting 6 Flue Connections 10 Supply Return Air Plenums 11 Oil Supply Line Filter Connections 12 Leak Check 13 Electrical Wiring 13 Unit Start Up Adjustments 15 Service 1...

Page 2: ...120 mm 495 778 457 498 406 O23Q5 140 154 in 22 1 2 33 1 8 21 22 1 8 18 O23Q5 140 154 mm 572 841 533 562 457 O23 Start Up Performance Check List Filter Clean Secure Supply Voltage Electrical Connectio...

Page 3: ...igure 2 FB HEAD HEAD INSULATOR CLIP RETAINING 1 4 HEX HEAD SCREW FB HEADS ASSY FOR AIR TUBE ASSY ELECTRODE HEAD NOZZLE LINE PEDESTAL ADAPTER NOZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET MOTOR 4X4...

Page 4: ...nings are required Dimensions of combustion air openings are shown in table 1 One opening shall be below burner level and the other opening shall be no more than 6 152 mm from the room s ceiling IMPOR...

Page 5: ...llowing D Draft gauge D CO2 or O2 analyzer D Smoke tester D Pressure gauge D High temperature thermometer D Beckett T 500 gauge D Oil vacuum gauge D Knowledge of proper test equipment operation CAUTIO...

Page 6: ...ss steel rather than aluminum Prior to installation of unit make a thorough inspection of the chimney to determine whether repairs are necessary Make sure the chimney is properly constructed and sized...

Page 7: ...needs to exit from side of cabinet use the pilot hole located on either side of the unit to cut a 6 152 mm round hole Attach finishing plate provided with four sheet metal screws to cover rough edges...

Page 8: ...alled so that supply ducts carry air circulated by the furnace to areas outside the space con taining the furnace the return air must be handled by ducts which are sealed to the furnace casing and whi...

Page 9: ...square inch 6 4 square centimeters per 4 000 Btu 1172 W per hour of the total input rating of all other equip ment in the enclosure OIL FURNACE When ducts are used they shall be of the same cross sec...

Page 10: ...operation Adjust ther mostat so appliance will operate continuously 5 Test for spillage using a draft gauge 6 After it has been determined that each appliance re maining connected to the common ventin...

Page 11: ...raft control at least 12 inches beyond the furnace If there is no space to install the draft control in the flue pipe it may be installed in the vent above the flue pipe Follow the instructions packed...

Page 12: ...ar walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings All fittings must be accessible Do not use compression fittings IMPORTANT Both o...

Page 13: ...mm Oil Filters Cat Number 10 micron filter no mounting bracket 81P89 10 micron filter mounting bracket 53P92 10 micron replacement cartridge for filter 45 gph 53P93 Filter restriction indicator gauge...

Page 14: ...Page 14 Figure 16 Fan Control Board thermostat terminal strip fan off delay switches Figure 17 Typical O23 Wiring Diagram...

Page 15: ...Page 15 Figure 18 Typical O23 Wiring Diagram...

Page 16: ...o its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the readings The difference in tempera tures in the supply and return air plenu...

Page 17: ...rol 7 Stack Temperature Take a stack temperature reading in the vent pipe Subtract the room air temperature from the stack temperature This will give you the net stack temperature Use the efficiency c...

Page 18: ...ergized Circulating fan is energized at the cool speed Cooling compressor turns on immediately Thermostat ends call for cool G and Y terminals are de energized Circulating fan and cooling compressor t...

Page 19: ...ry control If the burner starts fault is in the Flame detector exposed to light Seal off false source of light the burner starts fault is in the detector circuit short circuit in the flame detec tor R...

Page 20: ...ugged Nozzle strainer plugged Replace nozzle with the same size spray angle and spray type Inspect the nozzle for plugged orifice or carbon build up around orifice Poor or off center spray type Fouled...

Page 21: ...lace nozzle Too much air lean short fire Reduce combustion air check combustion Too little air long dirty fire Increase combustion air check combustion Poor Fire If burner con tinues to run does not l...

Page 22: ...operly rotating wheel Restrictions in return or supply air system Correct cause of restriction Adjustable limit control set too low Reset limit to maximum stop setting Power If voltage fluctuates faul...

Page 23: ...ack tem reading more than a trace Incorrect burner head adjust ment Correct burner setting CO2 stack tem perature and smoke Too little combustion air Increase combustion air smoke Too little blower ai...

Reviews: