background image

Page 20

Troubleshooting:  Burner starts, but no flame is established.

Source

Procedure

Causes

Correction

Check tank gauge or use dip
stick.

No oil in tank

Fill tank.

Oil Supply

Coat dip stick with litmus paste
and insert into bottom of tank.

Water in oil tank

If water depth exceeds 1 inch,
pump or drain water.

Listen for pump whine.

Tank shut−off valve closed

Open valve.

Oil line filter is plugged

Replace filter cartridges.

Listen for pump whine.

Kinks or restriction in oil line

Repair or replace oil line.

Oil Filters & Oil Line

Plugged fuel pump strainer

Clean strainer or replace pump.

Open bleed valve or gauge port.
Start the burner No oil or milky

Air leak in oil supply line

Locate and correct leak.

Start the burner. No oil or milky
oil indicates loss or prime.

Air leak in oil supply line

Tighten all connections.

Oil P

Install pressure gauge on pump

d

d

Sh

ld

t

Pump is partially or completely
frozen. No pressure and the
motor locks out on overload.

Replace pump.

Oil Pump

p

g

g

p

p

and read pressure. Should not
be less than 140 psi.

Coupling disengaged or broken
− no pressure

Re−engage or replace coupling.

Fuel pressure too low

Adjust to 100 psi.

Disconnect ignition leads. Ob-
serve the oil spray (gun assem-

Nozzle orifice plugged

Replace nozzle with the same

Nozzle

serve the oil spray (gun assem
bly must be removed from unit).
Inspect the nozzle for plugged

Nozzle strainer plugged

Replace nozzle with the same
size, spray angle, and spray
type

Inspect the nozzle for plugged
orifice or carbon build−up around
orifice.

Poor or off center spray

type.

Fouled or shorted electrodes

Clean electrode leads

Dirty electrodes and leads

Clean electrode leads.

Eroded electrode tips

Cl

l

t d ti

d

t

Improper electrode gap spacing

Clean electrode tips and reset
the gap to 5/32 inches and cor-

Ignition Electrodes

Remove gun assembly and in-
spect electrodes and leads.

Improper position of electrode
tips

the gap to 5/32 inches and cor
rectly position tips.

Bad buss bar connection

Retension and realign.

Cracked or chipped insulators

Replace electrode.

Cracked or burned lead insula-
tors

Replace electrode leads.

I

iti

Connect ignition leads to the
t

f

St t b

d b

Low line voltage

Check voltage at power source.
Correct cause of voltage drop
or call the power company.

Ignition

Transformer

g

transformer. Start burner and ob-
serve spark. Check line voltage
to transformer primary.

Burned out transformer wind-
ings.

Replace the transformer.

to transformer primary.

No spark or weak spark

Properly ground the transformer
case.

B

M t

Motor does not come up to
speed and trips out on overload.
T

ff

d

t t bl

Low line voltage

Check voltage at power source.
Correct cause of voltage drop
or the call power company.

 Burner Motor

p

p

Turn off power and rotate blower
wheel by hand to check for bind-
ing or excessive drag.

Pump or blower overloading
motor

Correct cause of overloading.

ing or excessive drag.

Faulty motor

Replace motor.

Summary of Contents for O23

Page 1: ...the Unit 5 Unit Adjustments 5 Venting 6 Flue Connections 10 Supply Return Air Plenums 11 Oil Supply Line Filter Connections 12 Leak Check 13 Electrical Wiring 13 Unit Start Up Adjustments 15 Service 1...

Page 2: ...120 mm 495 778 457 498 406 O23Q5 140 154 in 22 1 2 33 1 8 21 22 1 8 18 O23Q5 140 154 mm 572 841 533 562 457 O23 Start Up Performance Check List Filter Clean Secure Supply Voltage Electrical Connectio...

Page 3: ...igure 2 FB HEAD HEAD INSULATOR CLIP RETAINING 1 4 HEX HEAD SCREW FB HEADS ASSY FOR AIR TUBE ASSY ELECTRODE HEAD NOZZLE LINE PEDESTAL ADAPTER NOZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET MOTOR 4X4...

Page 4: ...nings are required Dimensions of combustion air openings are shown in table 1 One opening shall be below burner level and the other opening shall be no more than 6 152 mm from the room s ceiling IMPOR...

Page 5: ...llowing D Draft gauge D CO2 or O2 analyzer D Smoke tester D Pressure gauge D High temperature thermometer D Beckett T 500 gauge D Oil vacuum gauge D Knowledge of proper test equipment operation CAUTIO...

Page 6: ...ss steel rather than aluminum Prior to installation of unit make a thorough inspection of the chimney to determine whether repairs are necessary Make sure the chimney is properly constructed and sized...

Page 7: ...needs to exit from side of cabinet use the pilot hole located on either side of the unit to cut a 6 152 mm round hole Attach finishing plate provided with four sheet metal screws to cover rough edges...

Page 8: ...alled so that supply ducts carry air circulated by the furnace to areas outside the space con taining the furnace the return air must be handled by ducts which are sealed to the furnace casing and whi...

Page 9: ...square inch 6 4 square centimeters per 4 000 Btu 1172 W per hour of the total input rating of all other equip ment in the enclosure OIL FURNACE When ducts are used they shall be of the same cross sec...

Page 10: ...operation Adjust ther mostat so appliance will operate continuously 5 Test for spillage using a draft gauge 6 After it has been determined that each appliance re maining connected to the common ventin...

Page 11: ...raft control at least 12 inches beyond the furnace If there is no space to install the draft control in the flue pipe it may be installed in the vent above the flue pipe Follow the instructions packed...

Page 12: ...ar walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings All fittings must be accessible Do not use compression fittings IMPORTANT Both o...

Page 13: ...mm Oil Filters Cat Number 10 micron filter no mounting bracket 81P89 10 micron filter mounting bracket 53P92 10 micron replacement cartridge for filter 45 gph 53P93 Filter restriction indicator gauge...

Page 14: ...Page 14 Figure 16 Fan Control Board thermostat terminal strip fan off delay switches Figure 17 Typical O23 Wiring Diagram...

Page 15: ...Page 15 Figure 18 Typical O23 Wiring Diagram...

Page 16: ...o its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the readings The difference in tempera tures in the supply and return air plenu...

Page 17: ...rol 7 Stack Temperature Take a stack temperature reading in the vent pipe Subtract the room air temperature from the stack temperature This will give you the net stack temperature Use the efficiency c...

Page 18: ...ergized Circulating fan is energized at the cool speed Cooling compressor turns on immediately Thermostat ends call for cool G and Y terminals are de energized Circulating fan and cooling compressor t...

Page 19: ...ry control If the burner starts fault is in the Flame detector exposed to light Seal off false source of light the burner starts fault is in the detector circuit short circuit in the flame detec tor R...

Page 20: ...ugged Nozzle strainer plugged Replace nozzle with the same size spray angle and spray type Inspect the nozzle for plugged orifice or carbon build up around orifice Poor or off center spray type Fouled...

Page 21: ...lace nozzle Too much air lean short fire Reduce combustion air check combustion Too little air long dirty fire Increase combustion air check combustion Poor Fire If burner con tinues to run does not l...

Page 22: ...operly rotating wheel Restrictions in return or supply air system Correct cause of restriction Adjustable limit control set too low Reset limit to maximum stop setting Power If voltage fluctuates faul...

Page 23: ...ack tem reading more than a trace Incorrect burner head adjust ment Correct burner setting CO2 stack tem perature and smoke Too little combustion air Increase combustion air smoke Too little blower ai...

Reviews: