background image

Page 23

Troubleshooting:  Burner runs continuously (too little heat).

Source

Procedure

Causes

Correction

Too much combustion air

Reduce combustion air.

Low CO

2

less

Air leaks into heat exchanger
around inspection door, etc.

Correct cause of air leak.

Low CO

less

than 10%.

Excessive draft

Adjust barometric draft con-
trol for correct draft.

Incorrect burner head adjust-
ment

Correct burner head setting.

Dirty or plugged heat exchanger

Clean heat exchanger.

Hi h

k

Dirty or plugged heat exchanger

Readjust burner.

Check burner

High smoke
reading more

Insufficient draft

Increase draft.

Combustion

Check burner
combustion for
CO2, stack tem-

reading more
than a trace.

Incorrect burner head adjust-
ment

Correct burner setting.

CO2, stack tem
perature, and
smoke

Too little combustion air

Increase combustion air.

smoke

Too little blower air

Increase blower speed to
maintain proper temp. rise.

High stack tem-

Blower belt too loose (if
equipped)

Tighten blower belt.

High stack tem-
perature is
more than

Dirty or plugged heat exchanger Clean heat exchanger.

more than
550

_

F Net.

Dirty blower wheel

Clean blower wheel.

550 F Net.

Dirty furnace air filters

Clean or replace filter.

Restricted or closed registers or
dampers

Readjust registers or damp-
ers.

Oil Pressure

Inspect fire and check

Partially plugged or defective
nozzle

Replace nozzle.

Oil Pressure

Inspect fire and check

oil pressure.

Oil pressure is too low: less
than 100 psi.

Increase oil pressure top
100psi.

Summary of Contents for O23

Page 1: ...the Unit 5 Unit Adjustments 5 Venting 6 Flue Connections 10 Supply Return Air Plenums 11 Oil Supply Line Filter Connections 12 Leak Check 13 Electrical Wiring 13 Unit Start Up Adjustments 15 Service 1...

Page 2: ...120 mm 495 778 457 498 406 O23Q5 140 154 in 22 1 2 33 1 8 21 22 1 8 18 O23Q5 140 154 mm 572 841 533 562 457 O23 Start Up Performance Check List Filter Clean Secure Supply Voltage Electrical Connectio...

Page 3: ...igure 2 FB HEAD HEAD INSULATOR CLIP RETAINING 1 4 HEX HEAD SCREW FB HEADS ASSY FOR AIR TUBE ASSY ELECTRODE HEAD NOZZLE LINE PEDESTAL ADAPTER NOZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET MOTOR 4X4...

Page 4: ...nings are required Dimensions of combustion air openings are shown in table 1 One opening shall be below burner level and the other opening shall be no more than 6 152 mm from the room s ceiling IMPOR...

Page 5: ...llowing D Draft gauge D CO2 or O2 analyzer D Smoke tester D Pressure gauge D High temperature thermometer D Beckett T 500 gauge D Oil vacuum gauge D Knowledge of proper test equipment operation CAUTIO...

Page 6: ...ss steel rather than aluminum Prior to installation of unit make a thorough inspection of the chimney to determine whether repairs are necessary Make sure the chimney is properly constructed and sized...

Page 7: ...needs to exit from side of cabinet use the pilot hole located on either side of the unit to cut a 6 152 mm round hole Attach finishing plate provided with four sheet metal screws to cover rough edges...

Page 8: ...alled so that supply ducts carry air circulated by the furnace to areas outside the space con taining the furnace the return air must be handled by ducts which are sealed to the furnace casing and whi...

Page 9: ...square inch 6 4 square centimeters per 4 000 Btu 1172 W per hour of the total input rating of all other equip ment in the enclosure OIL FURNACE When ducts are used they shall be of the same cross sec...

Page 10: ...operation Adjust ther mostat so appliance will operate continuously 5 Test for spillage using a draft gauge 6 After it has been determined that each appliance re maining connected to the common ventin...

Page 11: ...raft control at least 12 inches beyond the furnace If there is no space to install the draft control in the flue pipe it may be installed in the vent above the flue pipe Follow the instructions packed...

Page 12: ...ar walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings All fittings must be accessible Do not use compression fittings IMPORTANT Both o...

Page 13: ...mm Oil Filters Cat Number 10 micron filter no mounting bracket 81P89 10 micron filter mounting bracket 53P92 10 micron replacement cartridge for filter 45 gph 53P93 Filter restriction indicator gauge...

Page 14: ...Page 14 Figure 16 Fan Control Board thermostat terminal strip fan off delay switches Figure 17 Typical O23 Wiring Diagram...

Page 15: ...Page 15 Figure 18 Typical O23 Wiring Diagram...

Page 16: ...o its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the readings The difference in tempera tures in the supply and return air plenu...

Page 17: ...rol 7 Stack Temperature Take a stack temperature reading in the vent pipe Subtract the room air temperature from the stack temperature This will give you the net stack temperature Use the efficiency c...

Page 18: ...ergized Circulating fan is energized at the cool speed Cooling compressor turns on immediately Thermostat ends call for cool G and Y terminals are de energized Circulating fan and cooling compressor t...

Page 19: ...ry control If the burner starts fault is in the Flame detector exposed to light Seal off false source of light the burner starts fault is in the detector circuit short circuit in the flame detec tor R...

Page 20: ...ugged Nozzle strainer plugged Replace nozzle with the same size spray angle and spray type Inspect the nozzle for plugged orifice or carbon build up around orifice Poor or off center spray type Fouled...

Page 21: ...lace nozzle Too much air lean short fire Reduce combustion air check combustion Too little air long dirty fire Increase combustion air check combustion Poor Fire If burner con tinues to run does not l...

Page 22: ...operly rotating wheel Restrictions in return or supply air system Correct cause of restriction Adjustable limit control set too low Reset limit to maximum stop setting Power If voltage fluctuates faul...

Page 23: ...ack tem reading more than a trace Incorrect burner head adjust ment Correct burner setting CO2 stack tem perature and smoke Too little combustion air Increase combustion air smoke Too little blower ai...

Reviews: