background image

Page 18

those things which might affect combustion. Those
things which might affect combustion can then do so
without causing the unit to start sooting/smoking.
Things which might affect combustion include a nozzle
going bad, draft that changes during different climatic
conditions, dirty oil, dirt obstructing the air inlet, etc.
To build in a window of operation," set up the burner to
be 2% less in CO

2

. For example, if you find a reading of

12% CO

2

, adjust the air inlet shutter to increase the air

and drop the CO

2

 to 10%.

5.

Retest the Smoke

With a drop in the CO

2

 and in-

crease in the air you should see that the smoke has re-
turned to 0.

6.

Retest the Overfire Draft

This test serves to con-

firm that you have not increased the air too much.
Again you do not want a positive pressure at the test
port. It should still be 0.02 less than the draft pressure
reading taken at the breach. You may need to increase
the stack draft by adjusting the barometric draft con-
trol.

7.

Stack Temperature

Take a stack temperature

reading in the vent pipe. Subtract the room air temper-
ature from the stack temperature. This will give you the
net stack temperature. Use the efficiency charts pro-
vided in most CO

2

 analyzers to determine furnace effi-

ciency.

Service

CAUTION

Do not tamper with unit controls. Call your qualified
service technician.

Servicing the Air Filter

NOTE − Under no circumstances should the access panels
to the blower compartment be left off or left partially open.

Throw-Away Type Filters

Check filters monthly and re-

place when necessary to assure proper furnace operation.
Replace filters with like kind and size filters.

Reusable Type Filters

Filters should be checked

monthly and cleaned when necessary to assure proper fur-
nace operation.

Servicing the Blower

Blower motor is prelubricated and sealed for extended op-
eration. No further lubrication is required. Disconnect pow-
er to unit before cleaning blower wheel for debris.

Inspecting the Flue Pipe

The flue pipe should be inspected annually by a qualified
service technician. Remove and clean any soot or ash
found in the flue pipe. Inspect pipe for holes or rusted
areas. If replacement is necessary, replace with the same
size and type as required by code. Inspect the flue draft
control device and replace if found defective.

Cleaning the Heat Exchanger

1. Remove the vent pipe from the furnace.
2. Remove the locking screws and the caps from the

clean out tubes. Remove flue access elbow.

3. Using a long spiral wire brush, sweep down the outer

drum of the heat exchanger. Then using the hose at-
tachment, vacuum out loose debris.

4. Remove the locking screw and cap from the observa-

tion tube and with the spiral wire brush, reach upward
toward the rear of the heat exchanger to clean out the
crossover tube.

CAUTION

Do not attempt to clean the combustion chamber. It
can be easily damaged.

5. Replace the three clean out caps and flue access el-

bow. Make sure locking screws are secure.

6. Brush out and vacuum the vent outlet area of the outer

drum and replace vent pipe.

7. Clean around the burner, blower deck and vestibule

area.

NOTE − A heat exchanger clean-out kit ABRSH380
(35K09) is available from Lennox.

Servicing the Oil Burner

The nozzle and oil filter must be checked before each heat-
ing season. Also, recheck the conditions shown in the Oil
Furnace Start−up Checklist (see page 24).

NOTE − Close the oil line shutoff valve if the burner is shut
down for an extended period of time.

Heating Events − Actions & Responses

1.

Action: Thermostat calls for heat

 (W terminal is en-

ergized)
Response:

D

Blower control board closes oil primary control
T−3T connections.

D

After a 15−second pre−purge period, power is sent
to the burner and ignition is established. When the
burner pump reaches full speed, the solenoid
valve is energized.

D

Ignition system and oil primary control start the
furnace. Oil flows as long as oil primary control
senses flame.

D

Burner motor energized and heat fan on ramp tim-
ing begins. When timing is complete, the circulat-
ing fan is at heat speed and warm air is delivered to
the controlled space.

2.

Action: Thermostat ends call for heat

 (W terminal

is de−energized)
Response:

D

Oil primary control is de−energized, terminating
the burner cycle.

D

Heat fan off ramp timing begins. When timing is
complete, circulating fan is de−energized.

D

Blower control board returns to standby mode (oil
primary control and circulating fan are off).

D

After the thermostat is satisfied, the thermostat
circuit opens. The solenoid valve is de−energized
before the pump rotation stops. Power to the burn-
er is interrupted, shutting down the burner.

3.

Action: Burner fails to light

Response:

D

Oil primary control locks out within lockout timing
(timing depends on oil primary control).

Downloaded from 

ManualsNet.com

 search engine

Summary of Contents for O23V Series

Page 1: ...sedes 10 2005 Table of Contents General 1 Shipping Packing List 1 O23V Unit Dimensions 2 O23V Unit Parts Arrangement 3 O23V Oil Burner Parts Arrangement 3 Requirements 4 Locate Level the Unit 4 Unit A...

Page 2: ...OW TOP VIEW RETURN AIR SIDE VIEW E RETURN AIR FRONT VIEW Figure 1 O23V Unit Dimensions Inches mm O23V Model A B C D E Q2 3 70 90 Q3 4 105 120 19 1 2 495 30 5 8 778 18 457 19 5 8 498 16 406 Q5 140 154...

Page 3: ...0 8 Figure 3 AIR TUBE SCREWS ELECTRONIC IGNITION TRANSFORMER FLANGE GASKET RETAIN ING CLIP IGNITOR PRIMARY CONTROL REAR ACCESS DOOR GASKET MAIN HOUSING ASSY AIR ADJUST DIAL 4X4 BOX BLOWER WHEEL INLET...

Page 4: ...i mum free area one half square inch per 1 000 Btu per hour input This combustion air should be brought into the area containing the furnace below the level of the furnace burner Table 2 O23V Installa...

Page 5: ...rner assembly from the vestibule By loosen ing the nuts and by turning the whole burner assembly counterclockwise figure 4 the entire burner assembly will come out of the furnace There is adequate wir...

Page 6: ...n outside or through any unconditioned space 6 Chimney should extend 3 feet 0 9 m above highest point where the vent passes through the roof and 2 feet 0 6 m higher than any portion of a building with...

Page 7: ...OR DEATH A living space which provides insufficient combustion air to the furnace can result in headaches nausea dizziness or asphyxiation CAUTION Insufficient combustion air to the furnace can cause...

Page 8: ...space shall be provided with two perma nent openings One opening shall be within 12 305 mm of the top of the enclosure and one within 12 305 mm of the bottom These openings must communicate directly o...

Page 9: ...from Common Venting System In the event that an existing furnace is removed from a venting system commonly run with separate appliances the venting system is likely to be too large to properly vent t...

Page 10: ...of the cabinet See unit dimensions on page 2 Using it as the center point cut a 6 inch 152 mm round hole in the cabinet s side Install the barometric draft control within 18 inches of the furnace flue...

Page 11: ...bing or steel pipe for oil supply pipe Install oil supply pipe under floor or near walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings...

Page 12: ...de the building between the tank shut off valve and the burn er Locate filter close to burner for easy maintenance Table 5 lists the filters for the O23V furnace Table 5 Installation Clearances inches...

Page 13: ...ted The Test jumper is used to operate the motor in the test mode See figure 17 Factory settings for the blower speed jumpers are given in the wiring diagram in figure 18 Figure 17 shows the blower co...

Page 14: ...age cooling closes the R to Y1 circuit on the A54 blower control board The blower motor runs at 57 CFM for the first 7 1 2 minutes of the 1st stage cooling demand After 7 1 2 minutes the blower motor...

Page 15: ...output to an electronic air cleaner The EAC terminal is energized when there is a call for heat cool or continuous blower See figure 18 Table 6 Blower Performance 0 through 0 80 in w g 0 through 200 P...

Page 16: ...Page 16 Figure 18 O23V Wiring Diagram P535277W Downloaded from ManualsNet com search engine...

Page 17: ...s above the range shown in the table check for high static pres sure Table 7 O23V Unit Nozzle Size Spray Angle Pattern Pump PSIG Input Rating BTU Hr Output Rating BTU Hr Head Temp Rise F 70 50GPH 80 A...

Page 18: ...ive Cleaning the Heat Exchanger 1 Remove the vent pipe from the furnace 2 Remove the locking screws and the caps from the clean out tubes Remove flue access elbow 3 Using a long spiral wire brush swee...

Page 19: ...rt Source Procedure Causes Correction Thermostat Check thermostat settings Thermostat in OFF or COOL Switch to HEAT Thermostat is set too low Turn thermostat to higher temperature Safety Overloads Che...

Page 20: ...flame is established Source Procedure Causes Correction Oil Supply Check tank gauge or use dip stick No oil in tank Fill tank Coat dip stick with litmus paste and insert into bottom of tank Water in o...

Page 21: ...ause of overloading Faulty motor Replace motor Troubleshooting Burner starts and fires but lock out on safety Source Procedure Causes Correction Poor Fire After burner fires immediately jumper across...

Page 22: ...ocedure Causes Correction Poor Fire After burner fires immediately jumper across flame detector terminals at the primary control SIf burner continues to run does not lock out of safety fault may be po...

Page 23: ...n air Air leaks into heat exchanger around inspection door etc Correct cause of air leak Excessive draft Adjust barometric draft control for correct draft Incorrect burner head adjustment Correct burn...

Page 24: ...nk Lift D Filter Type Inspect Change E Pressure Test F All fittings checked for tightness Thermostat A Type Heating Cooling B Anticipator Set C Wires New Old Air Filter A Filter Type Permanent Disposa...

Reviews: