background image

Page 21

Troubleshooting:   Burner starts, but no flame is established

Source

Correction

Causes

Procedure

Ignition
Electrodes

Remove gun assembly and inspect
electrodes and leads.

Fouled or shorted electrodes

Clean electrode leads.

Dirty electrodes and leads

Eroded electrode tips

Clean electrode tips and reset the
gap to 5/32 inches and correctly
position tips.

Improper electrode gap spacing

Improper position of electrode tips

Bad buss bar connection

Re−tension and realign.

Cracked or chipped insulators

Replace electrode.

Cracked or burned lead insulators

Replace electrode leads.

Ignition
Transformer

Connect ignition leads to the
transformer. Start burner and
observe spark. Check line voltage
to transformer primary.

Low line voltage

Check voltage at power source.
Correct cause of voltage drop or call
the power company.

Burned out transformer windings.

Replace the transformer.

No spark or weak spark

Properly ground the transformer
case.

Burner Motor

Motor does not come up to speed
and trips out on overload. Turn off
power and rotate blower wheel by
hand to check for binding or
excessive drag.

Low line voltage

Check voltage at power source.
Correct cause of voltage drop or the
call power company.

Pump or blower overloading motor

Correct cause of overloading.

Faulty motor

Replace motor.

 

Troubleshooting:   Burner starts and fires, but lock out on safety

Source

Procedure

Causes

Correction

Poor Fire

After burner fires,
immediately jumper across
flame detector terminals at
the primary control.

S

If burner continues to
run, this may be due to
poor fire. Inspect fire.

Unbalanced fire

Replace nozzle

Too much air − −lean short fire

Reduce combustion air − check
combustion.

Too little air − − long dirty fire

Increase combustion air − check
combustion.

Excessive draft

Adjust barometric damper for correct draft.

Too little draft or restriction

Correct draft or remove restriction.

Flame Detector

S

If fire is good, fault is in
the flame detector.
Check detector circuit.

Dirty cad cell face

Clean cad cell face.

Faulty cad cell − exceeds 15000 hms

Replace cad cell.

Loose or defective cad cell wires

Secure connections or replace cad cell
holder and wire leads.

Primary Control

S

If burner locks out on
safety, fault is in the pri-
mary control.

Primary control circuit defective

Replace primary control.

 

Troubleshooting:   Burner starts and fires, but short cycles (too little heat)

Source

Procedure

Causes

Correction

Thermostat

Check thermostat.

Heat anticipator set too low

Correct heat anticipator setting.

Vibration at thermostat

Correct source of vibration.

Thermostat in the path of a warm air
draft

Shield thermostat from draft or relocate.

table continued on next page

Downloaded from 

ManualsNet.com

 search engine

Summary of Contents for O23V Series

Page 1: ...sedes 10 2005 Table of Contents General 1 Shipping Packing List 1 O23V Unit Dimensions 2 O23V Unit Parts Arrangement 3 O23V Oil Burner Parts Arrangement 3 Requirements 4 Locate Level the Unit 4 Unit A...

Page 2: ...OW TOP VIEW RETURN AIR SIDE VIEW E RETURN AIR FRONT VIEW Figure 1 O23V Unit Dimensions Inches mm O23V Model A B C D E Q2 3 70 90 Q3 4 105 120 19 1 2 495 30 5 8 778 18 457 19 5 8 498 16 406 Q5 140 154...

Page 3: ...0 8 Figure 3 AIR TUBE SCREWS ELECTRONIC IGNITION TRANSFORMER FLANGE GASKET RETAIN ING CLIP IGNITOR PRIMARY CONTROL REAR ACCESS DOOR GASKET MAIN HOUSING ASSY AIR ADJUST DIAL 4X4 BOX BLOWER WHEEL INLET...

Page 4: ...i mum free area one half square inch per 1 000 Btu per hour input This combustion air should be brought into the area containing the furnace below the level of the furnace burner Table 2 O23V Installa...

Page 5: ...rner assembly from the vestibule By loosen ing the nuts and by turning the whole burner assembly counterclockwise figure 4 the entire burner assembly will come out of the furnace There is adequate wir...

Page 6: ...n outside or through any unconditioned space 6 Chimney should extend 3 feet 0 9 m above highest point where the vent passes through the roof and 2 feet 0 6 m higher than any portion of a building with...

Page 7: ...OR DEATH A living space which provides insufficient combustion air to the furnace can result in headaches nausea dizziness or asphyxiation CAUTION Insufficient combustion air to the furnace can cause...

Page 8: ...space shall be provided with two perma nent openings One opening shall be within 12 305 mm of the top of the enclosure and one within 12 305 mm of the bottom These openings must communicate directly o...

Page 9: ...from Common Venting System In the event that an existing furnace is removed from a venting system commonly run with separate appliances the venting system is likely to be too large to properly vent t...

Page 10: ...of the cabinet See unit dimensions on page 2 Using it as the center point cut a 6 inch 152 mm round hole in the cabinet s side Install the barometric draft control within 18 inches of the furnace flue...

Page 11: ...bing or steel pipe for oil supply pipe Install oil supply pipe under floor or near walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings...

Page 12: ...de the building between the tank shut off valve and the burn er Locate filter close to burner for easy maintenance Table 5 lists the filters for the O23V furnace Table 5 Installation Clearances inches...

Page 13: ...ted The Test jumper is used to operate the motor in the test mode See figure 17 Factory settings for the blower speed jumpers are given in the wiring diagram in figure 18 Figure 17 shows the blower co...

Page 14: ...age cooling closes the R to Y1 circuit on the A54 blower control board The blower motor runs at 57 CFM for the first 7 1 2 minutes of the 1st stage cooling demand After 7 1 2 minutes the blower motor...

Page 15: ...output to an electronic air cleaner The EAC terminal is energized when there is a call for heat cool or continuous blower See figure 18 Table 6 Blower Performance 0 through 0 80 in w g 0 through 200 P...

Page 16: ...Page 16 Figure 18 O23V Wiring Diagram P535277W Downloaded from ManualsNet com search engine...

Page 17: ...s above the range shown in the table check for high static pres sure Table 7 O23V Unit Nozzle Size Spray Angle Pattern Pump PSIG Input Rating BTU Hr Output Rating BTU Hr Head Temp Rise F 70 50GPH 80 A...

Page 18: ...ive Cleaning the Heat Exchanger 1 Remove the vent pipe from the furnace 2 Remove the locking screws and the caps from the clean out tubes Remove flue access elbow 3 Using a long spiral wire brush swee...

Page 19: ...rt Source Procedure Causes Correction Thermostat Check thermostat settings Thermostat in OFF or COOL Switch to HEAT Thermostat is set too low Turn thermostat to higher temperature Safety Overloads Che...

Page 20: ...flame is established Source Procedure Causes Correction Oil Supply Check tank gauge or use dip stick No oil in tank Fill tank Coat dip stick with litmus paste and insert into bottom of tank Water in o...

Page 21: ...ause of overloading Faulty motor Replace motor Troubleshooting Burner starts and fires but lock out on safety Source Procedure Causes Correction Poor Fire After burner fires immediately jumper across...

Page 22: ...ocedure Causes Correction Poor Fire After burner fires immediately jumper across flame detector terminals at the primary control SIf burner continues to run does not lock out of safety fault may be po...

Page 23: ...n air Air leaks into heat exchanger around inspection door etc Correct cause of air leak Excessive draft Adjust barometric draft control for correct draft Incorrect burner head adjustment Correct burn...

Page 24: ...nk Lift D Filter Type Inspect Change E Pressure Test F All fittings checked for tightness Thermostat A Type Heating Cooling B Anticipator Set C Wires New Old Air Filter A Filter Type Permanent Disposa...

Reviews: