IOM / ROOF-TOP FLEXY™ Series - Page 17
Check the setpoints on CLIMATIC™ (LF 20).
COMMISSIONING
C0
Password technician Level
63
C98
Type of Unit
Refer to configuration table LF20
C99
Type of Unit [off] Flexy [on] Linea
On or OFF
C103
Humidity and enthalpy management Option
[off] LINEA
[on] only Flexy with Advanced Pack
C77
(Linea) Authorisation of defrost. Threshold of temperature
of refrigerant fluid ( in°C)
1.0°C for R407c
-3.0°C for R22
C79
Defrost cycle end value indicating the nr of Start-ups of the
condenser fan to signify the end of defrost
Linea set to1
Flexy set to 3
C101
Activation of all seasons control option
[ON] / [OFF] if fitted
C73
All seasons control option on FLEXY -
Otherwise – unloading 50% of the compressors in cooling
mode
Set to 20.0°C for Linea
Set to 12°C for Flexy
C74
If option all seasons control – shut down condenser fans -
Otherwise - 100% unloading of compressors in cooling
mode -
Set to 12.0°C for Linea
Set to 5.0°C for Flexy
C49
Threshold of activation of the power exhaust fan according
to the position of the economiser damper (in %)
Set to 50%
C46
Number of minutes of anticipation per degrees. This allows
an anticipated start-up in the morning mode depending on
the outside temperature.
Set to 0
C83
Maximum usable power for electric heat (in %)
C90
Choice of operating mode for KP17
[ON] = KP17 in ON / OFF mode
C91
Identification number for the J-Bus connections
C93
Identification number for the connections link between
boards
C94
Number of boards linked on the bus
C95
Selection of the operating mode for KP017
C96
Selection of exchange mode for room temperature and
humidity-
C97
Selection of exchange mode for outdoor temperature and
humidity
C100
Activation of the dual-speed option for fan supply (Flexy)
C101
Activation of the all seasons control option
C102
Activation of the optimised defrost option
C05
Fault reset
Set to ON
C06
Remote control, On / Off Unit
Set to ON ( the unit should start)
Summary of Contents for ROOFTOP FLEXY FCA 100
Page 1: ...INSTALLATION OPERATING MAINTENANCE MANUAL ROOFTOP FLEXY English August 2003 ...
Page 2: ......
Page 33: ...IOM ROOF TOP FLEXY Series Page 31 AIR FLOW BALANCING AT 12 12 FAN ...
Page 34: ...Page 32 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING AT 15 15 FAN ...
Page 35: ...IOM ROOF TOP FLEXY Series Page 33 AIR FLOW BALANCING AT 18 13 ...
Page 36: ...Page 34 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING AT 18 18 FAN ...
Page 37: ...IOM ROOF TOP FLEXY Series Page 35 AIR FLOW BALANCING RDN 450 FAN ...
Page 38: ...Page 36 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING ADN 355 FAN ...
Page 39: ...IOM ROOF TOP FLEXY Series Page 37 AIR FLOW BALANCING ADN 400 FAN ...
Page 40: ...Page 38 IOM ROOF TOP FLEXY Series AIR FLOW BALANCING ADN 450 FAN ...
Page 104: ...Page 102 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS MAIN CURRENT DIAGRAM ...
Page 106: ...Page 104 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS CLIMATIC CONTROLLER ...
Page 108: ...Page 106 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS CLIMATIC INPUT FG FD ...
Page 112: ...Page 110 IOM ROOF TOP FLEXY Series ELECTRICAL WIRING DIAGRAMS GAS BURNER 180 Kw ...
Page 132: ...Page 130 IOM ROOF TOP FLEXY Series ISO 9001 CERTIFICATION ...
Page 133: ...IOM ROOF TOP FLEXY Series Page 131 PED CERTIFICATION OF CONFORMITY ...
Page 134: ...Page 132 IOM ROOF TOP FLEXY Series GLASS WOOL FIRE CLASS ...
Page 135: ...IOM ROOF TOP FLEXY Series Page 133 33 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Page 136: ...Page 134 IOM ROOF TOP FLEXY Series 60 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Page 137: ...IOM ROOF TOP FLEXY Series Page 135 120 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Page 138: ...Page 136 IOM ROOF TOP FLEXY Series 180 kW GAS BURNER CE CERTIFICATION OF CONFORMITY ...
Page 139: ...IOM ROOF TOP FLEXY Series Page 137 INSULATION FIRE CLASS ...
Page 140: ...Page 138 IOM ROOF TOP FLEXY Series INSULATION FIRE CLASS ...
Page 141: ......