BLOWER DATA
SLP99UH110XV60C BLOWER PERFORMANCE (less filter)
BOTTOM RETURN AIR
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35%
40%
50%
60%
70%
80%
90%
100%
Increase (+15%) Heat CFM
767
861
1049
1237
1424
1612
1800
1988
Increase (+7.5%) Heat CFM
738
825
1000
1174
1349
1524
1699
1874
Default Heat CFM
708
789
951
1112
1274
1436
1597
1759
Decrease (-7.5% ) Heat CFM
655
731
883
1035
1187
1339
1491
1644
Decrease (-15% ) Heat CFM
602
673
816
958
1101
1243
1386
1528
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm
Second Stage Cool Speed - cfm
Low
Medium-
Low
Medium
High
High
(Default)
Low
Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM
1060
1245
1345
1545
1560
1740
1930
2125
Default Cool CFM
970
1145
1265
1395
1405
1565
1775
1945
Decrease (-10%) Cool CFM
885
1025
1110
1250
1270
1425
1610
1770
The effect of static pressure is included in air volumes shown.
The following control configurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between.
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times.
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages.
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28% and 38% (DIP switch selectable) of the same second-stage COOL speed position.
minimum 380 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 450 cfm.