Page 17
BLOWER DATA
SLP99UH135XV60D BLOWER PERFORMANCE (less filter)
BOTTOM RETURN AIR
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35%
40%
50%
60%
70%
80%
90%
100%
Increase (+15%) Heat CFM
949
1033
1200
1367
1534
1701
1868
2035
Increase (+7.5%) Heat CFM
879
957
1113
1269
1426
1582
1738
1895
Default Heat CFM
808
881
1026
1172
1317
1463
1608
1754
Decrease (-7.5% ) Heat CFM
748
817
956
1095
1235
1374
1513
1652
Decrease (-15% ) Heat CFM
687
753
886
1019
1152
1284
1417
1550
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm
Second Stage Cool Speed - cfm
Low
Medium-
Low
Medium
High
High
(Default)
Low
Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM
1070
1260
1410
1555
1565
1750
1970
2190
Default Cool CFM
980
1115
1255
1430
1445
1615
1805
1985
Decrease (-10%) Cool CFM
865
1020
1115
1280
1290
1470
1650
1805
The effect of static pressure is included in air volumes shown.
The following control configurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between.
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times.
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages.
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28% and 38% (DIP switch selectable) of the same second-stage COOL speed position.
minimum 380 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 450 cfm.