Page 3
XP19 SERIES
Table 1. Torque Requirements
Parts
Recommended Torque
Service valve cap
8 ft.− lb.
11 NM
Sheet metal screws
16 in.− lb.
2 NM
Machine screws #10
28 in.− lb.
3 NM
Compressor bolts
90 in.− lb.
10 NM
Gauge port seal cap
8 ft.− lb.
11 NM
USING MANIFOLD GAUGE SETS
When checking the system charge, only use a manifold
gauge set that features low loss anti−blow back fittings.
See Figure 3 for a typical manifold gauge connection
setup.
Manifold gauge sets used with HFC−410A refrigerant
systems must be capable of handling the higher system
operating pressures. The gauges should be rated for use
with pressures of 0 − 800 on the high side and a low side of
30" vacuum to 250 psi with dampened speed to 500 psi.
Gauge hoses must be rated for use at up to 800 psi of
pressure with a 4000 psi burst rating.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for
removing refrigerant, flushing, leak testing, evacuating,
checking charge and charging.
Each valve is equipped with a service port which has a
factory−installed valve stem.
IMPORTANT
Only use Allen wrenches of sufficient hardness
(50Rc − Rockwell Harness Scale minimum). Fully
insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9
ft−lbs for small valves, to 25 ft−lbs for large valves) to
prevent refrigerant loss during shipping and
handling. Using an Allen wrench rated at less than
50Rc risks rounding or breaking off the wrench, or
stripping the valve stem recess.
1
2
3
4
5
6
7
8
9
10
11 12
1/6 TURN
1
2
3
4
5
6
7
8
9
10
11 12
1/12 TURN
Figure 2. Cap Tightening Distances
IMPORTANT
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and
fitted snugly over the cap before tightening.
To Access Angle−Type Service Port:
A service port cap protects the service port core from
contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized
wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and
tighten as follows:
D
With Torque Wrench
: Finger tighten and then
tighten per Table 1.
D
Without Torque Wrench
: Finger tighten and use an
appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in Figure 2.
To Open and Close Angle−Type Service Valve:
A valve stem cap protects the valve stem from
contamination and assures a leak−free seal.
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension
(3/16" for liquid-line valve sizes and 5/16" for
vapor-line valve sizes) to back the stem out
counterclockwise as far as it will go.
OUTDOOR
COIL
CHECK
EXPANSION VALVE
BI−FLOW
FILTER /
DRIER
TO
HFC−410
A DRUM
LOW
PRESSURE
COMPRESSOR
REVERSING VALVE
VAPOR
LINE
VALVE
MUFFLER
NOTE − Arrows indicate direction
of refrigerant flow.
CHECK EXPANSION VALVE
HEAT PUMP
LIQUID
SERVICE
PORT
GAUGE MANIFOLD
DISTRIBUTOR
INDOOR
COIL
VAPOR
SERVICE
PORT
HIGH
PRESSURE
LIQUID
LINE
VALVE
Figure 3. Typical Manifold Gauge Connection Setup