Page 7
BLOWER DATA
SL297UH080NV48C BLOWER PERFORMANCE (less filter)
BOTTOM RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
1499
1640
+18%
1427
1546
+12%
1361
1472
+6%
1294
1399
Factory Default
1219
1315
–6%
1176
1242
–12%
1090
1173
–18%
1007
1077
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low
Medium-High
2
High
Low
Medium-Low
Medium-High
2
High
+
797
954
1071
1241
1102
1304
1508
1713
Factory Default
713
873
969
1147
1006
1186
1392
1588
–
623
767
880
1025
911
1068
1252
1422
SL297UH080NV48C BLOWER PERFORMANCE (less filter)
SINGLE SIDE RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
1433
1542
+18%
1353
1480
+12%
1275
1398
+6%
1229
1334
Factory Default
1154
1253
–6%
1093
1181
–12%
1024
1107
–18%
958
1054
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low
Medium-High
2
High
Low
Medium-Low
Medium-High
2
High
+
792
959
1118
1264
1104
1302
1530
1730
Factory Default
844
876
1008
1162
1001
1202
1397
1612
–
643
771
908
1055
915
1090
1253
1443
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 380 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 380 cfm.