Page 9
BLOWER DATA
SL297UH080NV60C BLOWER PERFORMANCE (less filter)
SINGLE SIDE RETURN AIR
- Air volumes in
bold
require Optional Return Air Base and
field fabricated transition to accommodate
20 x 25 x 1 in. cleanable air filter in order to maintain proper air velocity across the filter.
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
1491
2027
+18%
1414
1901
+12%
1351
1801
+6%
1284
1722
Factory Default
1211
1621
–6%
1130
1517
–12%
1048
1407
–18%
993
1323
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low
Medium-High
2
High
Low
Medium-Low
Medium-High
2
High
+
1094
1279
1430
1609
1599
1823
2051
2239
Factory Default
1003
1160
1308
1454
1438
1649
1863
2097
–
894
1044
1166
1309
1301
1490
1683
1897
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 450 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 450 cfm.