Page 70
IX- Program Unit Capacity Size Modes
Power-Up
- Number displayed represents by integrated control unit size code (furnace model
and capacity). If three horizontal bars are displayed followed by continuous E203, furnace
control does not recognize
unit size code.
Configure per the following:
Furnace control in
IDLE
mode
No heating, cooling or indoor fan
operation)
To enter
Program Unit
Capacity/Size:
push
and hold button next to
7-segment LED display
until
solid “P”
symbol
appears. Release
button.
Turn room thermostat to
OFF
Solid
P
starts
blinking on
7-Segment LED
Push and hold button. Integrated control will
display unit size code number for each
furnace model for three seconds.
When the correct unit size code is displayed, release
button. Selected code will flash for 10-second period.
During that period, press and hold push button for 5
seconds. Integrated control will store code in
memory and will automatically exit
Program Unit
Capacity/Size Mode
and reset. (If second period
expires or push button is held less than five seconds,
control will automatically exit
Program
Capacity/Size Mode
and go into
IDLE
mode without
storing unit size code. If this happens, programming
function must be repeated).
Verify that the selected unit size code is correct
and stored in non-volatile memory by cycling
the 24 volt power to the furnace control. (At 24
volt power-up of the furnace control, the
7-segment LED will display a unit size code. If
three horizontal bars display, board does not
recognize unit size code. Programming
function must be repeated)
Yes
No
IMPORTANT
: Field replacement controls may
need to be manually configured to validate
furnace unit size code.
FURNACE MODEL
SL297UH040NV36B
SL297UH060NV36B
SL297UH080NV48C
SL297UH080NV60C
UNIT SIZE
CODE
0
1
3
4
−
−−
_
P
−
−−
FINISHED