20
Table 5. Lennox Smart Air Quality Monitor Alert Codes
Alert
ID
Source
device
Causing
Alert
Alert Code
Message
Priority
Condition
Troubleshooting
Clear Condition
70002
SAQM
IAQ: Internal
Data Fault
Service Soon
Unable to access internal data.
Cycle device power may clear
condition.
To cycle power, remove device
from the wall and disconnect the
R
terminal and then reconnect.
If cycling power does not resolve
issue then:
• Remove device from the smart
devices network.
• Perform a factory reset of the
for procedure.
• Perform the procedure to add
the device back to smart devices
network.
If recycling power or factory
reset does not resolve issue
then replace the
SAQM.
Automatically clears when
the system detects that the
issue no longer exists.
70003
SAQM
IAQ: Side
Switch in OFF
position
Service
Urgent
Slide the side switch to the ON
position. ON is the up position.
When the side switch is set
back to the ON position it
will automatically clear this
alert code.
70004
SAQM
IAQ: Replace
Smart IAQ
Monitor
Service Soon
The five year service life of the device
is about to expire.
Device will continue to function
however sensor data collected may
become unreliable thus affecting air
quality in the home.
Remove device from smart
devices network and then
replace the
SAQM
.
Automatically clears when
the system detects that the
issue no longer exists.