Stove Installation Configurations
Clearances
Models Profile 20-Freestanding
&
Profile 30-
Freestanding
- Standard Residential or Manufactured
(Mobile Home Installation. These appliances require the
following minimum clearances to combustibles:
Stove Clearances to Combustibles (inches).
inch / millimeter
Back Wall
1"
I
26mm
Side Wall
6" / 153 mm
Corner
1" / 26 mm
Floor Protector - Front 6" / 153 mm
6"
Sides O" / 0 mm
Back O" / 0 mm
Combustible Wall
Floor Protection
If placing stove on a combustible surface, the following
requirements must be met:
A non-combustible floor protector must fully cover
the area beneath the appliance and extend 6 " to
the front of the face of the door opening and O " be
yond both sides and back of the stove body.
Hearth Pad
'---.,1,.
5
n
5n
Page 11
Clearances
Model Traditions P11
-
Freestanding
- Standard
Residential or Manufactured (Mobile Home Installation.
These appliances require the following minimum clear
ances to combustibles:
Stove Clearances to Combustibles (inches).
inch/ millimeter
Back Wall
2" / 51 mm
Side Wall
6" / 153 mm
Corner
2"
I
51 mm
Floor Protector - Front 6" / 153 mm
Sides O" / 0 mm
Back O" / 0 mm
Combustible Wall
Floor Protection
If placing stove on a combustible surface, the following
requirements must be met:
A non-combustible floor protector must fully cover
the area beneath the appliance and extend 6 " to
the front of the face of the door opening and O " be
yond both sides and back of the stove body.
Hearth Pad