background image

13

Model

Condensate 

Life Pump 

Factory 

Mounted

Condensate 

Pump Lift  

Measurement

Condensate Pump 

Facility on Indoor 

PCB Board

Condensate 

Outlet of 

Indoor Unit

Flexible Drain Con­

nection (supplied 

with unit)

VOSB Outside Air 

Ducted

Yes - 036-054

No - 072/096

18 “

Yes

1” O.D.

1-5/8” O.D. 

adapter pro-

vided

1” I.D.

Table 4. Condensate Connection Sizes

Wiring Connections

In the U.S.A., wiring must conform with current local 

codes and the current National Electric Code (NEC). In 

Canada, wiring must conform with current local codes and 

the current Canadian Electrical Code (CEC). 

Refer to unit nameplate for minimum circuit ampacity and 

maximum overcurrent protection size.

NOTE - 

Two-conductor stranded shielded cable must be 

used for the communication wiring. This is necessary to 

ensure proper system communication and operation.

•  Indoor and outdoor unit equipment must each be on 

their own a dedicated breaker.

•  Indoor units must have a dedicated service disconnect. 

Switches are acceptable; however it must be a double 

pole switch that disconnects L1 and L2.

 WARNING

Isolate the power supply before accessing unit electrical 

terminals.
Install unit so that unit disconnect is accessible.
Follow all local and national codes, as well as this 

installation instruction, during installation. Do NOT 

overload electrical circuit, as this may lead to failure and 

possible fire.
Use  specified  wiring  and  cable  to  make  electrical 

connections. Clamp cables securely and make sure that 

connections are tight to avoid strain on wiring. Insecure 

wiring connections may result in equipment failure and 

risk of fire. 

Wiring must be installed so that all cover plates can be 

securely closed.

Do not attempt to repair a damaged power cord.

Do not modify the power cord in any way. Do not 

attempt to extend the length of the power cord or use 

an extension cord with this appliance. Do not share the 

single power outlet with any other appliances.

 CAUTION

This unit must be properly grounded and protected by a 

circuit breaker. The ground wire for the unit must not be 

connected to a gas or water pipe, a lightning conductor 

or a telephone ground wire. 

Do not connect power wires to the outdoor unit until 

all other wiring and piping connections have been 

completed.

Install all wiring at least 3 feet away from televisions,  

radios or other electronic devices in order to avoid the 

possibility of interference with the unit operation.

Do not install the unit near a lighting appliance that 

includes a ballast. The ballast may affect remote control 

operation.

Using an External Water Level Switch

1.  Disconnect the closed circuit loop connection  

labeled WATER. 

2. 

Connect the provided overflow harness accessory to 

the WATER connection. See Figure 14.

3.  See unit wiring diagrams for location of the WATER 

connection.

The connection has 5 VDC current, do not supply field 

voltage.
Table 3 lists available external condensate pump 

accessories. See Table 4 for connection sizes.

G

L2
L1

NC

COM

NO

PUMP

CONNECTIONS

0.5A

G

L1

L2

GREEN

OPTIMAL

Cut wire here

INDOOR 

UNIT 

MAIN 

BOARD

Connect to 

pump here 

using solder 

or butt joints

WATER

WATER

Figure 14. External Water Level Switch Connection

Summary of Contents for VOSB Series

Page 1: ...oss of life Installation and service must be performed by a li censed professional HVAC installer service agency or the gas supplier Failure to follow safety warnings and these instruc tions exactly c...

Page 2: ...cations department When the indicated lengths change from the figures stated within the report it is imperative that prior to the commencement of the refrigerant pipe work installation Lennox VRF appl...

Page 3: ...ETURN AIR DUCT OPENING SUPPLY AIR DUCT OPENING RIGHT SIDE VIEW LIQUID PIPE GAS PIPE AIR FLOW SECTION B B SUPPLY AIR DUCT OPENING AUXILIARY DRAIN CONNECTION Either Side PRIMARY DRAIN CONNECTION Either...

Page 4: ...IR DUCT OPENING 6 152 36 7 8 937 Supply Air Duct Opening 2 51 14 7 8 378 38 1 4 972 34 5 8 879 19 7 8 505 2 3 4 70 3 76 44 1 8 1120 13 1 2 343 38 1 4 972 32 7 8 835 56 3 4 1441 50 1270 12 1 8 308 5 1...

Page 5: ...Minimum Clearance Ceiling Wall Wall 1 25 mm Minimum Clearance Ceiling Suspended Minimum Service Clearance Figure 1 Minimum Installation Clearances NOTE No part of the suspended ceiling or other suppo...

Page 6: ...line radio telephone security system or intercom Electrical interference and radio frequencies from any of these sources may affect operation WARNING Do not install the unit in an area where flammabl...

Page 7: ...tighten each of the four nuts above the brackets down onto the brackets This will ensure that the unit remains level 5 It is recommended to install a field provided isolation grommet as shown in Figu...

Page 8: ...ut Filter Filter removal tab 3 Reverse these steps to reinstall the filter Be sure to reinstall the receiver if it was detached during the filter removal Figure 8 Filter Partially Removed Indoor Unit...

Page 9: ...for leaks per commissioning instructions WARNING WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing Ap...

Page 10: ...refrigerant line ports 3 Slowly loosen one of the rubber plugs to release the factory nitrogen charge Remove the rubber plug from both liquid and gas lines 4 Connect the liquid and gas lines to the ev...

Page 11: ...drain piping is properly routed and insulatedinordertopreventbothleaksandcondensation Follow these instructions exactly to ensure proper drainage and unit operation IMPORTANT You must confirm operati...

Page 12: ...spension Rods 3 ft 1 m Support straps NOTE Drain line should be sloped 1 4 inch per foot 18 mm per m AWAY from unit and should be supported as needed to prevent sagging Do not overtighten drain fittin...

Page 13: ...tight to avoid strain on wiring Insecure wiring connections may result in equipment failure and risk of fire Wiring must be installed so that all cover plates can be securely closed Do not attempt to...

Page 14: ...230V 1Ph 60Hz Power supply Mode Selection Box Indoor unit Indoor unit Indoor unit Dedicated breaker Service Disconnect L1 L2 L1 L2 Fuse Service Disconnect L1 L2 Fuse Service Disconnect L1 L2 Fuse Serv...

Page 15: ...polarity sensitive Typical Wiring Diagram NEC CEC and Local Codes apply Outdoor unit Outdoor unit sub1 unit Outdoor unit sub2 unit PQ main unit PQ MS Box PQ PQ MS Box PQ PQ H1 H2 H1 H2 H1 H2 Outdoor...

Page 16: ...Terminal Block HA HB 12V COM P Q Ground cable shield to Indoor Unit chassis Tightening torque for the terminal screws Use the correct screwdriver for tightening the terminal screws If the terminal sc...

Page 17: ...valve XT1 2 PUMP CS ALARM SVD Solenoid valve Code Title T2B E U L B T2A WHITE T1 T0 RED ACK L B TA C A L B K T2 Outlet air temperature sensor To wired controller power Display Board NOTE Component in...

Page 18: ...ntent E0 E1 E2 E4 E5 Mode conflict Communication error between indoor and main outdoor unit T0 Inlet air temperature sensor malfunction TA Outlet airtemperature sensor malfunction T2B Outlet of evapor...

Page 19: ...o the black wire on each end or use the VRF accessory V0SNSR00P 13G99 to splice in the extension cable 6 Locate the return air thermistor to the conditioned area of which the indoor unit serves Figure...

Page 20: ...function T2B Outlet of evaporator sensor malfunction T2A Inlet of evaporator sensor malfunction Error Content Error code FE Eb U4 Ed EE F8 No address EEV malfunction MS self inspection error Outdoor u...

Page 21: ...fixed plastic mounting brackets on the back of the receiver Figure 26 into the two slots on the bottom of the electrical control box Figure 25 and slide to secure it 3 Connect the 10 conductor wire o...

Page 22: ...emote controller No Content Recorded Value Date 0 Normal display 1 Communication address of indoor unit 2 Indoor unit capacity horsepower 3 Network address of indoor unit 4 The actual setpoint tempera...

Page 23: ...er power has been broken and restored at the disconnect switch or circuit breaker call VRF Technical Support 1 844 438 8731 Error Code Description FE No address E0 Mode conflict E1 Communication error...

Page 24: ...24 Technical Support 1 844 GET VRF1 1 844 438 8731 vrftechsupport lennoxind com www LennoxVRF com Download the app from the Apple App Store or the Google Play store...

Reviews: