PDU load groups
The PDU load groups are described in the following tables.
Table 1. Switched and monitored 1U C19 PDU load groups
Circuit breaker number
Associated front outlet
Associated rear outlet
Phase (when using 3-
phase input power)
1
1
10
1
2
2
3
3
4
4
11
2
5
5
6
6
7
7
12
3
8
8
9
9
Table 2. Switched and monitored 1U C13 PDU load groups
Circuit breaker number
Associated outlets (The load
segment number that is visible on
the front of the PDU is in
parentheses.)
Phase (when using 3-phase input
power)
1
1 and 2 (1)
1
2
3 and 4 (2)
3
5 and 6 (3)
2
4
7 and 8 (4)
5
9 and 10 (5)
3
6
11 and 12 (6)
Load balancing
The internal circuits of some PDUs might be overloaded if you are not aware of the circuit breaker
specifications and how the PDU outlets are connected. If loads are greater than the specification of the
circuit breaker, it will trip and turn off the load.
There are either six or nine circuit breakers on the front of the PDU, depending on the model. Each circuit
breaker is rated for 20 amps. When you connect loads, make sure that the rating for each circuit breaker is
not exceeded.
Some PDUs can be connected to three-phase power. The loads should be distributed across all three
phases. If single-phase power is used, it also is important to distribute the load between the outlet groups.
The PDU models with 12 C13 outlets on the front have phase one connected to the first 4 outlets, outlet
group one. Phase two is connected to the next 4 outlets, outlet group two and phase three are connected to
the last 4 outlets, outlet group three (see the following illustration).
Chapter 1
.
Introduction
7
Summary of Contents for 46M4002
Page 1: ...1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 24: ...16 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 30: ...22 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 34: ...26 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 56: ...48 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 60: ...52 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 62: ...54 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 68: ...60 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 70: ...62 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 74: ...66 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 85: ......
Page 86: ......