Chapter 4. Power cables connection
CAUTION:
This product might be equipped with a hard-wired power cable. Ensure that a
licensed electrician performs the installation per the national electrical code.
(C022)
Important:
This connection must be carried out by qualified electrical personnel.
Before carrying out any connection, check that the upstream protection devices
(Normal AC source and Bypass AC source) are open "O" (off).
Always connect the ground wire first.
Important:
Before connecting the HotSwap MBP to the UPS, make sure the UPS
has been properly shut down.
Always connect the ground wire first.
Access to terminal blocks
Procedure
1.
Remove the terminal blocks cover (one screw).
2.
Punch the knockouts and insert the cables/conduits inside.
Important: High leakage current:
An earth connection is essential before
connecting to the power supply.
Input/Output connection
About this task
Important:
This type of connection must be carried out by qualified electrical
personnel.
Before carrying out any connection, check that the upstream protection device
(Normal AC source) is open "O" (off).
© Copyright Lenovo 2015
25
Summary of Contents for 5594-5KX
Page 1: ...3U Rack or Tower UPS RT5 0kVA and RT6 0kVA Installation and User s Guide ...
Page 2: ......
Page 3: ...3U Rack or Tower UPS RT5 0kVA and RT6 0kVA Installation and User s Guide ...
Page 6: ...iv Installation and User s Guide ...
Page 18: ...xvi Installation and User s Guide ...
Page 22: ...4 Installation and User s Guide ...
Page 34: ...16 Installation and User s Guide ...
Page 50: ...32 Installation and User s Guide ...
Page 60: ...42 Installation and User s Guide ...
Page 72: ...54 Installation and User s Guide ...
Page 84: ...66 Installation and User s Guide ...
Page 86: ...68 Installation and User s Guide ...
Page 87: ......
Page 88: ...Part Number 00WA360 Printed in USA 1P P N 00WA360 ...