Note:
In High Efficiency mode, the UPS is in Bypass mode and transfers to Battery
mode in less than 10 microseconds (ms) when utility power fails. Transfers to High
Efficiency (HE) mode will be active after 5 minutes of Bypass voltage monitoring:
if Bypass quality is not in tolerance, then the UPS will remain in Online mode.
Transferring the UPS between modes
From Online or Battery to Bypass mode.
Press any button to activate the menu
options, then select
Control
and
Go to Bypass
.
From Bypass to Online or Battery mode.
Press any button to activate the menu
options, then select
Control
and
Go back normal
.
Setting High Efficiency mode
About this task
In High Efficiency mode, the UPS is in Bypass mode and transfers to Battery mode
in less than 10 microseconds (ms) when utility power fails. Transfers to High
Efficiency (HE) mode will be active after 5 minutes of Bypass voltage monitoring:
if Bypass quality is not in tolerance, then the UPS will remain in Online mode.
To set High Efficiency mode:
Procedure
1.
Put the UPS on Bypass: press any button to activate the menu options, select
Control
>
Go to Bypass
.
2.
Then, press
Escape
and select
Settings
>
In/Out settings
>
High Efficiency
mode
.
3.
Select
Enabled
and
Enter
to confirm. The UPS goes into Bypass mode and
transfers to Battery mode in the event utility power fails.
Configuring Bypass settings
The following settings are available for configuring Bypass operation for special
situations. Normally, these settings will not need to be changed.
Bypass transfer out of tolerance
Procedure
1.
Press any button to activate the menu options, then select
Settings
>
Output
settings
>
Bypass transfer
.
2.
Select
Enabled
or
Disabled
for
BP AC NOK
, and
Enter
to confirm. If
Enabled
,
the UPS transfers to Bypass even if Bypass AC source is out of tolerance,
depending on output mode. If
Disabled
, the UPS output is shut down.
Interrupt time
This setting is displayed to define the break duration during transfer to Bypass,
only if transfer out of tolerance is enabled. 10 ms or 20 ms can be selected.
30
Installation and User's Guide
Summary of Contents for 5594-5KX
Page 1: ...3U Rack or Tower UPS RT5 0kVA and RT6 0kVA Installation and User s Guide ...
Page 2: ......
Page 3: ...3U Rack or Tower UPS RT5 0kVA and RT6 0kVA Installation and User s Guide ...
Page 6: ...iv Installation and User s Guide ...
Page 18: ...xvi Installation and User s Guide ...
Page 22: ...4 Installation and User s Guide ...
Page 34: ...16 Installation and User s Guide ...
Page 50: ...32 Installation and User s Guide ...
Page 60: ...42 Installation and User s Guide ...
Page 72: ...54 Installation and User s Guide ...
Page 84: ...66 Installation and User s Guide ...
Page 86: ...68 Installation and User s Guide ...
Page 87: ......
Page 88: ...Part Number 00WA360 Printed in USA 1P P N 00WA360 ...