n.o.
: contact normally open
n.c.
: contact normally closed
Status active information: (if contact between
pin and common is closed)
v
Pin 1: not on Bypass
v
Pin 2: load not protected
v
Pin 3: not low battery
v
Pin 4: not on Battery
v
Pin 5: user common
v
Pin 6: on Bypass
v
Pin 7: low battery
v
Pin 8: load protected
v
Pin 9: on Battery
Important:
The relay output contacts must not be connected to any utility
connected circuits.
Reinforced insulation to the utility is required. The relay output contacts have a
maximum rating of 250 Vac/5A.
Remote On/Off
Remote On/Off allows remote control of the power (
) button to switch the UPS
on and off.
Normally open
When contact changes from open to closed, the UPS is switched on (or stays on).
When contact changes from closed to open, the UPS is switched off (or stays off).
Note:
On/Off control using the power (
) button has priority over the remote
control.
Remote Power Off
RPO is used to disable the UPS remotely. This feature can be used for unpowering
the load and shutting down the UPS by an external event, for example when the
room temperature is too high. When RPO is activated, the UPS disables the output
and all its power converters immediately. The UPS remains on, to alarm the fault.
34
Installation and User's Guide
Summary of Contents for 5594-5KX
Page 1: ...3U Rack or Tower UPS RT5 0kVA and RT6 0kVA Installation and User s Guide ...
Page 2: ......
Page 3: ...3U Rack or Tower UPS RT5 0kVA and RT6 0kVA Installation and User s Guide ...
Page 6: ...iv Installation and User s Guide ...
Page 18: ...xvi Installation and User s Guide ...
Page 22: ...4 Installation and User s Guide ...
Page 34: ...16 Installation and User s Guide ...
Page 50: ...32 Installation and User s Guide ...
Page 60: ...42 Installation and User s Guide ...
Page 72: ...54 Installation and User s Guide ...
Page 84: ...66 Installation and User s Guide ...
Page 86: ...68 Installation and User s Guide ...
Page 87: ......
Page 88: ...Part Number 00WA360 Printed in USA 1P P N 00WA360 ...