Severity: Critical
User Action:
1. Ensure all five fans are installed.
2. Reseat the indicated missing fans.
3. Replace the indicated missing fans.
•
040800B1: FAN2_NO_PRESENT: Fan sensor, Device Removed / Device Absent was asserted.
Indicated fan module is missing from the fan slot
Severity: Critical
User Action:
1. Ensure all five fans are installed.
2. Reseat the indicated missing fans.
3. Replace the indicated missing fans.
•
040800B2: FAN3_NO_PRESENT: Fan sensor, Device Removed / Device Absent was asserted.
Indicated fan module is missing from the fan slot
Severity: Critical
User Action:
1. Ensure all five fans are installed.
2. Reseat the indicated missing fans.
3. Replace the indicated missing fans.
•
040800B3: FAN4_NO_PRESENT: Fan sensor, Device Removed / Device Absent was asserted.
Indicated fan module is missing from the fan slot
Severity: Critical
User Action:
1. Ensure all five fans are installed.
2. Reseat the indicated missing fans.
3. Replace the indicated missing fans.
•
040800B4: FAN5_NO_PRESENT: Fan sensor, Device Removed / Device Absent was asserted.
Indicated fan module is missing from the fan slot
Severity: Critical
User Action:
1. Ensure all five fans are installed.
2. Reseat the indicated missing fans.
3. Replace the indicated missing fans.
•
080701AA: PSU_POLICY_LOST: Power Supply, transition to Non-Critical from OK was asserted.
The configured PSU policy has been disabled
Severity: Warning
User Action:
1. Check the inventory power of all powered on nodes to see if the summary over current power bank
– Replace the node with light configuration
12
ThinkSystem D2 Enclosure, Modular Enclosure, Modular Enclosure for 6U Configuration and ThinkSystem SD530 Compute Node
Messages and Codes Reference
Summary of Contents for 7X20