Load
UPS5000 battery
(hours:minutes)
With 1 OBP
(hours:minutes)
With 2 OBPs
(hours:minutes)
With 3 OBPs
(hours:minutes)
With 4 OBPs
(hours:minutes)
50 W
6:49
18:03
31:32
45:33
59:56
100 W
4:50
12:51
22:29
32:30
42:46
200 W
3:00
8:03
14:06
20:23
26:50
300 W
2:09
5:47
10:10
14:42
19:22
400 W
1:39
4:30
7:54
11:26
15:04
500 W
1:20
3:39
6:26
9:19
12:17
600 W
1:07
3:04
5:24
7:50
10:20
700 W
0:57
2:38
4:39
6:45
8:54
800 W
0:50
2:18
4:04
5:55
7:48
900 W
0:44
2:02
3:37
5:15
6:56
1000 W
0:39
1:50
3:15
4:43
6:14
1200 W
0:32
1:30
2:41
3:55
5:11
1400 W
0:26
1:16
2:17
3:20
4:25
1600 W
0:22
1:06
1:59
2:54
3:50
1800 W
0:19
0:58
1:45
2:33
3:23
2000 W
0:17
0:52
1:33
2:17
3:01
2500 W
0:12
0:40
1:13
1:47
2:22
3000 W
0:09
0:32
1:00
1:28
1:57
3400 W
0:07
0:25
0:50
1:12
1:40
4000 W
0:06
0:23
0:43
1:00
1:25
4500 W
0:05
0:20
0:38
0:54
1:15
Table 3 lists the number of hours needed to recharge the IBM UPS5000 HV uninterruptible power supply
and optional Online Battery Packs.
Table 3. Recharge times
UPS5000 battery With 1 OBP
With 2 OBPs
With 3 OBPs
With 4 OBPs
Recharge time
3 hours
9 hours
15 hours
21 hours
27 hours