Operation
status
Cause
Description
Is Battery
Being
Charged?
End of
backup time
1 beep every
3 seconds
The UPS is in Battery mode
and the battery packs are
running low.
This warning is
approximate, and the actual
time to shut down might
vary significantly.
Depending on the UPS load
and number of Extended
Battery Modules (EBMs), the
"Battery Low" warning
might occur before the
battery packs reach 20%
capacity.
No
High
Efficiency
mode
The UPS is operating in
High Efficiency mode.
The UPS is powering and
protecting the equipment.
Yes
Bypass mode
An overload or a fault has
occurred, or a command has
been received, and the UPS
is in Bypass mode.
Equipment is powered
directly from AC input and
is not protected by the UPS.
Yes
Display functions
Press the Enter (
) button to activate the menu options. Use the two middle
buttons (
and
) to scroll through the menu structure. Press the Enter (
)
button to select an option. Press the
button to cancel or return to the previous
menu.
Main menu
Submenu
Function
Measurements
[Load] W VA A pf / [Input/Bypass] V Hz
/ [Output/Efficiency] V Hz %/ [Battery]
% min V n° / [DCbus] V / [Average
power usage] Wh / [Cumulat. power
usage] Wh since date
Control
Go to Bypass
Transfers the UPS on Bypass mode
Start battery test
Starts a manual battery test
Reset fault state
Clears active fault
Restore factory settings
Returns all settings to factory values
Reset average power
Clears average power usage measurement
Reset cumul. power
Clears accumulated power usage
measurement
Dry contacts test
Tests dry contact relay outputs
Chapter 2. Presentation
9
Summary of Contents for RT11.0VA
Page 2: ......
Page 18: ...xvi Installation and User s Guide ...
Page 22: ...4 Installation and User s Guide ...
Page 86: ...68 Installation and User s Guide ...
Page 98: ...80 Installation and User s Guide ...
Page 100: ...82 Installation and User s Guide ...
Page 101: ......
Page 102: ...Part Number 00WA361 Printed in USA 1P P N 00WA361 ...