Submenu
Available settings
Default settings
Battery settings
Automatic battery
test
In constant charge
mode:
[No test] [Every day]
[Every week] [Every
month]
In ABM cycling
mode:
[No test] [Every ABM
cycle]
[Every ABM cycle]
Low battery warning [0%] ... [100%]
The alarm triggers
when the set
percentage of battery
capacity is reached
during back-up time.
[20%]
Restart battery level
[0%] ... [100%]
If set, automatic
restart will occur
only when
percentage of battery
charge is reached.
[0%]
Battery charge mode
[ABM cycling]
[Constant charge]
[ABM cycling]
External battery
[Auto detection]
[Manual EBM set.]
[Manual battery set.]
[No battery]
[Auto detection]
Using standard EBM,
UPS detects
automatically the
number of EBM
connected
Deep discharge
protection
[Yes] [No]
If set to Yes, the UPS
automatically
prevents battery pack
from deep discharge
by adapting end of
back-up time voltage
threshold. Warranty
void if set to No.
[Yes]
Extended Battery Modules (EBMs)
Up to four EBMs can be connected to the UPS.
Part number
Description
55949BX
Additional Extended Battery Module
14
Installation and User's Guide